ONOKOM AIR AUX-1-MB-B
Onokom
Controls AUX air conditioners via the ONOKOM AUX-1-MB-B Modbus gateway
Overzicht
Belangrijke uitlezingen
- Indoor air temperature
- Outdoor air temperature
- AC connected
- Current fan speed
- Turbo mode status
- Sleep mode status

Onokom
Controls AUX air conditioners via the ONOKOM AUX-1-MB-B Modbus gateway
13 lezen / 15 schrijven
| Naam | Adres | Functie | Type | Eenheid | Toegang |
|---|---|---|---|---|---|
Indoor air temperature | 3 | FC03 | uint16 | °C | R |
Outdoor air temperature | 4 | FC03 | int16 | °C | R |
AC connected | 20 | FC01 | uint16 | R | |
Screen light (Status) | 2 | FC01 | uint16 | R/W | |
Mold protection (Status) | 11 | FC01 | uint16 | R/W | |
Ionization (Status) | 9 | FC01 | uint16 | R/W | |
Self cleaning (Status) | 10 | FC01 | uint16 | R/W | |
Sleep mode (Status) | 8 | FC01 | uint16 | R/W | |
Vertical vanes (Status) | 10 | FC03 | uint16 | R/W | |
Current fan speed (Status) | 32 | FC03 | uint16 | R | |
Quiet mode (Status) | 4 | FC02 | uint16 | R | |
Turbo mode (Status) | 7 | FC02 | uint16 | R/W | |
Horizontal vanes | 9 | FC03 | uint16 | R/W | |
Active (Control) | 1 | FC05 | uint16 | W | |
Loxone modes (Control) | 15 | FC06 | uint16 | W | |
Smart fan speed | 8 | FC06 | uint16 | W | |
Target temperature | 5 | FC06 | int16 | °C | W |
Modbus address (Service) | 128 | FC06 | uint16 | W | |
Quiet mode (Control) | 5 | FC05 | uint16 | W | |
Vanes swing | 11 | FC06 | uint16 | W |
ModbusCloud is het hardware- en softwareplatform waarmee installateurs Modbus-apparaten monitoren, visualiseren en aansturen vanuit één portaal. Dit sjabloon is één van honderden die je direct kunt gebruiken.

Onokom
Controls Gree air conditioners via the ONOKOM GR-1-MB-B Modbus gateway.

Onokom
Controls TCL air conditioners via the ONOKOM TCL-6-MB-B Modbus gateway.

Onokom
Controls Hisense air conditioners via the ONOKOM HS-5-MB-B Modbus gateway.

Onokom
Controls Hitachi air conditioners via the ONOKOM HS-3-MB-B gateway over Modbus RTU.

Onokom
Controls Daikin air conditioners via the ONOKOM DK-5-MB-B Modbus gateway.

Onokom
Controls Hisense air conditioners via the ONOKOM HS-3-MB-B Modbus gateway.

Alnor Systemy Wentylacji Sp. z o. o.
Controls Alnor HRU-P heat recovery ventilation units via Modbus RTU.

Alnor Systemy Wentylacji Sp. z o. o.
Controls and monitors Alnor heat recovery ventilation units via Modbus RTU.

Wattsonic
Monitors Schmachtl Wattsonic hybrid inverter via Modbus RTU
AMPERFIED GmbH
Controls and monitors Heidelberg Wallbox Energy Control EV charger via Modbus RTU.

connecdoor
Controls and monitors smart door access points via RS485

Belimo