Victron Battery
Victron
Registers (84)
84 read / 0 write
| Name | Address | Function | Type | Unit | Access |
|---|---|---|---|---|---|
voltage Battery.ChannelId.VOLTAGE (FC3ReadRegistersTask) | 259 | FC03 | uint16 | V | R |
starter_battery_voltage VictronBattery.ChannelId.STARTER_BATTERY_VOLTAGE (FC3ReadRegistersTask) | 260 | FC03 | uint16 | V | R |
current Battery.ChannelId.CURRENT (FC3ReadRegistersTask) | 261 | FC03 | int16 | A | R |
temperature VictronBattery.ChannelId.TEMPERATURE (FC3ReadRegistersTask) | 262 | FC03 | int16 | °C | R |
mid_voltage VictronBattery.ChannelId.MID_VOLTAGE (FC3ReadRegistersTask) | 263 | FC03 | uint16 | V | R |
mid_voltage_deviation VictronBattery.ChannelId.MID_VOLTAGE_DEVIATION (FC3ReadRegistersTask) | 264 | FC03 | uint16 | R | |
consumed_amphours VictronBattery.ChannelId.CONSUMED_AMPHOURS (FC3ReadRegistersTask) | 265 | FC03 | uint16 | R | |
soc Battery.ChannelId.SOC (FC3ReadRegistersTask) | 266 | FC03 | uint16 | % | R |
alarm VictronBattery.ChannelId.ALARM (FC3ReadRegistersTask) | 267 | FC03 | uint16 | R | |
low_voltage_alarm VictronBattery.ChannelId.LOW_VOLTAGE_ALARM (FC3ReadRegistersTask) | 268 | FC03 | uint16 | R | |
high_voltage_alarm VictronBattery.ChannelId.HIGH_VOLTAGE_ALARM (FC3ReadRegistersTask) | 269 | FC03 | uint16 | R | |
low_starter_voltage_alarm VictronBattery.ChannelId.LOW_STARTER_VOLTAGE_ALARM (FC3ReadRegistersTask) | 270 | FC03 | uint16 | R | |
high_starter_voltage_alarm VictronBattery.ChannelId.HIGH_STARTER_VOLTAGE_ALARM (FC3ReadRegistersTask) | 271 | FC03 | uint16 | R | |
low_state_of_charge_alarm VictronBattery.ChannelId.LOW_STATE_OF_CHARGE_ALARM (FC3ReadRegistersTask) | 272 | FC03 | uint16 | R | |
low_temperature_alarm VictronBattery.ChannelId.LOW_TEMPERATURE_ALARM (FC3ReadRegistersTask) | 273 | FC03 | uint16 | R | |
high_temperature_alarm VictronBattery.ChannelId.HIGH_TEMPERATURE_ALARM (FC3ReadRegistersTask) | 274 | FC03 | uint16 | R | |
mid_voltage_alarm VictronBattery.ChannelId.MID_VOLTAGE_ALARM (FC3ReadRegistersTask) | 275 | FC03 | uint16 | R | |
low_fused_voltage_alarm VictronBattery.ChannelId.LOW_FUSED_VOLTAGE_ALARM (FC3ReadRegistersTask) | 276 | FC03 | uint16 | R | |
high_fused_voltage_alarm VictronBattery.ChannelId.HIGH_FUSED_VOLTAGE_ALARM (FC3ReadRegistersTask) | 277 | FC03 | uint16 | R | |
fuse_blown_alarm VictronBattery.ChannelId.FUSE_BLOWN_ALARM (FC3ReadRegistersTask) | 278 | FC03 | uint16 | R | |
high_internal_temperature_alarm VictronBattery.ChannelId.HIGH_INTERNAL_TEMPERATURE_ALARM (FC3ReadRegistersTask) | 279 | FC03 | uint16 | R | |
relay_status VictronBattery.ChannelId.RELAY_STATUS (FC3ReadRegistersTask) | 280 | FC03 | uint16 | R | |
deepest_discharge VictronBattery.ChannelId.DEEPEST_DISCHARGE (FC3ReadRegistersTask) | 281 | FC03 | uint16 | R | |
last_discharge VictronBattery.ChannelId.LAST_DISCHARGE (FC3ReadRegistersTask) | 282 | FC03 | uint16 | R | |
average_discharge VictronBattery.ChannelId.AVERAGE_DISCHARGE (FC3ReadRegistersTask) | 283 | FC03 | uint16 | R | |
charge_cycles VictronBattery.ChannelId.CHARGE_CYCLES (FC3ReadRegistersTask) | 284 | FC03 | uint16 | R | |
full_discharges VictronBattery.ChannelId.FULL_DISCHARGES (FC3ReadRegistersTask) | 285 | FC03 | uint16 | R | |
total_amphours_drawn VictronBattery.ChannelId.TOTAL_AMPHOURS_DRAWN (FC3ReadRegistersTask) | 286 | FC03 | uint16 | R | |
