Delta C2000 Plus
Vector control drive for pumps, fans and machines with full status and parameter access.
The Delta C2000 Plus is a vector control drive that runs induction, PM and SynRM motors for pumps, fans, compressors and machines. This Modbus RTU template reads frequency, current, voltage, power, torque, temperatures and fault codes, and lets you start, stop, set the speed and change every drive parameter from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 774, read and write
- Brand
- Delta
- Key readings
- Output frequency · Output current · DC bus voltage · Output power · Motor speed · IGBT temperature · Fault and warning code · Drive status
- Available commands
- Run and stop command · Frequency command · Fault reset · Acceleration and deceleration times · PID settings · Drive parameters
- Compatible models
- VFD-C2000 Plus 230 V models (VFDxxxC23A/E) · VFD-C2000 Plus 460 V models (VFDxxxC43A/E) · VFD-C2000 Plus 575 V and 690 V models · Delta C2000 Plus series vector control drives
- Last updated
Registers (774)
774 read, 656 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Output Frequency | Hz | Read | |||
| Output Current | A | Read | |||
| DC Bus Voltage | V | Read | |||
| Output Voltage | V | Read | |||
| Output Power | kW | Read | |||
| Output Torque | % | Read | |||
| Motor Actual Speed | rpm | Read | |||
| Frequency Command Status | Hz | Read | |||
| Fault Status | Read | ||||
| Drive Operation Status | Read | ||||
| Multi-Step Speed Status | Read | ||||
| Counter Value | Read | ||||
| Output Power Factor Angle | ° | Read | |||
| PG Feedback Pulses | Read | ||||
| PG2 Pulse Commands | Read | ||||
| Multi-Function Display Low Word | Read | ||||
| Maximum User-Defined Value | Read | ||||
| Display Output Current | A | Read | |||
| Display Counter Value | Read | ||||
| Display Output Frequency | Hz | Read | |||
| Display DC Bus Voltage | V | Read | |||
| Display Output Voltage | V | Read | |||
| Power Angle | Read | ||||
| Display Output Power | kW | Read | |||
| Display Motor Speed | rpm | Read | |||
| Display Output Torque | % | Read | |||
| Feedback Position | Read | ||||
| PID Feedback Value | % | Read | |||
| AVI Analog Input | % | Read | |||
| ACI Analog Input | % | Read | |||
| AUI Analog Input | % | Read | |||
| IGBT Temperature | °C | Read | |||
| Capacitor Temperature | °C | Read | |||
| Digital Input Status | Read | ||||
| Digital Output Status | Read | ||||
| Executing Multi-Step Speed | Read | ||||
| CPU Digital Input Pin Status | Read | ||||
| CPU Digital Output Pin Status | Read | ||||
| Actual Motor Position | Read | ||||
| Pulse Input Frequency | Hz | Read | |||
| Pulse Input Position | Read | ||||
| Position Command Tracing Error | Read | ||||
| Overload Counter | % | Read | |||
| Ground Fault GFF | % | Read | |||
| DC Bus Voltage Ripple | V | Read | |||
| PLC Register D1043 | Read | ||||
| PM Magnetic Pole Zone | Read | ||||
| User-Defined Output | Read | ||||
| Pr.00-05 Gain Value | Hz | Read | |||
| Number Of Motor Runs | Read | ||||
| Motor Operating Position | Read | ||||
| Fan Speed | % | Read | |||
| Control Mode Status | Read | ||||
| Carrier Frequency | Read | ||||
| Drive Status | Read | ||||
| Positive Negative Torque | Nm | Read | |||
| Torque Command | % | Read | |||
| kWh Display | kWh | Read | |||
| PG2 Pulse Input Low Word | Read | ||||
| PG2 Pulse Input High Word | Read | ||||
| Motor Actual Position Low Word | Read | ||||
| Motor Actual Position High Word | Read | ||||
| PID Reference | % | Read | |||
| PID Offset | % | Read | |||
