system_state Overall system operating state, encoded as enumeration. | 100 | FC03 | uint16 | | R |
control_mode Active control mode of the energy storage system. | 101 | FC03 | uint16 | | R |
work_mode Current work mode reported by the system. | 102 | FC03 | uint16 | | R |
active_charge_energy Cumulative AC energy charged into the battery, watt-hours. | 104 | FC03 | uint32 | Wh | R |
active_discharge_energy Cumulative AC energy discharged from the battery, watt-hours. | 106 | FC03 | uint32 | Wh | R |
battery_group_state Operational state of the battery group, enumeration. | 108 | FC03 | uint16 | | R |
soc Battery state of charge, 0 to 100 percent. | 109 | FC03 | uint16 | % | R |
battery_voltage DC battery pack voltage, volts. | 110 | FC03 | uint16 | V | R |
battery_current DC battery current, positive charging, negative discharging. | 111 | FC03 | int16 | A | R |
battery_power DC battery power, positive charging, negative discharging. | 112 | FC03 | int16 | W | R |
pcs_operation_state Power conversion system operational state, enumeration. | 114 | FC03 | uint16 | | R |
current_l1 AC phase L1 current, amperes, signed. | 118 | FC03 | int16 | A | R |
current_l2 AC phase L2 current, amperes, signed. | 119 | FC03 | int16 | A | R |
current_l3 AC phase L3 current, amperes, signed. | 120 | FC03 | int16 | A | R |
voltage_l1 AC phase L1 voltage to neutral, volts. | 121 | FC03 | uint16 | V | R |
voltage_l2 AC phase L2 voltage to neutral, volts. | 122 | FC03 | uint16 | V | R |
voltage_l3 AC phase L3 voltage to neutral, volts. | 123 | FC03 | uint16 | V | R |
active_power_l1 AC active power on phase L1, watts, signed. | 124 | FC03 | int16 | W | R |
active_power_l2 AC active power on phase L2, watts, signed. | 125 | FC03 | int16 | W | R |
active_power_l3 AC active power on phase L3, watts, signed. | 126 | FC03 | int16 | W | R |
reactive_power_l1 AC reactive power on phase L1, signed. | 127 | FC03 | int16 | W | R |
reactive_power_l2 AC reactive power on phase L2, signed. | 128 | FC03 | int16 | W | R |
reactive_power_l3 AC reactive power on phase L3, signed. | 129 | FC03 | int16 | W | R |
frequency_l1 AC grid frequency measured on phase L1. | 131 | FC03 | uint16 | Hz | R |
frequency_l2 AC grid frequency measured on phase L2. | 132 | FC03 | uint16 | Hz | R |
frequency_l3 AC grid frequency measured on phase L3. | 133 | FC03 | uint16 | Hz | R |
single_phase_allowed_apparent Maximum allowed apparent power for a single phase. | 134 | FC03 | uint16 | VA | R |
allowed_charge_power Maximum charge power currently permitted by the BMS, watts. | 141 | FC03 | uint16 | W | R |
allowed_discharge_power Maximum discharge power currently permitted by the BMS, watts. | 142 | FC03 | uint16 | W | R |
set_work_state Setpoint to command the system work state, enumeration. | 200 | FC16 | uint16 | | W |
set_active_power_l1 Active power setpoint for phase L1, watts, signed. | 206 | FC16 | int16 | W | W |
set_reactive_power_l1 Reactive power setpoint for phase L1, signed. | 207 | FC16 | int16 | W | W |
set_active_power_l2 Active power setpoint for phase L2, watts, signed. | 208 | FC16 | int16 | W | W |
set_reactive_power_l2 Reactive power setpoint for phase L2, signed. | 209 | FC16 | int16 | W | W |
set_active_power_l3 Active power setpoint for phase L3, watts, signed. | 210 | FC16 | int16 | W | W |
set_reactive_power_l3 Reactive power setpoint for phase L3, signed. | 211 | FC16 | int16 | W | W |
battery_voltage_section_1 Voltage of battery cell section 1, raw value. | 3020 | FC03 | uint16 | V | R |
battery_voltage_section_2 Voltage of battery cell section 2, raw value. | 3021 | FC03 | uint16 | V | R |
battery_voltage_section_3 Voltage of battery cell section 3, raw value. | 3022 | FC03 | uint16 | V | R |
battery_voltage_section_4 Voltage of battery cell section 4, raw value. | 3023 | FC03 | uint16 | V | R |
battery_voltage_section_5 Voltage of battery cell section 5, raw value. | 3024 | FC03 | uint16 | V | R |
