aqotec RM360 via Modbus TCP
Monitors and controls an aqotec RM360 district heating substation controller via Modbus TCP
Template voor de Aqotec RM360 stadsverwarming onderstationregelaar via Modbus TCP. Leest temperaturen, warmtemetergegevens, pompstatussen en foutbytes. Maakt het mogelijk setpoints, modi en correcties te schrijven voor maximaal vier verwarmingskringen en twee warmwatertanks.
- Protocol
- Modbus TCP
- Aansluiting
- Ethernet, Modbus TCP
- Registers
- 98, lezen en schrijven
- Merk
- Aqotec
- Belangrijke uitlezingen
- Primary and secondary temperatures · Heatmeter energy and power · Heatmeter flowrate and volume · HC1 to HC4 flow and return temperatures · Operating and error status bytes · Pump statuses
- Beschikbare commando's
- HC1 to HC4 mode and room setpoint · HC1 to HC4 heating/reduction corrections · Main mode · TC1/TC2 hot water tank mode
- Ondersteunde modellen
- RM360
- Laatst bijgewerkt
Registers (98)
98 lezen, 29 schrijven
| Naam | Eenheid | Toegang | Adres (Verborgen tot je je e-mailadres invult) | Functie (verborgen) | Type (verborgen) |
|---|---|---|---|---|---|
| sensorvalue T10 outdoor | °C | Lezen | |||
| sensorvalue T11 prim. return | °C | Lezen | |||
| sensorvalue T12 sec. flow temperature | °C | Lezen | |||
| sensorvalue T15 sec. return temperature | °C | Lezen | |||
| setpoint sec. flow temperature | °C | Lezen | |||
| calculated primary-valve position | % | Lezen | |||
| actual used return limitation | °C | Lezen | |||
| operating status | Lezen | ||||
| main mode | Lezen en schrijven | ||||
| general-correction in reduction mode | K | Lezen en schrijven | |||
| general-correction in heating mode | K | Lezen en schrijven | |||
| Error-Byte 1 Status | Lezen | ||||
| Error-Byte 2 Status | Lezen | ||||
| Error-Byte 3 Status | Lezen | ||||
| Error-Byte 4 Status | Lezen | ||||
| Heatmeter Energy in kWh | kWh | Lezen | |||
| Heatmeter actual power in kW | kW | Lezen | |||
| Heatmeter flowrate in l/h | l/h | Lezen | |||
| Heatmeter flow temperature | °C | Lezen | |||
| Heatmeter return temperature | °C | Lezen | |||
| Heatmeter serial number | Lezen | ||||
| Heatmeter volume in m³ | m³ | Lezen | |||
| Heatmeter error status (value vom heatmeter) | Lezen | ||||
| HC1 flow temperature setpoint | °C | Lezen | |||
| HC1 used room-setpoint | °C | Lezen | |||
| HC1 sensorvalue T17 return/room | °C | Lezen | |||
| HC1 status pump (P3) | Lezen | ||||
| HC1 operating status | Lezen | ||||
| HC1 room-setpoint | °C | Lezen en schrijven | |||
| HC1 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC1 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC1 mode | Lezen en schrijven | ||||
| HC1 correction in heating mode | K | Lezen en schrijven | |||
| HC1 correction in reduction mode | K | Lezen en schrijven | |||
| HC2 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC2 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC2 mode | Lezen en schrijven | ||||
| HC2 correction in heating mode | K | Lezen en schrijven | |||
| HC2 correction in reduction mode | K | Lezen en schrijven | |||
| HC2 room-setpoint | °C | Lezen en schrijven | |||
| HC2 status pump (P8) | Lezen | ||||
| HC2 operating status | Lezen | ||||
| HC2 sensorvalue T16 flow temperature | °C | Lezen | |||
| HC2 flow temperature setpoint | °C | Lezen | |||
| HC2 sensorvalue T20 return/room | °C | Lezen | |||
| HC2 used room-setpoint | °C | Lezen | |||
| HC3 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC3 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC3 mode | Lezen en schrijven | ||||
| HC3 correction in heating mode | K | Lezen en schrijven | |||
| HC3 correction in reduction mode | K | Lezen en schrijven | |||
| HC3 room-setpoint | °C | Lezen en schrijven | |||
| HC3 status pump (3P1) | Lezen | ||||
| HC3 operating status | Lezen | ||||
| HC3 sensorvalue 3TMP flow temperature | °C | Lezen | |||
| HC3 flow temperature setpoint | °C | Lezen | |||
| HC3 sensorvalue 3FBT return/room | °C | Lezen | |||
| HC3 used room-setpoint | °C | Lezen | |||
| HC4 outdoor switch-off temperature in heating mode | °C | Lezen en schrijven | |||
| HC4 outdoor switch-off temperature in reduction mode | °C | Lezen en schrijven | |||
| HC4 mode | Lezen en schrijven | ||||
| HC4 correction in heating mode | K | Lezen en schrijven | |||
| HC4 correction in reduction mode | K | Lezen en schrijven | |||
| HC4 room-setpoint | °C | Lezen en schrijven | |||
| HC4 status pump (4P1) | Lezen | ||||
| HC4 operating status | Lezen | ||||
| HC4 sensorvalue 4TMP flow temperature | °C | Lezen | |||
| HC4 flow temperature setpoint | °C | Lezen | |||
