Aqotec aqotec RM360 via Modbus RTU Modbus Extension RS485 Modbus RTU template

aqotec RM360 via Modbus RTU Modbus Extension RS485

Monitors and controls an Aqotec RM360 district heating substation controller via Modbus RTU

Template for the Aqotec RM360 district heating substation controller via Modbus RTU over RS485. It reads temperatures, heat meter data, error statuses, and operating states for up to four heating circuits and hot water tanks. It also allows writing setpoints, modes, and correction values.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
98, read and write
Brand
Aqotec
Key readings
Outdoor and flow/return temperatures · Primary valve position · Heatmeter energy, power, and flowrate · HC1 to HC4 operating status and setpoints · Error bytes 1 to 4 · Heatmeter volume and serial number
Available commands
Main mode and HC1 to HC4 modes · HC1 to HC4 room setpoints and corrections · HC1 to HC4 outdoor switch-off temperatures · TC1 and TC2 hot water tank modes
Compatible models
RM360
Last updated

Registers (98)

98 read, 29 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
sensorvalue T10 outdoor°CRead
sensorvalue T11 prim. return°CRead
sensorvalue T12 sec. flow temperature°CRead
sensorvalue T15 sec. return temperature°CRead
setpoint sec. flow temperature°CRead
calculated primary-valve position%Read
actual used return limitation°CRead
operating statusRead
main modeRead and write
general-correction in reduction modeKRead and write
general-correction in heating modeKRead and write
Error-Byte 1 statusRead
Error-Byte 2 statusRead
Error-Byte 3 statusRead
Error-Byte 4 statusRead
Heatmeter energy in kWhkWhRead
Heatmeter actual power in kWkWRead
Heatmeter flowrate in l/hl/hRead
Heatmeter flow temperature°CRead
Heatmeter return temperature°CRead
Heatmeter serial numberRead
Heatmeter volume in m³m³Read
Heatmeter error status (value vom heatmeter)Read
HC1 flow temperature setpoint°CRead
HC1 used room-setpoint°CRead
HC1 sensorvalue T17 return/room°CRead
HC1 status pump (P3)Read
HC1 operating statusRead
HC1 room-setpoint°CRead and write
HC1 outdoor switch-off temperature in heating mode°CRead and write
HC1 outdoor switch-off temperature in reduction mode°CRead and write
HC1 modeRead and write
HC1 correction in heating modeKRead and write
HC1 correction in reduction modeKRead and write
HC2 outdoor switch-off temperature in heating mode°CRead and write
HC2 outdoor switch-off temperature in reduction mode°CRead and write
HC2 modeRead and write
HC2 correction in heating modeKRead and write
HC2 correction in reduction modeKRead and write
HC2 room-setpoint°CRead and write
HC2 status pump (P8)Read
HC2 operating statusRead
HC2 sensorvalue T16 flow temperature°CRead
HC2 flow temperature setpoint°CRead
HC2 sensorvalue T20 return/room°CRead
HC2 used room-setpoint°CRead
HC3 outdoor switch-off temperature in heating mode°CRead and write
HC3 outdoor switch-off temperature in reduction mode°CRead and write
HC3 modeRead and write
HC3 correction in heating modeKRead and write
HC3 correction in reduction modeKRead and write
HC3 room-setpoint°CRead and write
HC3 status Pumpe (3P1)Read
HC3 operating statusRead
HC3 sensorvalue 3TMP flow temperature°CRead
HC3 flow temperature setpoint°CRead
HC3 sensorvalue 3FBT return/room°CRead
HC3 used room-setpoint°CRead
HC4 correction in heating mode°CRead and write
HC4 correction in reduction mode°CRead and write
HC4 modeRead and write
HC4 correction in heating modeKRead and write
HC4 correction in reduction modeKRead and write
HC4 room-setpoint°CRead and write
HC4 status pump (4P1)Read
HC4 operating statusRead
HC4 sensorvalue 4TMP flow temperature°CRead
HC4 flow temperature setpoint°CRead
HC4 sensorvalue 4FBT return/room°CRead
HC4 used room-setpoint°CRead
TC1 operating statusRead
TC1 used setpoint for sensor top°CRead
TC1 sensorvalue T13 top°CRead
TC1 used start temperature for sensor top°CRead
TC1 used setpoint/switchoff temperature for sensor bottom°CRead
TC1 sensorvalue T14 bottom°CRead
TC1 used start temperature for sensor bottom°CRead
TC1 used charging temperature°CRead
TC1 status pump (P4)Read
TC1 mode hot water tankRead and write
HC3 status flow-switch from tapwaterstationRead
HC3 actual flow from tapwater stationl/minRead
TC2 status pump (P5)Read
TC2 setpoint pumpe/valve (AO2)%Read
TC2 sensorvalue T23 top°CRead
TC2 sensorvalue T24 bottom°CRead
TC2 used charging temperature°CRead
TC2 hot water tank used setpoint for sensor top°CRead
TC2 hot water tank used start temperature for sensor top°CRead
TC2 hot water tank used setpoint/switchoff temperature for sensor bottom°CRead
TC2 hot water tank used start temperature for sensor bottom°CRead
TC2 operating status hot water tank<v.>Read
TC2 mode hot water tankRead and write
TC2 used setpoint buffer tank top°CRead
TC2 buffer tank used switchoff temperature botton°CRead
TC2 operating status buffer tankRead
HC7 sensorvalue 7TMP flow temperature°CRead
HC7 sensorvalue 7FBT return/room°CRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor outdoor, flow, and return temperatures on a live dashboard to verify district heating supply conditions.
  • Track heat meter energy consumption and flow rates over time to validate billing data for building operators.
  • Create alerts when error bytes indicate a fault condition on any of the four heating circuits.
  • Adjust HC1 to HC4 room temperature setpoints remotely during seasonal commissioning without a site visit.
  • Switch TC1 and TC2 hot water tank modes from the cloud to respond to occupancy changes or maintenance schedules.
  • Log primary valve position data to diagnose control stability and detect hunting or stuck valve issues.

Installation

  1. Connect the RS485 A and B terminals of the ModbusCloud Gateway to the corresponding RS485 terminals on the Aqotec RM360 controller.

  2. Set the Modbus baud rate on the gateway to 19200 to match the RM360 default communication settings.

  3. Configure a unique Modbus slave address on the RM360 and enter the same address in the ModbusCloud template settings.

  4. Import the Aqotec RM360 Modbus RTU template into your ModbusCloud project from the template library.

  5. Verify communication by checking that outdoor temperature and heat meter readings appear correctly on the cloud dashboard.

  6. Confirm that float32 registers are read as two consecutive addresses and that the byte order matches the RM360 register map.

Things to watch for

Why are some temperature or energy readings showing incorrect or extremely large values?

The RM360 register map uses mixed data types including float32 values that span two consecutive addresses. Ensure the template is configured with the correct data type and byte order (typically big-endian) for each register. A mismatch will produce nonsensical values.

What baud rate should I use for the RS485 connection?

The RM360 communicates at 19200 baud by default. Make sure both the ModbusCloud gateway and the controller are set to the same baud rate, parity, and stop bit configuration.

Can I control all four heating circuits even if my installation uses fewer?

Yes. The template exposes HC1 through HC4, but unused circuits will simply return default or zero values. You can ignore or hide unused registers in the ModbusCloud dashboard.

How do I identify which fault has occurred using the error bytes?

The template reads error bytes 1 through 4 from the RM360. Refer to the official Aqotec RM360 controller documentation for the specific bit definitions and fault codes associated with each error byte.