ems_communication_timeout_a EMS communication timeout setting, write to configure timeout value. | 4132 | FC16 | uint16 | ms | W |
ems_address_a EMS Modbus slave address setting, write to assign address. | 4133 | FC16 | uint16 | | W |
ems_baudrate_a EMS serial baud rate setting, write to configure communication speed. | 4134 | FC16 | uint16 | | W |
ems_communication_timeout_b EMS communication timeout readback, current configured timeout value. | 4132 | FC03 | uint16 | ms | R |
ems_address_b EMS Modbus slave address readback, currently active address. | 4133 | FC03 | uint16 | | R |
ems_baudrate_b EMS serial baud rate readback, currently active baud rate. | 4134 | FC03 | uint16 | | R |
cluster_start_stop_a Cluster start or stop command, write to start or stop the cluster. | 4291 | FC16 | uint16 | | W |
rack_1_usage_a Rack 1 enable or disable command, write to set rack usage. | 4292 | FC16 | uint16 | | W |
rack_2_usage_a Rack 2 enable or disable command, write to set rack usage. | 4293 | FC16 | uint16 | | W |
rack_3_usage_a Rack 3 enable or disable command, write to set rack usage. | 4294 | FC16 | uint16 | | W |
rack_4_usage_a Rack 4 enable or disable command, write to set rack usage. | 4295 | FC16 | uint16 | | W |
rack_5_usage_a Rack 5 enable or disable command, write to set rack usage. | 4296 | FC16 | uint16 | | W |
cluster_start_stop_b Cluster start or stop state readback, current run state. | 4291 | FC03 | uint16 | | R |
rack_1_usage_b Rack 1 usage state readback, indicates if rack is enabled. | 4292 | FC03 | uint16 | | R |
rack_2_usage_b Rack 2 usage state readback, indicates if rack is enabled. | 4293 | FC03 | uint16 | | R |
rack_3_usage_b Rack 3 usage state readback, indicates if rack is enabled. | 4294 | FC03 | uint16 | | R |
rack_4_usage_b Rack 4 usage state readback, indicates if rack is enabled. | 4295 | FC03 | uint16 | | R |
rack_5_usage_b Rack 5 usage state readback, indicates if rack is enabled. | 4296 | FC03 | uint16 | | R |
charge_indication Charge or discharge direction indicator for the cluster. | 4164 | FC03 | uint16 | | R |
current Cluster DC current, amperes, instantaneous measurement. | 4165 | FC03 | uint16 | A | R |
original_soc Cluster state of charge reported by the BMS, 0 to 100 percent. | 4167 | FC03 | uint16 | % | R |
system_running_state Overall system operating state code from the BMS. | 4168 | FC03 | uint16 | | R |
voltage Cluster DC bus voltage, volts, instantaneous measurement. | 4169 | FC03 | uint16 | V | R |
system_insulation System insulation resistance status reported by the BMS. | 4170 | FC03 | uint16 | | R |
bp_charge_bms BMS charge permission flag, indicates whether charging is allowed. | 4174 | FC03 | uint16 | | R |
bp_discharge_bms BMS discharge permission flag, indicates whether discharging is allowed. | 4175 | FC03 | uint16 | | R |