| PID Output Frequency | Hz | Read | |||
| Control Board Hardware ID | Read | ||||
| Operation Command | Read and write | ||||
| Frequency Command | Hz | Read and write | |||
| Fault Control Command | Read and write | ||||
| Remote Digital Input MI16-MI1 Status | Read | ||||
| Remote Digital Output Status | Read and write | ||||
| Remote AVI Proportional Value | Read | ||||
| Remote ACI Proportional Value | Read | ||||
| Remote AUI Proportional Value | Read | ||||
| Remote AI10 Input Percentage | Read | ||||
| Remote AI11 Input Percentage | Read | ||||
| Remote AFM1 Output Value | Read and write | ||||
| Remote AFM2 Output Value | Read and write | ||||
| Remote AO10 Output Percentage | Read and write | ||||
| Remote AO11 Output Percentage | Read and write | ||||
| AC Motor Drive Identity Code | Read | ||||
| AC Motor Drive Rated Current Display | Read | ||||
| Parameter Reset | Read and write | ||||
| Start-Up Display | Read and write | ||||
| Content of Multi-Function Display (User-Defined) | Read and write | ||||
| Coefficient Gain in Actual Output Frequency | Read and write | ||||
| Firmware Version | Read | ||||
| Parameter Protection Password Input | Read and write | ||||
| Parameter Protection Password Setting | Read and write | ||||
| Control Mode | Read and write | ||||
| Speed Control Mode | Read and write | ||||
| Point-to-Point Position Mode | Read and write | ||||
| Torque Mode Control | Read and write | ||||
| Duty Selection | Read and write | ||||
| Carrier Frequency (kHz) | Read and write | ||||
| PLC Command Mask | Read | ||||
| Master Frequency Command Source (AUTO) | Read and write | ||||
| Operation Command Source (AUTO) | Read and write | ||||
| Stop Method | Read and write | ||||
| Motor Direction Control | Read and write | ||||
| Digital Operator (Keypad) Frequency Command Memory | Read | ||||
| User Defined Characteristics | Read and write | ||||
| Maximum User-Defined Value (00-26) | Read and write | ||||
| User-Defined Value | Read | ||||
| LOCAL / REMOTE Selection | Read and write | ||||
| Master Frequency Command Source (HAND) | Read and write | ||||
| Operation Command Source (HAND) | Read and write | ||||
| Digital Keypad STOP Function | Read and write | ||||
| RPWM Mode Selection | Read and write | ||||
| RPWM Range | Read and write | ||||
| Over-Modulation Gain | Read and write | ||||
| Display Filter Time (Current) | s | Read and write | |||
| Display Filter Time (Keypad) | s | Read and write | |||
| Software Version (Date) | Read | ||||
| Maximum Operation Frequency | Hz | Read and write | |||
| Motor 1 Rated / Base Frequency | Hz | Read and write | |||
| Motor 1 Rated / Base Output Voltage | V | Read and write | |||
| Motor 1 Mid-Point Frequency 1 | Hz | Read and write | |||
| Motor 1 Mid-Point Voltage 1 | V | Read and write | |||
| Motor 1 Mid-Point Frequency 2 | Hz | Read and write | |||
| Motor 1 Mid-Point Voltage 2 | V | Read and write | |||
| Motor 1 Minimum Output Frequency | Hz | Read and write | |||
| Motor 1 Minimum Output Voltage | V | Read and write | |||
| Start-Up Frequency | Hz | Read and write | |||
| Output Frequency Upper Limit | Hz | Read and write | |||
| Output Frequency Lower Limit | Hz | Read and write | |||
| Acceleration Time 1 | s | Read and write | |||
| Deceleration Time 1 | s | Read and write | |||
| Acceleration Time 2 | s | Read and write | |||
| Deceleration Time 2 | s | Read and write | |||
| Acceleration Time 3 | s | Read and write | |||
| Deceleration Time 3 | s | Read and write | |||
| Acceleration Time 4 | s | Read and write | |||