| HC4 sensorvalue 4FBT return/room | °C | Lezen | |||
| HC4 used room-setpoint | °C | Lezen | |||
| TC1 operating status | Lezen | ||||
| TC1 used setpoint for sensor top | °C | Lezen | |||
| TC1 sensorvalue T13 top | °C | Lezen | |||
| TC1 used start temperature for sensor top | °C | Lezen | |||
| TC1 used setpoint/switchoff temperature for sensor bottom | °C | Lezen | |||
| TC1 sensorvalue T14 bottom | °C | Lezen | |||
| TC1 used start temperature for sensor bottom | °C | Lezen | |||
| TC1 used charging temperature | °C | Lezen | |||
| TC1 status pump (P4) | Lezen | ||||
| TC1 mode hot water tank | Lezen en schrijven | ||||
| HC3 status flow-switch from tapwaterstation | Lezen | ||||
| HC3 actual flow from tapwater station | l/min | Lezen | |||
| TC2 status pump (P5) | Lezen | ||||
| TC2 setpoint pumpe/valve (AO2) | % | Lezen | |||
| TC2 sensorvalue T23 top | °C | Lezen | |||
| TC2 sensorvalue T24 bottom | °C | Lezen | |||
| TC2 used charging temperature | °C | Lezen | |||
| TC2 hot water tank used setpoint for sensor top | °C | Lezen | |||
| TC2 hot water tank used start temperature for sensor top | °C | Lezen | |||
| TC2 hot water tank used setpoint/switchoff temperature for sensor bottom | °C | Lezen | |||
| TC2 hot water tank used start temperature for sensor bottom | °C | Lezen | |||
| TC2 operating status hot water tank | <v.> | Lezen | |||
| TC2 mode hot water tank | Lezen en schrijven | ||||
| TC2 used setpoint buffer tank top | °C | Lezen | |||
| TC2 buffer tank used switchoff temperature botton | °C | Lezen | |||
| TC2 operating status buffer tank | Lezen | ||||
| HC7 sensorvalue 7TMP flow temperature | °C | Lezen | |||
| HC7 sensorvalue 7FBT return/room | °C | Lezen |
Registers laden…
Stuur jouw apparatenlijst
Staat een apparaat niet in de bibliotheek, dan maken we de template gratis zodra we de registers hebben.
Gebruikstoepassingen
- Bewaak primaire en secundaire temperaturen van een stadsverwarming onderstation op een live clouddashboard.
- Pas ruimtetemperatuursetpoints en verwarmingscorrecties voor alle vier verwarmingskringen op afstand aan.
- Stel een melding in wanneer een foutstatusbyte een storingssituatie op de RM360-regelaar aangeeft.
- Log warmtemeterenergie- en debietgegevens over tijd om het stadsverwarming verbruik te verifiëren.
- Schakel de hoofdbedrijfsmodus of de warmwatertankmodi voor TC1 en TC2 om zonder een bezoek ter plaatse.
- Vergelijk aan- en afvoertemperaturen over verwarmingskringen heen om balanceringsproblemen te detecteren.
Installatie
Verbind de Aqotec RM360 via de Ethernet-poort met uw lokale netwerk en controleer of Modbus TCP is ingeschakeld in de regelaarinstellingen.
Verbind uw ModbusCloud Gateway met hetzelfde lokale netwerk en zorg ervoor dat deze het IP-adres van de RM360 kan bereiken op de geconfigureerde Modbus TCP-poort.
Noteer het IP-adres en de Modbus TCP-poort van de RM360 en configureer deze in de instellingen van de ModbusCloud-gateway.
Importeer het Aqotec RM360 Modbus TCP-template uit de ModbusCloud-templatebibliotheek in uw project.
Verifieer de communicatie door te controleren of temperatuurmetingen en statuswaarden correct worden weergegeven op het ModbusCloud-dashboard.
Test schrijftoegang door een setpoint van een verwarmingskring aan te passen en te bevestigen dat de wijziging zichtbaar is op het display van de RM360-regelaar.
Veelvoorkomende aandachtspunten
Waarom verschijnen sommige temperatuurwaarden als onjuiste of zeer grote getallen?
De RM360 gebruikt float32-registers die twee opeenvolgende Modbus-adressen beslaan. Zorg ervoor dat de byte-volgorde en woordvolgorde in de gateway overeenkomen met de RM360-configuratie. Het template is vooraf geconfigureerd voor de juiste gegevenstypen, maar aangepaste wijzigingen kunnen fouten introduceren.
Welke Modbus TCP-poort gebruikt de RM360?
De standaard Modbus TCP-poort is doorgaans 502. Controleer dit in de netwerkinstellingen van de RM360. Als een andere poort is geconfigureerd, pas dan de gatewayverbindingsinstellingen dienovereenkomstig aan.
Kan ik dit template gebruiken als ik slechts twee verwarmingskringen geïnstalleerd heb?
Ja. Het template bevat registers voor HC1 tot en met HC4 en beide warmwatertanks. Ongebruikte kringen geven eenvoudigweg nul of standaardwaarden terug. U kunt ongebruikte registers verbergen in uw ModbusCloud-dashboard.
Heb ik een specifieke firmwareversie op de RM360 nodig om Modbus TCP te laten werken?
Modbus TCP-ondersteuning is afhankelijk van de firmware en hardwareversie van de RM360. Raadpleeg de Aqotec-documentatie of neem contact op met Aqotec-support om te bevestigen dat uw unit Modbus TCP-communicatie ondersteunt.