aqotec RM360 via Modbus RTU Modbus Extension RS485
Monitors and controls an Aqotec RM360 district heating substation controller via Modbus RTU
Template voor de Aqotec RM360 stadsverwarming onderstationregelaar via Modbus RTU over RS485. Het leest temperaturen, warmtemetergegevens, foutstatussen en bedrijfstoestanden voor maximaal vier verwarmingskringen en warmwatertanks. Het ondersteunt ook het schrijven van setpoints, modi en correctiewaarden.
- Protocol
- Modbus RTU
- Aansluiting
- RS485, 19200 baud
- Registers
- 98, lezen en schrijven
- Merk
- Aqotec
- Belangrijke uitlezingen
- Outdoor and flow/return temperatures · Primary valve position · Heatmeter energy, power, and flowrate · HC1 to HC4 operating status and setpoints · Error bytes 1 to 4 · Heatmeter volume and serial number
- Beschikbare commando's
- Main mode and HC1 to HC4 modes · HC1 to HC4 room setpoints and corrections · HC1 to HC4 outdoor switch-off temperatures · TC1 and TC2 hot water tank modes
- Ondersteunde modellen
- RM360
- Laatst bijgewerkt
Registers (98)
98 lezen, 29 schrijven
| Naam | Eenheid | Toegang | Adres (Verborgen tot je je e-mailadres invult) | Functie (verborgen) | Type (verborgen) |
|---|---|---|---|---|---|
| sensorvalue T10 outdoor | °C | Lezen | |||
| sensorvalue T11 prim. return | °C | Lezen | |||
| sensorvalue T12 sec. flow temperature | °C | Lezen | |||
| sensorvalue T15 sec. return temperature | °C | Lezen | |||
| setpoint sec. flow temperature | °C | Lezen | |||
| calculated primary-valve position | % | Lezen | |||
| actual used return limitation | °C | Lezen | |||
| operating status | Lezen | ||||
| main mode | Lezen en schrijven | ||||
| general-correction in reduction mode | K | Lezen en schrijven | |||
| general-correction in heating mode | K | Lezen en schrijven | |||
| Error-Byte 1 status | Lezen | ||||
| Error-Byte 2 status | Lezen | ||||
| Error-Byte 3 status | Lezen | ||||
| Error-Byte 4 status | Lezen | ||||
| Heatmeter energy in kWh | kWh | Lezen | |||
| Heatmeter actual power in kW | kW | Lezen | |||
| Heatmeter flowrate in l/h | l/h | Lezen | |||
| Heatmeter flow temperature | °C | Lezen | |||
| Heatmeter return temperature | °C | Lezen | |||
| Heatmeter serial number | Lezen | ||||
| Heatmeter volume in m³ | m³ | Lezen | |||
| Heatmeter error status (value vom heatmeter) | Lezen | ||||
| HC1 flow temperature setpoint | °C | Lezen | |||
| HC1 used room-setpoint | °C | Lezen | |||
| HC1 sensorvalue T17 return/room | °C | Lezen | |||
| HC1 status pump (P3) | Lezen | ||||
| HC1 operating status | Lezen | ||||
| HC1 room-setpoint | °C | Lezen en schrijven | |||
| HC1 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC1 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC1 mode | Lezen en schrijven | ||||
| HC1 correction in heating mode | K | Lezen en schrijven | |||
| HC1 correction in reduction mode | K | Lezen en schrijven | |||
| HC2 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC2 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC2 mode | Lezen en schrijven | ||||
| HC2 correction in heating mode | K | Lezen en schrijven | |||
| HC2 correction in reduction mode | K | Lezen en schrijven | |||
| HC2 room-setpoint | °C | Lezen en schrijven | |||
| HC2 status pump (P8) | Lezen | ||||
| HC2 operating status | Lezen | ||||
| HC2 sensorvalue T16 flow temperature | °C | Lezen | |||
| HC2 flow temperature setpoint | °C | Lezen | |||
| HC2 sensorvalue T20 return/room | °C | Lezen | |||
| HC2 used room-setpoint | °C | Lezen | |||
| HC3 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC3 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC3 mode | Lezen en schrijven | ||||
| HC3 correction in heating mode | K | Lezen en schrijven | |||
| HC3 correction in reduction mode | K | Lezen en schrijven | |||
| HC3 room-setpoint | °C | Lezen en schrijven | |||
| HC3 status Pumpe (3P1) | Lezen | ||||
| HC3 operating status | Lezen | ||||
| HC3 sensorvalue 3TMP flow temperature | °C | Lezen | |||
| HC3 flow temperature setpoint | °C | Lezen | |||
| HC3 sensorvalue 3FBT return/room | °C | Lezen | |||
| HC3 used room-setpoint | °C | Lezen | |||
| HC4 correction in heating mode | °C | Lezen en schrijven | |||
| HC4 correction in reduction mode | °C | Lezen en schrijven | |||
| HC4 mode | Lezen en schrijven | ||||
| HC4 correction in heating mode | K | Lezen en schrijven | |||
| HC4 correction in reduction mode | K | Lezen en schrijven | |||
| HC4 room-setpoint | °C | Lezen en schrijven | |||
| HC4 status pump (4P1) | Lezen | ||||
| HC4 operating status | Lezen | ||||
| HC4 sensorvalue 4TMP flow temperature | °C | Lezen | |||
| HC4 flow temperature setpoint | °C | Lezen | |||
