Room temperature heating circuit 1 | 149 | FC03 | int16 | °C | R/W |
Room temperature heating circuit 2 | 150 | FC03 | int16 | °C | R/W |
Relative humidity heating circuit 1 | 159 | FC03 | uint16 | % | R/W |
Relative humidity heating circuit 2 | 160 | FC03 | uint16 | % | R/W |
Heat pump operating status (0) Off, (1) Heating, (2) Cooling, (3) DHW, (4) Defrost, (5) PSU outage, (6) Manual heating, (7) Manual cooling, (8) Bivalent interlock, (9) Operating mode changeover, (10) Operating mode changeover, (11) Pump pre-run time, (12) Standby, (13) Pump run-on time, (14) Fault, (15) Current limit, (16) Standby, (17) Operating program switched off, (18) Minimum time off, (19) Minimum time on, (20) Minimum system pressure | 50 | FC03 | uint16 | | R |
Target operating mode: plant (0) Off, (1) Heating, (2) Cooling | 11 | FC03 | uint16 | | R |
Target heating_cooling temperature | 12 | FC03 | uint16 | °C | R |
System operating status (0) Off, (1) Heating, (2) Domestic hot water, (3) Cooling, (4) Defrost, (5) Defrost | 49 | FC03 | uint16 | | R |
Auxiliary heater operating status (0) Standby, (1) Heating, (2) Standby, (3) DHW, (4) Bivalent interlock, (5) Fault, (6) Frost protection mode, (7) Maximum temperature shutdown, (8) PSU outage, (9) DHW, (10) Operating program switched off, (11) Minimum system pressure, (12) Pump pre-run time, (13) Pump run-on time | 59 | FC03 | uint16 | | R |
Target operating mode: DHW (0) Off, (1) On | 13 | FC03 | uint16 | | R |
Target DHW temperature | 14 | FC03 | uint16 | °C | R |
Switch-ON differential: DHW | 15 | FC03 | int16 | K | R |
Room temperature heating circuit 3 | 151 | FC03 | int16 | °C | R/W |
Room temperature heating circuit 4 | 152 | FC03 | int16 | °C | R/W |
Relative humidity heating circuit 3 | 161 | FC03 | uint16 | % | R/W |
Relative humidity heating circuit 4 | 162 | FC03 | uint16 | % | R/W |
Heat pump flow temperature | 34 | FC03 | int16 | °C | R |
Heat pump return temperature | 35 | FC03 | int16 | °C | R |
Flow rate, heat sink system | 36 | FC03 | uint16 | m³/h | R |
Buffer temperature top | 37 | FC03 | int16 | °C | R |
Flow temperature auxiliary heater | 39 | FC03 | int16 | °C | R |
System pressure, heat sink system | 40 | FC03 | uint16 | bar(g) | R |
Evaporator intake air temperature | 41 | FC03 | int16 | °C | R |
Evaporator discharge air temperature | 42 | FC03 | int16 | °C | R |
Outdoor temperature | 48 | FC03 | int16 | °C | R |
Compressor hours of operation | 79 | FC03 | uint32 | h | R |
Switching cycles, compressor | 81 | FC03 | uint32 | | R |
Hours of operation, auxiliary heater | 83 | FC03 | uint32 | h | R |
Switching cycles, auxiliary heater | 85 | FC03 | uint32 | | R |
Heat pump heating energy | 89 | FC03 | uint32 | kWh | R |
Heat pump cooling energy | 91 | FC03 | uint32 | kWh | R |
Heat pump DHW energy | 93 | FC03 | uint32 | kWh | R |
Heat pump defrosting energy | 95 | FC03 | uint32 | kWh | R |
Heat pump power demand heating | 97 | FC03 | uint32 | kWh | R |
Heat pump power demand cooling | 99 | FC03 | uint32 | kWh | R |
Heat pump power demand DHW | 101 | FC03 | uint32 | kWh | R |
Heat pump power demand defrosting | 103 | FC03 | uint32 | kWh | R |
Auxiliary heater heating energy | 119 | FC03 | uint32 | kWh | R |
Auxiliary heater DHW energy | 121 | FC03 | uint32 | kWh | R |
Auxiliary heater defrosting energy | 123 | FC03 | uint32 | kWh | R |
DHW temperature | 29 | FC03 | uint16 | °C | R |
Buffer temperature bottom | 38 | FC03 | int16 | °C | R |
Target operating mode: plant (0) Off, (1) Heating, (2) Cooling | 1 | FC06 | uint16 | | W |
Target heating_cooling temperature | 2 | FC06 | uint16 | °C | W |
Target operating mode: DHW (0) Off, (1) On | 3 | FC06 | uint16 | | W |
Target DHW temperature | 4 | FC06 | uint16 | °C | W |
Switch-ON differential: DHW | 5 | FC06 | int16 | K | W |