Room Temperature in Celcius | 0 | FC03 | uint16 | °C | R |
Room Temperature in Selected Unit | 1 | FC03 | uint16 | °C | R |
Relative Humidity | 2 | FC03 | uint16 | % | R |
CO2 Value of the Room | 3 | FC03 | uint16 | ppm | R |
Dew Point Temperature in Celcius | 4 | FC03 | uint16 | °C | R |
Dew Point Temperature in Selected Unit | 5 | FC03 | uint16 | °C | R |
Air Quality Status | 6 | FC03 | uint16 | | R |
Digital Input | 7 | FC03 | uint16 | | R |
Bus Termination | 99 | FC03 | uint16 | | R |
Serial Number Device – 1st part | 100 | FC03 | uint16 | | R |
Serial Number Device – 2nd part | 101 | FC03 | uint16 | | R |
Serial Number Device – 4th part | 102 | FC03 | uint16 | | R |
Firmware Version | 103 | FC03 | uint16 | | R |
Display Warning Icon | 10 | FC06 | uint16 | | W |
Display Window Icon | 11 | FC06 | uint16 | | W |
Room/Zone Temperature Setpoint in Celcius | 21 | FC06 | uint16 | °C | W |
Set Ventilation Stage | 22 | FC06 | uint16 | % | W |
System Operation Mode | 30 | FC06 | uint16 | | W |
Ventilation Stage Control Mode | 31 | FC06 | uint16 | | W |
Heating and Cooling Application Status | 32 | FC06 | uint16 | | W |
Enable Local Adjustment | 33 | FC06 | uint16 | | W |
Room/Zone Temperature Setpoint in Selected Unit | 34 | FC06 | uint16 | °C | W |
Relative Room/Zone Temperature Setpoint in Celcius | 35 | FC06 | uint16 | °C | W |
Relative Room/Zone Temperature Setpoint in Selected Unit | 36 | FC06 | uint16 | °C | W |
Room Temperature Offset | 110 | FC06 | uint16 | K | W |
Relative Humidity Offset | 111 | FC06 | uint16 | % | W |
CO2 Value Offset | 112 | FC06 | uint16 | ppm | W |
CO2 Limit for Good Air Quality | 115 | FC06 | uint16 | ppm | W |
CO2 Limit for Medium Air Quality | 116 | FC06 | uint16 | ppm | W |
Air Quality Indication | 117 | FC06 | uint16 | | W |
Window Icon Function | 136 | FC06 | uint16 | | W |
Mode Temperature on Display | 137 | FC06 | uint16 | | W |
Display Ventilation Stages | 138 | FC06 | uint16 | | W |
Select the preferable temperature unit | 120 | FC06 | uint16 | | W |
Unit for temperature shown on display | 121 | FC06 | uint16 | | W |
Select the preferable differential temperature unit | 122 | FC06 | uint16 | | W |
Light/Dark Color Scheme | 130 | FC06 | uint16 | | W |
Display Room/Zone Temperature | 131 | FC06 | uint16 | | W |
Display Relative Humidity | 132 | FC06 | uint16 | | W |
Display CO2 Value | 133 | FC06 | uint16 | | W |
Display Heating/Cooling Icon | 134 | FC06 | uint16 | | W |
Warning Icon Function | 135 | FC06 | uint16 | | W |
Eco Button Mode | 139 | FC06 | uint16 | | W |
Display Boost Button | 140 | FC06 | uint16 | | W |
Mode On/Off Button | 141 | FC06 | uint16 | | W |
Boost Mode Duration | 142 | FC06 | uint16 | s | W |
Temperature Setpoint Type | 145 | FC06 | uint16 | | W |
Default Room Temperature Setpoint | 146 | FC06 | uint16 | | W |
Adjustment range temperature setpoint | 147 | FC06 | uint16 | | W |
Ventilation Stage Configuration | 148 | FC06 | uint16 | | W |
Ventilation Control Mode | 149 | FC06 | uint16 | | W |