software_version Firmware version number of the meter. | 16391 | FC03 | float32 | | R |
primary_current Configured CT primary current rating, amperes. | 16415 | FC03 | int16 | A | R |
secondary_current Configured CT secondary current rating, amperes. | 16416 | FC03 | int16 | A | R |
software_version_check_sum Checksum value for firmware version integrity verification. | 16419 | FC03 | uint32 | | R |
voltage_l1 Phase L1 line-to-neutral voltage, volts. | 20482 | FC03 | float32 | V | R |
voltage_l2 Phase L2 line-to-neutral voltage, volts. | 20484 | FC03 | float32 | V | R |
voltage_l3 Phase L3 line-to-neutral voltage, volts. | 20486 | FC03 | float32 | V | R |
frequency Grid frequency, hertz, typically 50 or 60. | 20488 | FC03 | float32 | Hz | R |
meter_current_l1 Instantaneous current on phase L1, amperes. | 20492 | FC03 | float32 | A | R |
meter_current_l2 Instantaneous current on phase L2, amperes. | 20494 | FC03 | float32 | A | R |
meter_current_l3 Instantaneous current on phase L3, amperes. | 20496 | FC03 | float32 | A | R |
meter_active_power Total three-phase active power, watts. | 20498 | FC03 | float32 | W | R |
meter_active_power_l1 Active power on phase L1, watts. | 20500 | FC03 | float32 | W | R |
meter_active_power_l2 Active power on phase L2, watts. | 20502 | FC03 | float32 | W | R |
meter_active_power_l3 Active power on phase L3, watts. | 20504 | FC03 | float32 | W | R |
meter_reactive_power Total three-phase reactive power, volt-amperes reactive. | 20506 | FC03 | float32 | W | R |
meter_reactive_power_l1 Reactive power on phase L1, volt-amperes reactive. | 20508 | FC03 | float32 | W | R |
meter_reactive_power_l2 Reactive power on phase L2, volt-amperes reactive. | 20510 | FC03 | float32 | W | R |
meter_reactive_power_l3 Reactive power on phase L3, volt-amperes reactive. | 20512 | FC03 | float32 | W | R |
active_consumption_energy Cumulative total active energy imported from the grid, watt-hours. | 24588 | FC03 | float32 | Wh | R |
active_consumption_energy_l1 Cumulative active energy imported on phase L1. | 24594 | FC03 | float32 | Wh | R |
active_consumption_energy_l2 Cumulative active energy imported on phase L2. | 24596 | FC03 | float32 | Wh | R |
active_consumption_energy_l3 Cumulative active energy imported on phase L3. | 24598 | FC03 | float32 | Wh | R |
active_production_energy Cumulative total active energy exported to the grid, watt-hours. | 24600 | FC03 | float32 | Wh | R |
active_production_energy_l1 Cumulative active energy exported on phase L1. | 24606 | FC03 | float32 | Wh | R |
active_production_energy_l2 Cumulative active energy exported on phase L2. | 24608 | FC03 | float32 | Wh | R |
active_production_energy_l3 Cumulative active energy exported on phase L3. | 24610 | FC03 | float32 | Wh | R |