| Deceleration Time 4 | s | Read and write | |||
| JOG Acceleration Time | s | Read and write | |||
| JOG Deceleration Time | s | Read and write | |||
| JOG Frequency | Hz | Read and write | |||
| Switch Frequency between the First and Fourth Accel./Decel. | Hz | Read and write | |||
| S-Curve for Acceleration Begin Time 1 | s | Read and write | |||
| S-Curve for Acceleration Arrival Time 2 | s | Read and write | |||
| S-Curve for Deceleration Begin Time 1 | s | Read and write | |||
| S-Curve for Deceleration Arrival Time 2 | s | Read and write | |||
| Skip Frequency 1 (Upper Limit) | Hz | Read and write | |||
| Skip Frequency 1 (Lower Limit) | Hz | Read and write | |||
| Skip Frequency 2 (Upper Limit) | Hz | Read and write | |||
| Skip Frequency 2 (Lower Limit) | Hz | Read and write | |||
| Skip Frequency 3 (Upper Limit) | Hz | Read and write | |||
| Skip Frequency 3 (Lower Limit) | Hz | Read and write | |||
| Zero-Speed Mode | Read and write | ||||
| Motor 2 Rated / Base Frequency | Hz | Read and write | |||
| Motor 2 Rated / Base Output Voltage | V | Read and write | |||
| Motor 2 Mid-Point Frequency 1 | Hz | Read and write | |||
| Motor 2 Mid-Point Voltage 1 | V | Read and write | |||
| Motor 2 Mid-Point Frequency 2 | Hz | Read and write | |||
| Motor 2 Mid-Point Voltage 2 | V | Read and write | |||
| Motor 2 Minimum Output Frequency | Hz | Read and write | |||
| Motor 2 Minimum Output Voltage | V | Read and write | |||
| V/F Curve Selection | Read and write | ||||
| Auto-Acceleration and Auto-Deceleration Setting | Read and write | ||||
| Time Unit for Acceleration / Deceleration and S-Curve | Read and write | ||||
| CANopen Quick Stop Time | s | Read and write | |||
| Deceleration Method Selection | Read and write | ||||
| Electromagnetic Traction Energy Consumption Coefficient | Hz | Read and write | |||
| Flux-Weakening Overload Stall Prevention Time | s | Read and write | |||
| Zero-Speed Delay Time | Read and write | ||||
| Zero-Speed Delay Level | Hz | Read and write | |||
| Zero-Speed Delay Time Out | s | Read and write | |||
| Two-Wire / Three-Wire Operation Control | Read and write | ||||
| Multi-Function Input Command 1 (MI1) | Read and write | ||||
| Multi-Function Input Command 2 (MI2) | Read and write | ||||
| Multi-Function Input Command 3 (MI3) | Read and write | ||||
| Multi-Function Input Command 4 (MI4) | Read and write | ||||
| Multi-Function Input Command 5 (MI5) | Read and write | ||||
| Multi-Function Input Command 6 (MI6) | Read and write | ||||
| Multi-Function Input Command 7 (MI7) | Read and write | ||||
| Multi-Function Input Command 8 (MI8) | Read and write | ||||
| Input Terminal of I/O Extension Card (MI10) | Read and write | ||||
| Input Terminal of I/O Extension Card (MI11) | Read and write | ||||
| Input Terminal of I/O Extension Card (MI12) | Read and write | ||||
| Input Terminal of I/O Extension Card (MI13) | Read and write | ||||
| Input Terminal of I/O Extension Card (MI14) | Read and write | ||||
| Input Terminal of I/O Extension Card (MI15) | Read and write | ||||
| External UP / DOWN Key Mode | Read and write | ||||
| Acceleration / Deceleration Speed of External UP / DOWN Key | Hz | Read and write | |||
| Multi-Function Input Response Time | s | Read and write | |||
| Multi-Function Input Mode Selection | Read and write | ||||
| Multi-Function Output 1 (Relay1) | Read and write | ||||
| Multi-Function Output 2 (Relay2) | Read and write | ||||
| Multi-Function Output 3 (MO1) | Read and write | ||||
