voltage_l1 Phase L1 to neutral RMS voltage, volts. | 1317 | FC03 | float32 | V | R |
voltage_l2 Phase L2 to neutral RMS voltage, volts. | 1319 | FC03 | float32 | V | R |
voltage_l3 Phase L3 to neutral RMS voltage, volts. | 1321 | FC03 | float32 | V | R |
current_l1 RMS current on phase L1, amperes. | 1325 | FC03 | float32 | A | R |
current_l2 RMS current on phase L2, amperes. | 1327 | FC03 | float32 | A | R |
current_l3 RMS current on phase L3, amperes. | 1329 | FC03 | float32 | A | R |
active_power_l1 Active power on phase L1, watts. | 1333 | FC03 | float32 | W | R |
active_power_l2 Active power on phase L2, watts. | 1335 | FC03 | float32 | W | R |
active_power_l3 Active power on phase L3, watts. | 1337 | FC03 | float32 | W | R |
reactive_power_l1 Reactive power on phase L1, volt-amperes reactive. | 1341 | FC03 | float32 | W | R |
reactive_power_l2 Reactive power on phase L2, volt-amperes reactive. | 1343 | FC03 | float32 | W | R |
reactive_power_l3 Reactive power on phase L3, volt-amperes reactive. | 1345 | FC03 | float32 | W | R |
active_power Total three-phase active power sum, watts. | 1369 | FC03 | float32 | W | R |
reactive_power Total three-phase reactive power sum, var. | 1371 | FC03 | float32 | var | R |
frequency Grid frequency, hertz, typically 50 or 60. | 1439 | FC03 | float32 | Hz | R |
rotation_field Phase rotation field indicator, clockwise or counter-clockwise. | 1449 | FC03 | float32 | | R |
internal_temperature Internal device temperature, degrees Celsius. | 1461 | FC03 | float32 | °C | R |
active_consumption_energy Cumulative active energy consumed from the grid, watt-hours. | 9851 | FC03 | float32 | Wh | R |
active_production_energy Cumulative active energy supplied to the grid, watt-hours. | 9863 | FC03 | float32 | Wh | R |