Intensis IntesisBox DK-AC-MBS-1 Modbus RTU template

IntesisBox DK-AC-MBS-1

Controls Daikin domestic air conditioners via Modbus RTU interface

Template for the IntesisBox DK-AC-MBS-1, a Modbus RTU interface for Daikin domestic air conditioners. It reads and controls on/off state, operating mode, fan speed, temperature setpoint, vane positions, and alarm status over an EIA-485 connection.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
13, read and write
Key readings
On/Off State · Mode · Fan Speed · Temperature Setpoint · Up/Down and Left/Right Vane Position · Alarm Status and Error Code
Available commands
On/Off · Mode and Fan Speed · Temperature Setpoint · Vane Positions
Compatible models
DK-AC-MBS-1
Last updated

Registers (13)

13 read, 11 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
FanSpeed°CRead and write
Mode°CRead and write
UpDownVanePosition°CRead and write
TemperatureSetpoint°CRead and write
OnOff°CRead and write
WindowContact°CRead and write
ControlDisablement°CRead and write
RemoteControlDisablement°CRead and write
OperationTime°CRead and write
AlarmStatus°CRead
ErrorCode°CRead
LeftRightVanePosition°CRead and write
HumidificationValue°CRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor room temperature setpoints and on/off states across multiple Daikin units on a single dashboard.
  • Create an alert when the DK-AC-MBS-1 reports an alarm status or error code so you can respond before the customer calls.
  • Adjust temperature setpoints and operating modes remotely to support seasonal commissioning or tenant requests.
  • Log fan speed and vane position data over time to verify that scheduled comfort profiles are being followed.
  • Verify correct operation of newly installed Daikin domestic units by checking live Modbus register values from your office.

Installation

  1. Connect the IntesisBox DK-AC-MBS-1 to the Daikin indoor unit using the supplied connector cable, following the IntesisBox wiring diagram.

  2. Wire the RS-485 (A/B) terminals of the DK-AC-MBS-1 to the RS-485 port on your ModbusCloud Gateway, observing correct polarity.

  3. Set the Modbus slave address on the DK-AC-MBS-1 using its DIP switches or configuration tool, and note the address for the next step.

  4. In the ModbusCloud platform, add a new device, select the IntesisBox DK-AC-MBS-1 template, and enter the matching slave address and baud rate (9600, 8N1).

  5. Power on both devices and verify that register values such as on/off state and temperature setpoint appear on the ModbusCloud dashboard.

Things to watch for

What baud rate and serial settings should I use?

The default communication settings for the DK-AC-MBS-1 are 9600 bps, 8 data bits, no parity, 1 stop bit (9600 8N1). Make sure the ModbusCloud gateway port is configured identically.

Why does the temperature setpoint show an incorrect value?

The setpoint register at address 4 is a uint32 value that spans two consecutive 16-bit registers. The ModbusCloud template handles this automatically, but if you have customised the register map, ensure both registers are read together in the correct byte order.

Can I use this template with Daikin commercial or VRV units?

No. The DK-AC-MBS-1 is designed exclusively for the Daikin domestic air conditioning line. Intesis offers separate interfaces for Daikin commercial and VRV systems.

The gateway reads registers but cannot control the unit. What should I check?

Confirm that the DK-AC-MBS-1 is set to allow write access and that the Modbus function code used is correct (typically FC06 or FC16 for writing). Also verify that no other master on the RS-485 bus is conflicting.

Want to see how it works?

Electrician working in an open distribution board