APC Smart-UPS SMT
APC
Reads APC Smart-UPS status and battery data via Modbus RTU.
Overzicht
Belangrijke uitlezingen
- Battery Voltage
- Battery Charge State
- Remaining Run Time
- Input Voltage
- Output Voltage and Frequency
- Battery Temperature

APC
Reads APC Smart-UPS status and battery data via Modbus RTU.
10 lezen / 0 schrijven
| Naam | Adres | Functie | Type | Eenheid | Toegang |
|---|---|---|---|---|---|
Battery Voltage | 131 | FC03 | uint16 | V DC | R |
Output Frequency | 144 | FC03 | uint16 | Hz | R |
Battery Charge State | 130 | FC03 | uint16 | % | R |
Input Voltage | 151 | FC03 | uint16 | V AC | R |
UPS Status Display (0-OK >0 Error) | 26 | FC03 | uint16 | R | |
Remaining Run Time | 128 | FC03 | uint32 | min. | R |
Battery Temperature | 135 | FC03 | int16 | °C | R |
Utilisation | 136 | FC03 | uint16 | % | R |
Output Voltage | 142 | FC03 | uint16 | V | R |
Supply Drop Out | 18 | FC03 | uint16 | R |
Importeer deze template met een klik in je eigen portaal of neem contact op voor begeleiding bij de installatie.

Alnor Systemy Wentylacji Sp. z o. o.
Controls and monitors Alnor heat recovery ventilation units via Modbus RTU.
AMPERFIED GmbH
Controls and monitors Heidelberg Wallbox Energy Control EV charger via Modbus RTU.

connecdoor
Controls and monitors smart door access points via RS485

Wattsonic
Monitors Schmachtl Wattsonic hybrid inverter via Modbus RTU

Alnor Systemy Wentylacji Sp. z o. o.
Controls Alnor HRU-P heat recovery ventilation units via Modbus RTU.

E+E Elektronik
Measures differential air pressure for HVAC and filter monitoring applications.