history_min_voltage VictronBattery.ChannelId.HISTORY_MIN_VOLTAGE (FC3ReadRegistersTask) | 287 | FC03 | uint16 | V | R |
history_max_voltage VictronBattery.ChannelId.HISTORY_MAX_VOLTAGE (FC3ReadRegistersTask) | 288 | FC03 | uint16 | V | R |
time_since_last_full_charge VictronBattery.ChannelId.TIME_SINCE_LAST_FULL_CHARGE (FC3ReadRegistersTask) | 289 | FC03 | uint16 | R | |
automatic_syncs VictronBattery.ChannelId.AUTOMATIC_SYNCS (FC3ReadRegistersTask) | 290 | FC03 | uint16 | R | |
low_voltage_alarms VictronBattery.ChannelId.LOW_VOLTAGE_ALARMS (FC3ReadRegistersTask) | 291 | FC03 | uint16 | R | |
high_voltage_alarms VictronBattery.ChannelId.HIGH_VOLTAGE_ALARMS (FC3ReadRegistersTask) | 292 | FC03 | uint16 | R | |
low_starter_voltage_alarms VictronBattery.ChannelId.LOW_STARTER_VOLTAGE_ALARMS (FC3ReadRegistersTask) | 293 | FC03 | uint16 | R | |
high_starter_voltage_alarms VictronBattery.ChannelId.HIGH_STARTER_VOLTAGE_ALARMS (FC3ReadRegistersTask) | 294 | FC03 | uint16 | R | |
min_starter_voltage VictronBattery.ChannelId.MIN_STARTER_VOLTAGE (FC3ReadRegistersTask) | 295 | FC03 | uint16 | V | R |
max_starter_voltage VictronBattery.ChannelId.MAX_STARTER_VOLTAGE (FC3ReadRegistersTask) | 296 | FC03 | uint16 | V | R |
low_fused_voltage_alarms VictronBattery.ChannelId.LOW_FUSED_VOLTAGE_ALARMS (FC3ReadRegistersTask) | 297 | FC03 | uint16 | R | |
high_fused_voltage_alarms VictronBattery.ChannelId.HIGH_FUSED_VOLTAGE_ALARMS (FC3ReadRegistersTask) | 298 | FC03 | uint16 | R | |
min_fused_voltage VictronBattery.ChannelId.MIN_FUSED_VOLTAGE (FC3ReadRegistersTask) | 299 | FC03 | uint16 | V | R |
max_fused_voltage VictronBattery.ChannelId.MAX_FUSED_VOLTAGE (FC3ReadRegistersTask) | 300 | FC03 | uint16 | V | R |
dc_discharged_energy VictronBattery.ChannelId.DC_DISCHARGED_ENERGY (FC3ReadRegistersTask) | 301 | FC03 | uint16 | Wh | R |
dc_charged_energy VictronBattery.ChannelId.DC_CHARGED_ENERGY (FC3ReadRegistersTask) | 302 | FC03 | uint16 | Wh | R |
time_to_go VictronBattery.ChannelId.TIME_TO_GO (FC3ReadRegistersTask) | 303 | FC03 | uint16 | R | |
soh Battery.ChannelId.SOH (FC3ReadRegistersTask) | 304 | FC03 | uint16 | % | R |
charge_max_voltage Battery.ChannelId.CHARGE_MAX_VOLTAGE (FC3ReadRegistersTask) | 305 | FC03 | uint16 | V | R |
discharge_min_voltage Battery.ChannelId.DISCHARGE_MIN_VOLTAGE (FC3ReadRegistersTask) | 306 | FC03 | uint16 | V | R |
charge_max_current Battery.ChannelId.CHARGE_MAX_CURRENT (FC3ReadRegistersTask) | 307 | FC03 | uint16 | A | R |
discharge_max_current Battery.ChannelId.DISCHARGE_MAX_CURRENT (FC3ReadRegistersTask) | 308 | FC03 | uint16 | A | R |
capacity_in_amphours VictronBattery.ChannelId.CAPACITY_IN_AMPHOURS (FC3ReadRegistersTask) | 309 | FC03 | uint16 | R | |
timestamp_1st_last_error VictronBattery.ChannelId.TIMESTAMP_1ST_LAST_ERROR (FC3ReadRegistersTask) | 310 | FC03 | int32 | R | |
timestamp_2nd_last_error VictronBattery.ChannelId.TIMESTAMP_2ND_LAST_ERROR (FC3ReadRegistersTask) | 312 | FC03 | int32 | R | |
timestamp_3rd_last_error VictronBattery.ChannelId.TIMESTAMP_3RD_LAST_ERROR (FC3ReadRegistersTask) | 314 | FC03 | int32 | R | |
timestamp_4th_last_error VictronBattery.ChannelId.TIMESTAMP_4TH_LAST_ERROR (FC3ReadRegistersTask) | 316 | FC03 | int32 | R | |
min_cell_temperature Battery.ChannelId.MIN_CELL_TEMPERATURE (FC3ReadRegistersTask) | 318 | FC03 | int16 | °C | R |
