Actuator type | 3 | FC03 | uint16 | | R |
Relative position | 4 | FC03 | uint16 | % | R |
Absolute position | 5 | FC03 | uint16 | ° | R |
Relative volumetric flow | 6 | FC03 | uint16 | % | R |
Absolute volumetric flow in selected unit | 9 | FC03 | uint32 | l/h | R |
Setpoint analog | 11 | FC03 | uint16 | % | R |
Temperature 1 in degree Celsius | 19 | FC03 | int16 | °C | R |
Temperature 1 in degree Fahrenheit | 20 | FC03 | int16 | °F | R |
Temperature 2 in degree Celsius | 21 | FC03 | int16 | °C | R |
Temperature 2 in degree Fahrenheit | 22 | FC03 | int16 | °F | R |
DeltaT_K | 23 | FC03 | uint16 | K | R |
DeltaT_F | 24 | FC03 | uint16 | °F | R |
Glycol concentration | 25 | FC03 | uint16 | % | R |
Relative power | 26 | FC03 | uint16 | % | R |
Series Number 1st part | 100 | FC03 | uint16 | | R |
Series Number 2nd part | 101 | FC03 | uint16 | | R |
Series Number 4th part | 102 | FC03 | uint16 | | R |
Firmware version | 103 | FC03 | uint16 | | R |
Error state | 157 | FC03 | uint32 | | R |
DeltaT Manager Status | 180 | FC03 | uint16 | | R |
Absolute volumetric flow in liter per second | 7 | FC03 | uint16 | l/s | R |
Absolute volumetric flow in gpm | 8 | FC03 | uint16 | gpm | R |
Setpoint flow in selected unit | 17 | FC03 | uint32 | l/h | R |
Absolute Power Cooling in selected unit | 31 | FC03 | uint32 | kW | R |
Absolute Power Cooling in kW | 27 | FC03 | uint32 | kW | R |
Absolute Power Cooling in kBtu per hour | 29 | FC03 | uint32 | kBtu/h | R |
Energy Cooling in selected unit | 69 | FC03 | uint32 | kWh | R |
Energy Cooling in kWh | 65 | FC03 | uint32 | kWh | R |
Energy Cooling in kBtu | 67 | FC03 | uint32 | kBtu | R |
Energy Heating in selected unit | 75 | FC03 | uint32 | kWh | R |
Energy Heating in kWh | 71 | FC03 | uint32 | kWh | R |
Energy Heating in kBtu | 73 | FC03 | uint32 | kBtu | R |
Nominal volumetric flow in selected unit | 112 | FC03 | uint32 | l/h | R |
Nominal volumetric flow in liter per second | 110 | FC03 | uint16 | l/s | R |
Nominal volumetric flow in gpm | 111 | FC03 | uint16 | gpm | R |
Nominal power in selected unit | 163 | FC03 | uint32 | kW | R |
Nominal power in kW | 159 | FC03 | uint32 | kW | R |
Nominal power in kBtu per hour | 161 | FC03 | uint32 | kBtu/h | R |
Setpoint flow in liter per second | 15 | FC03 | uint16 | l/s | R |
Setpoint flow in gpm | 16 | FC03 | uint16 | gpm | R |
Absolute Power Heating in kW | 33 | FC03 | uint32 | kW | R |
Absolute Power Heating in kBtu per hour | 35 | FC03 | uint32 | kbtu/h | R |
Absolute Power Heating in selected unit | 37 | FC03 | uint32 | kW | R |
Sensor Serial Number 1st Part | 200 | FC03 | uint32 | | R |
Sensor Serial Number 2nd Part | 202 | FC03 | uint32 | | R |
Sensor value 1 | 12 | FC03 | uint16 | | R |
Sensor 1 value in degree Celcius | 13 | FC03 | int16 | °C | R |
Sensor 1 value in degree Fahrenheit | 14 | FC03 | int16 | °F | R |
Total volume in cubic meter | 59 | FC03 | uint32 | m3 | R |
Total volume in gallon | 61 | FC03 | uint32 | gal | R |
