aqotec RM360 via Modbus TCP
Monitors and controls an aqotec RM360 district heating substation controller via Modbus TCP
Vorlage für den Aqotec RM360 Fernwärme-Übergabestationsregler via Modbus TCP. Liest Temperaturen, Wärmezählerdaten, Pumpenstatus und Fehlerbytes. Ermöglicht das Schreiben von Sollwerten, Betriebsmodi und Korrekturen für bis zu vier Heizkreise und zwei Warmwasserspeicher.
- Protokoll
- Modbus TCP
- Anschluss
- Ethernet, Modbus TCP
- Register
- 98, lesen und schreiben
- Marke
- Aqotec
- Wichtige Messwerte
- Primary and secondary temperatures · Heatmeter energy and power · Heatmeter flowrate and volume · HC1 to HC4 flow and return temperatures · Operating and error status bytes · Pump statuses
- Verfügbare Befehle
- HC1 to HC4 mode and room setpoint · HC1 to HC4 heating/reduction corrections · Main mode · TC1/TC2 hot water tank mode
- Kompatible Modelle
- RM360
- Zuletzt aktualisiert
Register (98)
98 lesen, 29 schreiben
| Name | Einheit | Zugriff | Adresse (Verborgen bis zur Eingabe Ihrer E-Mail-Adresse) | Funktion (verborgen) | Typ (verborgen) |
|---|---|---|---|---|---|
| sensorvalue T10 outdoor | °C | Lesen | |||
| sensorvalue T11 prim. return | °C | Lesen | |||
| sensorvalue T12 sec. flow temperature | °C | Lesen | |||
| sensorvalue T15 sec. return temperature | °C | Lesen | |||
| setpoint sec. flow temperature | °C | Lesen | |||
| calculated primary-valve position | % | Lesen | |||
| actual used return limitation | °C | Lesen | |||
| operating status | Lesen | ||||
| main mode | Lesen und Schreiben | ||||
| general-correction in reduction mode | K | Lesen und Schreiben | |||
| general-correction in heating mode | K | Lesen und Schreiben | |||
| Error-Byte 1 Status | Lesen | ||||
| Error-Byte 2 Status | Lesen | ||||
| Error-Byte 3 Status | Lesen | ||||
| Error-Byte 4 Status | Lesen | ||||
| Heatmeter Energy in kWh | kWh | Lesen | |||
| Heatmeter actual power in kW | kW | Lesen | |||
| Heatmeter flowrate in l/h | l/h | Lesen | |||
| Heatmeter flow temperature | °C | Lesen | |||
| Heatmeter return temperature | °C | Lesen | |||
| Heatmeter serial number | Lesen | ||||
| Heatmeter volume in m³ | m³ | Lesen | |||
| Heatmeter error status (value vom heatmeter) | Lesen | ||||
| HC1 flow temperature setpoint | °C | Lesen | |||
| HC1 used room-setpoint | °C | Lesen | |||
| HC1 sensorvalue T17 return/room | °C | Lesen | |||
| HC1 status pump (P3) | Lesen | ||||
| HC1 operating status | Lesen | ||||
| HC1 room-setpoint | °C | Lesen und Schreiben | |||
| HC1 outdoor switch-off temperature in heating mode | °C | Lesen und Schreiben | |||
| HC1 outdoor switch-off temperature in reduction mode | °C | Lesen und Schreiben | |||
| HC1 mode | Lesen und Schreiben | ||||
| HC1 correction in heating mode | K | Lesen und Schreiben | |||
| HC1 correction in reduction mode | K | Lesen und Schreiben | |||
| HC2 outdoor switch-off temperature in heating mode | °C | Lesen und Schreiben | |||
| HC2 outdoor switch-off temperature in reduction mode | °C | Lesen und Schreiben | |||
| HC2 mode | Lesen und Schreiben | ||||
| HC2 correction in heating mode | K | Lesen und Schreiben | |||
| HC2 correction in reduction mode | K | Lesen und Schreiben | |||
| HC2 room-setpoint | °C | Lesen und Schreiben | |||
| HC2 status pump (P8) | Lesen | ||||
| HC2 operating status | Lesen | ||||
