Outside temperaturee Outdoor temperaturee sensor | 2 | FC03 | int16 | °C | R |
Plant operating mode (0) Off (1) Auto (2) Domestic Hot Water | 3 | FC03 | uint16 | | R/W |
Heating circuit 1 operating mode (0) Off, (1) Auto, (2) Heat, (3) Setback | 10 | FC03 | int16 | | R/W |
Hot water 1 (WW) operating mode (0)Off, (1) Auto, (2) On | 47 | FC03 | int16 | | R/W |
Hot water 1 (Auto) operating mode (0)Off, (1) Auto, (2) On | 48 | FC03 | int16 | | R/W |
Hot water 1 1x preheating Heatup water once | 49 | FC03 | uint16 | | R/W |
Heating circuit 1 heating temperature | 11 | FC03 | int16 | °C | R/W |
Heating circuit 1 setback temperature | 12 | FC03 | int16 | °C | R/W |
Heating circuit 1 time program | 14 | FC03 | uint16 | | R/W |
Heating circuit 1 room temperature | 13 | FC03 | int16 | °C | R |
Hot water 1 temperature | 50 | FC03 | int16 | °C | R |
Hot water 1 time program | 51 | FC03 | uint16 | | R/W |
Buffer 1 TPO | 62 | FC03 | int16 | °C | R |
Buffer 1 TPM | 63 | FC03 | int16 | °C | R |
Solar 1 collector | 68 | FC03 | int16 | °C | R |
Solar 1 SPU 1 | 69 | FC03 | int16 | °C | R |
Solar 1 SPU 2 | 70 | FC03 | int16 | °C | R |
SolarGain 1 | 77 | FC03 | uint16 | kW | R |
SolarGain 1 today | 78 | FC03 | uint16 | kWh | R |
SolarGain 1 yesterday | 79 | FC03 | uint16 | kWh | R |
SolarGain 1 total | 80 | FC03 | uint16 | kWh | R |
ECO mode | 89 | FC03 | uint16 | | R/W |
ECO temp | 90 | FC03 | int16 | °C | R |
ECO clouds | 91 | FC03 | int16 | % | R |
ECO forecast temp | 92 | FC03 | int16 | °C | R |
ECO forecast clouds | 93 | FC03 | int16 | % | R |
PE 1 mode | 105 | FC03 | int16 | | R/W |
PE 1 temp | 106 | FC03 | int16 | °C | R |
PE 1 modulation | 107 | FC03 | int16 | % | R |
PE 1 status | 108 | FC03 | uint16 | | R |
Buffer 2 TPM | 65 | FC03 | int16 | °C | R |
Buffer 2 TPO | 64 | FC03 | int16 | °C | R |
Buffer 3 TPM | 67 | FC03 | int16 | °C | R |
Buffer 3 TPO | 66 | FC03 | int16 | °C | R |
Solar 2 collector | 71 | FC03 | int16 | °C | R |
Solar 2 SPU 1 | 72 | FC03 | int16 | °C | R |
Solar 2 SPU 2 | 73 | FC03 | int16 | °C | R |
Solar 3 collector | 74 | FC03 | int16 | °C | R |
Solar 3 SPU 1 | 75 | FC03 | int16 | °C | R |
Solar 3 SPU 2 | 76 | FC03 | int16 | °C | R |
SolarGain 2 | 81 | FC03 | uint16 | kW | R |
SolarGain 3 | 85 | FC03 | uint16 | kW | R |
SolarGain 2 yesterday | 83 | FC03 | uint16 | kWh | R |
SolarGain 3 yesterday | 87 | FC03 | uint16 | kWh | R |
SolarGain 2 today | 82 | FC03 | uint16 | kWh | R |
SolarGain 3 today | 86 | FC03 | uint16 | kWh | R |
SolarGain 2 total | 84 | FC03 | uint16 | kWh | R |
SolarGain 3 total | 88 | FC03 | uint16 | kWh | R |
Hot water 2 (Auto) operating mode (0)Off, (1) Auto, (2) On | 53 | FC03 | int16 | | R/W |
Hot water 3 (Auto) operating mode (0)Off, (1) Auto, (2) On | 58 | FC03 | int16 | | R/W |
Hot water 2 (WW) operating mode (0)Off, (1) Auto, (2) On | 52 | FC03 | int16 | | R/W |
Hot water 3 (WW) operating mode (0)Off, (1) Auto, (2) On | 57 | FC03 | int16 | | R/W |
Hot water 2 1x preheating Heatup water once | 54 | FC03 | uint16 | | R/W |
Hot water 3 1x preheating Heatup water once | 59 | FC03 | uint16 | | R/W |
Hot water 2 temperature | 55 | FC03 | int16 | °C | R |
Hot water 3 temperature | 60 | FC03 | int16 | °C | R |
Hot water 2 time program | 56 | FC03 | uint16 | | R/W |