battery_voltage_section_6 Voltage of battery cell section 6, raw value. | 3025 | FC03 | uint16 | V | R |
battery_voltage_section_7 Voltage of battery cell section 7, raw value. | 3026 | FC03 | uint16 | V | R |
battery_voltage_section_8 Voltage of battery cell section 8, raw value. | 3027 | FC03 | uint16 | V | R |
battery_voltage_section_9 Voltage of battery cell section 9, raw value. | 3028 | FC03 | uint16 | V | R |
battery_voltage_section_10 Voltage of battery cell section 10, raw value. | 3029 | FC03 | uint16 | V | R |
battery_voltage_section_11 Voltage of battery cell section 11, raw value. | 3030 | FC03 | uint16 | V | R |
battery_voltage_section_12 Voltage of battery cell section 12, raw value. | 3031 | FC03 | uint16 | V | R |
battery_voltage_section_13 Voltage of battery cell section 13, raw value. | 3032 | FC03 | uint16 | V | R |
battery_voltage_section_14 Voltage of battery cell section 14, raw value. | 3033 | FC03 | uint16 | V | R |
battery_voltage_section_15 Voltage of battery cell section 15, raw value. | 3034 | FC03 | uint16 | V | R |
battery_voltage_section_16 Voltage of battery cell section 16, raw value. | 3035 | FC03 | uint16 | V | R |
battery_temperature_section_1 Temperature of battery cell section 1, raw value. | 3036 | FC03 | uint16 | °C | R |
battery_temperature_section_2 Temperature of battery cell section 2, raw value. | 3037 | FC03 | uint16 | °C | R |
battery_temperature_section_3 Temperature of battery cell section 3, raw value. | 3038 | FC03 | uint16 | °C | R |
battery_temperature_section_4 Temperature of battery cell section 4, raw value. | 3039 | FC03 | uint16 | °C | R |
battery_temperature_section_5 Temperature of battery cell section 5, raw value. | 3040 | FC03 | uint16 | °C | R |
battery_temperature_section_6 Temperature of battery cell section 6, raw value. | 3041 | FC03 | uint16 | °C | R |
battery_temperature_section_7 Temperature of battery cell section 7, raw value. | 3042 | FC03 | uint16 | °C | R |
battery_temperature_section_8 Temperature of battery cell section 8, raw value. | 3043 | FC03 | uint16 | °C | R |
battery_temperature_section_9 Temperature of battery cell section 9, raw value. | 3044 | FC03 | uint16 | °C | R |
battery_temperature_section_10 Temperature of battery cell section 10, raw value. | 3045 | FC03 | uint16 | °C | R |
battery_temperature_section_11 Temperature of battery cell section 11, raw value. | 3046 | FC03 | uint16 | °C | R |
battery_temperature_section_12 Temperature of battery cell section 12, raw value. | 3047 | FC03 | uint16 | °C | R |
battery_temperature_section_13 Temperature of battery cell section 13, raw value. | 3048 | FC03 | uint16 | °C | R |
battery_temperature_section_14 Temperature of battery cell section 14, raw value. | 3049 | FC03 | uint16 | °C | R |
battery_temperature_section_15 Temperature of battery cell section 15, raw value. | 3050 | FC03 | uint16 | °C | R |
battery_temperature_section_16 Temperature of battery cell section 16, raw value. | 3051 | FC03 | uint16 | °C | R |
rtc_year Real-time clock year setpoint for system time sync. | 9014 | FC16 | uint16 | | W |
rtc_month Real-time clock month setpoint for system time sync. | 9015 | FC16 | uint16 | | W |
rtc_day Real-time clock day setpoint for system time sync. | 9016 | FC16 | uint16 | | W |
rtc_hour Real-time clock hour setpoint for system time sync. | 9017 | FC16 | uint16 | | W |
rtc_minute Real-time clock minute setpoint for system time sync. | 9018 | FC16 | uint16 | | W |
rtc_second Real-time clock second setpoint for system time sync. | 9019 | FC16 | uint16 | | W |
setup_mode_a Setup mode write register, activates or deactivates setup state. | 30558 | FC16 | uint16 | | W |
pcs_mode_a PCS mode write register, switches PCS between local and remote control. | 30559 | FC16 | uint16 | | W |
setup_mode_b Setup mode read-back register, confirms current setup state. | 30157 | FC03 | uint16 | | R |
pcs_mode_b PCS mode read-back register, confirms current PCS control mode. | 30158 | FC03 | uint16 | | R |