| HC2 sensorvalue T16 flow temperature | °C | Lesen | |||
| HC2 flow temperature setpoint | °C | Lesen | |||
| HC2 sensorvalue T20 return/room | °C | Lesen | |||
| HC2 used room-setpoint | °C | Lesen | |||
| HC3 outdoor switch-off temperature in heating mode | °C | Lesen und Schreiben | |||
| HC3 outdoor switch-off temperature in reduction mode | °C | Lesen und Schreiben | |||
| HC3 mode | Lesen und Schreiben | ||||
| HC3 correction in heating mode | K | Lesen und Schreiben | |||
| HC3 correction in reduction mode | K | Lesen und Schreiben | |||
| HC3 room-setpoint | °C | Lesen und Schreiben | |||
| HC3 status pump (3P1) | Lesen | ||||
| HC3 operating status | Lesen | ||||
| HC3 sensorvalue 3TMP flow temperature | °C | Lesen | |||
| HC3 flow temperature setpoint | °C | Lesen | |||
| HC3 sensorvalue 3FBT return/room | °C | Lesen | |||
| HC3 used room-setpoint | °C | Lesen | |||
| HC4 outdoor switch-off temperature in heating mode | °C | Lesen und Schreiben | |||
| HC4 outdoor switch-off temperature in reduction mode | °C | Lesen und Schreiben | |||
| HC4 mode | Lesen und Schreiben | ||||
| HC4 correction in heating mode | K | Lesen und Schreiben | |||
| HC4 correction in reduction mode | K | Lesen und Schreiben | |||
| HC4 room-setpoint | °C | Lesen und Schreiben | |||
| HC4 status pump (4P1) | Lesen | ||||
| HC4 operating status | Lesen | ||||
| HC4 sensorvalue 4TMP flow temperature | °C | Lesen | |||
| HC4 flow temperature setpoint | °C | Lesen | |||
| HC4 sensorvalue 4FBT return/room | °C | Lesen | |||
| HC4 used room-setpoint | °C | Lesen | |||
| TC1 operating status | Lesen | ||||
| TC1 used setpoint for sensor top | °C | Lesen | |||
| TC1 sensorvalue T13 top | °C | Lesen | |||
| TC1 used start temperature for sensor top | °C | Lesen | |||
| TC1 used setpoint/switchoff temperature for sensor bottom | °C | Lesen | |||
| TC1 sensorvalue T14 bottom | °C | Lesen | |||
| TC1 used start temperature for sensor bottom | °C | Lesen | |||
| TC1 used charging temperature | °C | Lesen | |||
| TC1 status pump (P4) | Lesen | ||||
| TC1 mode hot water tank | Lesen und Schreiben | ||||
| HC3 status flow-switch from tapwaterstation | Lesen | ||||
| HC3 actual flow from tapwater station | l/min | Lesen | |||
| TC2 status pump (P5) | Lesen | ||||
| TC2 setpoint pumpe/valve (AO2) | % | Lesen | |||
| TC2 sensorvalue T23 top | °C | Lesen | |||
| TC2 sensorvalue T24 bottom | °C | Lesen | |||
| TC2 used charging temperature | °C | Lesen | |||
| TC2 hot water tank used setpoint for sensor top | °C | Lesen | |||
| TC2 hot water tank used start temperature for sensor top | °C | Lesen | |||
| TC2 hot water tank used setpoint/switchoff temperature for sensor bottom | °C | Lesen | |||
| TC2 hot water tank used start temperature for sensor bottom | °C | Lesen | |||
| TC2 operating status hot water tank | <v.> | Lesen | |||
| TC2 mode hot water tank | Lesen und Schreiben | ||||
| TC2 used setpoint buffer tank top | °C | Lesen | |||
| TC2 buffer tank used switchoff temperature botton | °C | Lesen | |||
| TC2 operating status buffer tank | Lesen | ||||
| HC7 sensorvalue 7TMP flow temperature | °C | Lesen | |||
| HC7 sensorvalue 7FBT return/room | °C | Lesen |
Register werden geladen…
Senden Sie Ihre Geräteliste
Steht ein Gerät noch nicht in der Bibliothek, erstellen wir die Vorlage kostenlos, sobald wir die Register haben.