Hot water 3 time program | 61 | FC03 | uint16 | | R/W |
PE 2 mode | 109 | FC03 | int16 | | R/W |
PE 3 mode | 113 | FC03 | int16 | | R/W |
PE 4 mode | 117 | FC03 | int16 | | R/W |
PE 2 modulation | 111 | FC03 | int16 | % | R |
PE 3 modulation | 115 | FC03 | int16 | % | R |
PE 4 modulation | 119 | FC03 | int16 | % | R |
PE 2 status | 112 | FC03 | uint16 | | R |
PE 3 status | 116 | FC03 | uint16 | | R |
PE 4 status | 120 | FC03 | uint16 | | R |
PE 2 temp | 110 | FC03 | int16 | °C | R |
PE 3 temp | 114 | FC03 | int16 | °C | R |
PE 4 temp | 118 | FC03 | int16 | °C | R |
Heating circuit 2 setback temperature | 18 | FC03 | int16 | °C | R |
Heating circuit 3 setback temperature | 24 | FC03 | int16 | °C | R/W |
Heating circuit 4 setback temperature | 30 | FC03 | int16 | °C | R/W |
Heating circuit 5 setback temperature | 36 | FC03 | int16 | °C | R/W |
Heating circuit 6 setback temperature | 42 | FC03 | int16 | °C | R/W |
Heating circuit 2 operating mode (0) Off, (1) Auto, (2) Heat, (3) Setback | 16 | FC03 | int16 | | R/W |
Heating circuit 3 operating mode (0) Off, (1) Auto, (2) Heat, (3) Setback | 22 | FC03 | int16 | | R/W |
Heating circuit 4 operating mode (0) Off, (1) Auto, (2) Heat, (3) Setback | 28 | FC03 | int16 | | R/W |
Heating circuit 5 operating mode (0) Off, (1) Auto, (2) Heat, (3) Setback | 34 | FC03 | int16 | | R/W |
Heating circuit 6 operating mode (0) Off, (1) Auto, (2) Heat, (3) Setback | 40 | FC03 | int16 | | R/W |
Heating circuit 2 heating temperature | 17 | FC03 | int16 | °C | R/W |
Heating circuit 3 heating temperature | 23 | FC03 | int16 | °C | R/W |
Heating circuit 4 heating temperature | 29 | FC03 | int16 | °C | R/W |
Heating circuit 5 heating temperature | 35 | FC03 | int16 | °C | R/W |
Heating circuit 6 heating temperature | 41 | FC03 | int16 | °C | R/W |
Heating circuit 2 room temperature | 19 | FC03 | int16 | °C | R/W |
Heating circuit 3 room temperature | 25 | FC03 | int16 | °C | R |
Heating circuit 4 room temperature | 31 | FC03 | int16 | °C | R |
Heating circuit 5 room temperature | 37 | FC03 | int16 | °C | R |
Heating circuit 6 room temperature | 43 | FC03 | int16 | °C | R |
Heating circuit 2 time program | 20 | FC03 | uint16 | | R/W |
Heating circuit 3 time program | 26 | FC03 | uint16 | | R/W |
Heating circuit 4 time program | 32 | FC03 | uint16 | | R/W |
Heating circuit 5 time program | 38 | FC03 | uint16 | | R/W |
Heating circuit 6 time program | 44 | FC03 | uint16 | | R/W |
Error 1 | 5 | FC03 | uint16 | | R |
Error 2 | 6 | FC03 | uint16 | | R |
Error 3 | 7 | FC03 | uint16 | | R |
Error 4 | 8 | FC03 | uint16 | | R |
Error 5 | 9 | FC03 | uint16 | | R |
Version W | 1 | FC06 | int16 | | W |
Heating circuit 1 Eco mode W (0)Off, (1)Comfort, (2)Minimum, (3) Eco | 15 | FC06 | int16 | | W |
Heating circuit 2 Eco mode W (0)Off, (1)Comfort, (2)Minimum, (3) Eco | 21 | FC06 | int16 | | W |
Heating circuit 3 Eco mode W (0)Off, (1)Comfort, (2)Minimum, (3) Eco | 27 | FC06 | int16 | | W |
Heating circuit 4 Eco mode W (0)Off, (1)Comfort, (2)Minimum, (3) Eco | 33 | FC06 | int16 | | W |
Heating circuit 5 Eco mode W (0)Off, (1)Comfort, (2)Minimum, (3) Eco | 39 | FC06 | int16 | | W |
Heating circuit 6 Eco mode W (0)Off, (1)Comfort, (2)Minimum, (3) Eco | 45 | FC06 | int16 | | W |