max_cell_temperature Battery.ChannelId.MAX_CELL_TEMPERATURE (FC3ReadRegistersTask) | 319 | FC03 | int16 | °C | R |
high_charge_current_alarm VictronBattery.ChannelId.HIGH_CHARGE_CURRENT_ALARM (FC3ReadRegistersTask) | 320 | FC03 | uint16 | R | |
high_discharge_current_alarm VictronBattery.ChannelId.HIGH_DISCHARGE_CURRENT_ALARM (FC3ReadRegistersTask) | 321 | FC03 | uint16 | R | |
cell_imbalance_alarm VictronBattery.ChannelId.CELL_IMBALANCE_ALARM (FC3ReadRegistersTask) | 322 | FC03 | uint16 | R | |
internal_failure_alarm VictronBattery.ChannelId.INTERNAL_FAILURE_ALARM (FC3ReadRegistersTask) | 323 | FC03 | uint16 | R | |
high_charge_temperature_alarm VictronBattery.ChannelId.HIGH_CHARGE_TEMPERATURE_ALARM (FC3ReadRegistersTask) | 324 | FC03 | uint16 | R | |
low_charge_temperature_alarm VictronBattery.ChannelId.LOW_CHARGE_TEMPERATURE_ALARM (FC3ReadRegistersTask) | 325 | FC03 | uint16 | R | |
low_cell_voltage_alarm VictronBattery.ChannelId.LOW_CELL_VOLTAGE_ALARM (FC3ReadRegistersTask) | 326 | FC03 | uint16 | R | |
victron_state VictronBattery.ChannelId.VICTRON_STATE (FC3ReadRegistersTask) | 1282 | FC03 | uint16 | R | |
error VictronBattery.ChannelId.ERROR (FC3ReadRegistersTask) | 1283 | FC03 | uint16 | R | |
system_switch VictronBattery.ChannelId.SYSTEM_SWITCH (FC3ReadRegistersTask) | 1284 | FC03 | uint16 | R | |
balancing VictronBattery.ChannelId.BALANCING (FC3ReadRegistersTask) | 1285 | FC03 | uint16 | R | |
number_of_batteries VictronBattery.ChannelId.NUMBER_OF_BATTERIES (FC3ReadRegistersTask) | 1286 | FC03 | uint16 | R | |
batteries_parallel VictronBattery.ChannelId.BATTERIES_PARALLEL (FC3ReadRegistersTask) | 1287 | FC03 | uint16 | R | |
batteries_series VictronBattery.ChannelId.BATTERIES_SERIES (FC3ReadRegistersTask) | 1288 | FC03 | uint16 | R | |
number_of_cells_per_battery VictronBattery.ChannelId.NUMBER_OF_CELLS_PER_BATTERY (FC3ReadRegistersTask) | 1289 | FC03 | uint16 | R | |
min_cell_voltage Battery.ChannelId.MIN_CELL_VOLTAGE (FC3ReadRegistersTask) | 1290 | FC03 | uint16 | mV | R |
max_cell_voltage Battery.ChannelId.MAX_CELL_VOLTAGE (FC3ReadRegistersTask) | 1291 | FC03 | uint16 | mV | R |
shutdowns_due_error VictronBattery.ChannelId.SHUTDOWNS_DUE_ERROR (FC3ReadRegistersTask) | 1292 | FC03 | uint16 | R | |
diagnostics_1st_last_error VictronBattery.ChannelId.DIAGNOSTICS_1ST_LAST_ERROR (FC3ReadRegistersTask) | 1293 | FC03 | uint16 | R | |
diagnostics_2nd_last_error VictronBattery.ChannelId.DIAGNOSTICS_2ND_LAST_ERROR (FC3ReadRegistersTask) | 1294 | FC03 | uint16 | R | |
diagnostics_3rd_last_error VictronBattery.ChannelId.DIAGNOSTICS_3RD_LAST_ERROR (FC3ReadRegistersTask) | 1295 | FC03 | uint16 | R | |
diagnostics_4th_last_error VictronBattery.ChannelId.DIAGNOSTICS_4TH_LAST_ERROR (FC3ReadRegistersTask) | 1296 | FC03 | uint16 | R | |
allow_to_charge VictronBattery.ChannelId.ALLOW_TO_CHARGE (FC3ReadRegistersTask) | 1297 | FC03 | uint16 | R | |
allow_to_discharge VictronBattery.ChannelId.ALLOW_TO_DISCHARGE (FC3ReadRegistersTask) | 1298 | FC03 | uint16 | R | |
external_relay VictronBattery.ChannelId.EXTERNAL_RELAY (FC3ReadRegistersTask) | 1299 | FC03 | uint16 | R | |
history_min_cell_voltage VictronBattery.ChannelId.HISTORY_MIN_CELL_VOLTAGE (FC3ReadRegistersTask) | 1300 | FC03 | uint16 | V | R |
history_max_cell_voltage VictronBattery.ChannelId.HISTORY_MAX_CELL_VOLTAGE (FC3ReadRegistersTask) | 1301 | FC03 | uint16 | V | R |
Use directly in ModbusCloud