| HC4 sensorvalue 4FBT return/room | °C | Lezen | |||
| HC4 used room-setpoint | °C | Lezen | |||
| TC1 operating status | Lezen | ||||
| TC1 used setpoint for sensor top | °C | Lezen | |||
| TC1 sensorvalue T13 top | °C | Lezen | |||
| TC1 used start temperature for sensor top | °C | Lezen | |||
| TC1 used setpoint/switchoff temperature for sensor bottom | °C | Lezen | |||
| TC1 sensorvalue T14 bottom | °C | Lezen | |||
| TC1 used start temperature for sensor bottom | °C | Lezen | |||
| TC1 used charging temperature | °C | Lezen | |||
| TC1 status pump (P4) | Lezen | ||||
| TC1 mode hot water tank | Lezen en schrijven | ||||
| HC3 status flow-switch from tapwaterstation | Lezen | ||||
| HC3 actual flow from tapwater station | l/min | Lezen | |||
| TC2 status pump (P5) | Lezen | ||||
| TC2 setpoint pumpe/valve (AO2) | % | Lezen | |||
| TC2 sensorvalue T23 top | °C | Lezen | |||
| TC2 sensorvalue T24 bottom | °C | Lezen | |||
| TC2 used charging temperature | °C | Lezen | |||
| TC2 hot water tank used setpoint for sensor top | °C | Lezen | |||
| TC2 hot water tank used start temperature for sensor top | °C | Lezen | |||
| TC2 hot water tank used setpoint/switchoff temperature for sensor bottom | °C | Lezen | |||
| TC2 hot water tank used start temperature for sensor bottom | °C | Lezen | |||
| TC2 operating status hot water tank | <v.> | Lezen | |||
| TC2 mode hot water tank | Lezen en schrijven | ||||
| TC2 used setpoint buffer tank top | °C | Lezen | |||
| TC2 buffer tank used switchoff temperature botton | °C | Lezen | |||
| TC2 operating status buffer tank | Lezen | ||||
| HC7 sensorvalue 7TMP flow temperature | °C | Lezen | |||
| HC7 sensorvalue 7FBT return/room | °C | Lezen |
Registers laden…
Stuur jouw apparatenlijst
Staat een apparaat niet in de bibliotheek, dan maken we de template gratis zodra we de registers hebben.
Gebruikstoepassingen
- Monitor buiten-, aanvoer- en retourtemperaturen op een live dashboard om de aanvoercondities van de stadsverwarming te controleren.
- Volg het energieverbruik en de doorstroomsnelheden van de warmtemeter over tijd om factureringsgegevens voor gebouwbeheerders te valideren.
- Maak meldingen aan wanneer foutbytes een storingsconditie aangeven in een van de vier verwarmingskringen.
- Pas HC1 tot HC4 kamertemperatuursetpoints op afstand aan tijdens seizoensgebonden inbedrijfstelling zonder een locatiebezoek.
- Schakel TC1 en TC2 warmwatertankmodi vanuit de cloud om in te spelen op bezettingswijzigingen of onderhoudsplanningen.
- Log de positiegegevens van de primaire klep om regelstabiliteit te diagnosticeren en jagende of vastgelopen klepkwesties op te sporen.
Installatie
Verbind de RS485 A- en B-klemmen van de ModbusCloud Gateway met de bijbehorende RS485 klemmen op de Aqotec RM360 regelaar.
Stel de Modbus baudrate op de gateway in op 19200 om overeen te komen met de standaard communicatie-instellingen van de RM360.
Configureer een uniek Modbus slave adres op de RM360 en voer hetzelfde adres in de ModbusCloud template-instellingen in.
Importeer het Aqotec RM360 Modbus RTU template in uw ModbusCloud project vanuit de templatebibliotheek.
Controleer de communicatie door te controleren of de buitentemperatuur en warmtemetergegevens correct worden weergegeven op het clouddashboard.
Bevestig dat float32 registers worden uitgelezen als twee opeenvolgende adressen en dat de bytevolgorde overeenkomt met de registerkaart van de RM360.
Veelvoorkomende aandachtspunten
Waarom tonen sommige temperatuur- of energiemetingen onjuiste of extreem grote waarden?
De registerkaart van de RM360 gebruikt gemengde datatypes, waaronder float32 waarden die twee opeenvolgende adressen beslaan. Zorg ervoor dat het template is geconfigureerd met het juiste datatype en de juiste bytevolgorde (doorgaans big-endian) voor elk register. Een afwijking levert onzinnige waarden op.
Welke baudrate moet ik gebruiken voor de RS485 verbinding?
De RM360 communiceert standaard op 19200 baud. Zorg ervoor dat zowel de ModbusCloud gateway als de regelaar zijn ingesteld op dezelfde baudrate, pariteit en stopbitconfiguratie.
Kan ik alle vier verwarmingskringen aansturen, zelfs als mijn installatie er minder gebruikt?
Ja. Het template biedt toegang tot HC1 tot en met HC4, maar ongebruikte kringen retourneren eenvoudigweg standaard- of nulwaarden. U kunt ongebruikte registers verbergen of negeren op het ModbusCloud dashboard.
Hoe stel ik vast welke storing is opgetreden aan de hand van de foutbytes?
Het template leest foutbytes 1 tot en met 4 uit de RM360. Raadpleeg de officiële Aqotec RM360 regelaarsdocumentatie voor de specifieke bitdefinities en foutcodes die bij elk foutbyte horen.
Meer Aqotec-templates