Total volume in selected unit | 63 | FC03 | uint32 | m3 | R |
Bus termination | 99 | FC03 | uint16 | | R |
Absolute differential water pressure in selected unit | 47 | FC03 | int32 | bar | R |
Relative water differential pressure | 49 | FC03 | int32 | % | R |
Absolute differential water pressure in psi | 51 | FC03 | int32 | psi | R |
Absolute differential water pressure in kPa | 57 | FC03 | int32 | kPa | R |
Status of the differential water pressure sensor | 181 | FC03 | uint16 | | R |
Differential water pressure control status | 182 | FC03 | uint16 | | R |
Nominal differential water pressure in selected unit | 184 | FC03 | uint32 | bar | R |
Nominal differential water pressure in psi | 186 | FC03 | uint32 | psi | R |
Nominal differential water pressure in kPa | 188 | FC03 | uint32 | kPa | R |
Malfunction and service information | 104 | FC03 | uint16 | | R |
Setpoint | 0 | FC06 | uint16 | % | W |
Override control | 1 | FC06 | uint16 | | W |
Vmax in percent of Vnom | 106 | FC06 | uint16 | % | W |
Pmax in percent of Pnom | 165 | FC06 | uint16 | % | W |
Delta T Limitation | 179 | FC06 | uint16 | | W |
Setpoint DeltaT in K | 39 | FC06 | uint16 | K | W |
Setpoint DeltaT in F | 40 | FC06 | uint16 | °F | W |
Control Mode | 116 | FC06 | uint16 | | W |
Unit Selection Flow | 147 | FC06 | uint16 | | W |
Unit Selection Power | 148 | FC06 | uint16 | | W |
Unit Selection Energy | 150 | FC06 | uint16 | | W |
Setpoint Source | 118 | FC06 | uint16 | | W |
Absolute Vmax in liter per second | 133 | FC06 | uint16 | l/s | W |
Absolute Vmax in gpm | 134 | FC06 | uint16 | gpm | W |
Absolute Pmax in kW | 166 | FC16 | uint32 | kW | W |
Absolute Pmax in kBtu per hour | 168 | FC16 | uint32 | kBtu/h | W |
Vmin in percent of Vmax | 105 | FC06 | uint16 | % | W |
Absolute Vmax in selected unit | 135 | FC16 | uint32 | l/h | W |
Absolute Vmin in liter per second | 129 | FC06 | uint16 | l/s | W |
Absolute Vmin in gpm | 130 | FC06 | uint16 | gpm | W |
Absolute Vmin in selected unit | 131 | FC16 | uint32 | l/h | W |
Absolute Pmax in selected unit | 170 | FC16 | uint32 | kW | W |
Unit Selection Volume | 149 | FC06 | uint16 | | W |
Select Meter Register | 204 | FC06 | uint16 | | W |
Command | 2 | FC06 | uint16 | | W |
Setpoint Flow at DeltaT in liter per second | 41 | FC16 | uint32 | l/s | W |
Setpoint Flow at DeltaT in gpm | 43 | FC16 | uint32 | gpm | W |
Setpoint Flow at DeltaT in selected unit | 45 | FC16 | uint32 | l/h | W |
Communication Watchdog | 109 | FC06 | uint16 | | W |
Sensor 1 Type | 120 | FC06 | uint16 | | W |
Sensor 1 Passive Sensor Type | 121 | FC06 | uint16 | | W |
Unit selection pressure difference | 151 | FC06 | uint16 | | W |
Absolute differential water pressure setpoint in selected unit | 172 | FC16 | uint32 | bar | W |
Absolute differential water pressure setpoint in psi | 174 | FC16 | uint32 | psi | W |
Absolute differential water pressure setpoint in kPa | 176 | FC16 | uint32 | kPa | W |
Bus watchdog fail action | 108 | FC06 | uint16 | | W |