Anwendungsfälle
- Primär- und Sekundärtemperaturen einer Fernwärme-Übergabestation auf einem Live-Cloud-Dashboard überwachen.
- Raumtemperatursollwerte und Heizkorrekturen für alle vier Heizkreise ferngesteuert anpassen.
- Einen Alarm auslösen, wenn ein Fehlerstatusbyte einen Störungszustand am RM360-Regler meldet.
- Energiemenge und Durchflussdaten des Wärmezählers über die Zeit aufzeichnen, um den Fernwärmeverbrauch zu überprüfen.
- Den Hauptbetriebsmodus oder die Warmwasserspeichermodi für TC1 und TC2 ohne Vor-Ort-Besuch umschalten.
- Vor- und Rücklauftemperaturen der Heizkreise vergleichen, um Einregulierungsprobleme zu erkennen.
Installation
Den Aqotec RM360 über den Ethernet-Anschluss mit dem lokalen Netzwerk verbinden und sicherstellen, dass Modbus TCP in den Reglereinstellungen aktiviert ist.
Die ModbusCloud Gateway mit demselben lokalen Netzwerk verbinden und sicherstellen, dass sie die IP-Adresse des RM360 am konfigurierten Modbus TCP-Port erreichen kann.
Die IP-Adresse und den Modbus TCP-Port des RM360 notieren und in den ModbusCloud-Gateway-Einstellungen eintragen.
Die Aqotec RM360 Modbus TCP-Vorlage aus der ModbusCloud-Vorlagenbibliothek in das Projekt importieren.
Die Kommunikation überprüfen, indem kontrolliert wird, ob Temperaturmesswerte und Statuswerte korrekt im ModbusCloud-Dashboard erscheinen.
Den Schreibzugriff testen, indem ein Heizkreissollwert geändert und das Ergebnis auf dem Display des RM360-Reglers bestätigt wird.
Zu beachten
Warum erscheinen manche Temperaturwerte als falsche oder sehr große Zahlen?
Der RM360 verwendet float32-Register, die sich über zwei aufeinanderfolgende Modbus-Adressen erstrecken. Stellen Sie sicher, dass die Byte-Reihenfolge und die Wortreihenfolge im Gateway mit der RM360-Konfiguration übereinstimmen. Die Vorlage ist für die korrekten Datentypen vorkonfiguriert, jedoch können individuelle Anpassungen zu Fehlern führen.
Welchen Modbus TCP-Port verwendet der RM360?
Der Standard-Modbus TCP-Port ist üblicherweise 502. Überprüfen Sie dies in den Netzwerkeinstellungen des RM360. Wenn ein anderer Port konfiguriert wurde, passen Sie die Gateway-Verbindungseinstellungen entsprechend an.
Kann ich diese Vorlage verwenden, wenn nur zwei Heizkreise installiert sind?
Ja. Die Vorlage enthält Register für HC1 bis HC4 sowie beide Warmwasserspeicher. Nicht verwendete Kreise liefern einfach null oder Standardwerte zurück. Nicht benötigte Register können im ModbusCloud-Dashboard ausgeblendet werden.
Benötige ich eine bestimmte Firmware-Version auf dem RM360, damit Modbus TCP funktioniert?
Die Modbus TCP-Unterstützung hängt von der Firmware und der Hardwarerevision des RM360 ab. Prüfen Sie die Aqotec-Dokumentation oder kontaktieren Sie den Aqotec-Support, um zu bestätigen, dass Ihr Gerät Modbus TCP-Kommunikation unterstützt.