| Multi-Function Output 4 (MO2) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO10) or (RA10) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO11) or (RA11) | Read and write | ||||
| Output Terminal of I/O Extension Card (RA12) | Read and write | ||||
| Output Terminal of I/O Extension Card (RA13) | Read and write | ||||
| Output Terminal of I/O Extension Card (RA14) | Read and write | ||||
| Output Terminal of I/O Extension Card (RA15) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO16 Virtual Terminal) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO17 Virtual Terminal) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO18 Virtual Terminal) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO19 Virtual Terminal) | Read and write | ||||
| Output Terminal of I/O Extension Card (MO20 Virtual Terminal) | Read and write | ||||
| Multi-Function Output Direction | Read and write | ||||
| Terminal Counting Value Reached (Returns to 0) | Read and write | ||||
| Preliminary Counting Value Reached (Does Not Return to 0) | Read and write | ||||
| Digital Output Gain (DFM) | Read and write | ||||
| Desired Frequency Reached 1 | Hz | Read and write | |||
| The Width of the Desired Frequency Reached 1 | Hz | Read and write | |||
| Desired Frequency Reached 2 | Hz | Read and write | |||
| The Width of the Desired Frequency Reached 2 | Hz | Read and write | |||
| Brake Delay Time | s | Read and write | |||
| Output Current Level Setting for Multi-Function Output Terminal | % | Read and write | |||
| Output Frequency Setting for Multi-Function Output Terminal | Hz | Read and write | |||
| External Operation Control Selection after Reset and Reboot | Read and write | ||||
| Motor Zero-Speed Level | rpm | Read and write | |||
| Maximum Frequency of Resolution Switch | Hz | Read and write | |||
| Switch Delay Time of Maximum Output Frequency | s | Read and write | |||
| Display the Status of Multi-Function Input Terminal | Read | ||||
| Display the Status of Multi-Function Output Terminal | Read | ||||
| Display the External Multi-Function Input Terminals Used by PLC | Read | ||||
| Display the External Multi-Function Output Terminals Used by PLC | Read | ||||
| Display the Frequency Command Executed by External Terminal | Hz | Read | |||
| Brake Release Check Time | s | Read and write | |||
| Multi-Function Output Terminal (Function 42): Brake Current | % | Read and write | |||
| Multi-Function Output Terminal (Function 42): Brake Frequency | Hz | Read and write | |||
| Frequency Reached Detection Amplitude | Hz | Read and write | |||
| IO Card Types | Read | ||||
| DFM Output Selection | Read and write | ||||
| Internal / External Multi-Function Input Terminal Selection | Read and write | ||||
| Internal Multi-Function Output Terminal Selection | Read and write | ||||
| AVI Analog Input Selection | Read and write | ||||
| ACI Analog Input Selection | Read and write | ||||
| AUI Analog Input Selection | Read and write | ||||
| AVI Analog Input Bias | % | Read and write | |||
| ACI Analog Input Bias | % | Read and write | |||
| AUI Analog Input Bias | % | Read and write | |||
| AVI Positive / Negative Bias Mode | Read and write | ||||
| ACI Positive / Negative Bias Mode | Read and write | ||||
| AUI Positive / Negative Bias Mode | Read and write | ||||
| Reverse Setting When Analog Signal Input is Negative Frequency | Read and write | ||||
| AVI Analog Input Gain | % | Read and write | |||
| ACI Analog Input Gain | % | Read and write | |||
| AUI Analog Positive Input Gain | % | Read and write | |||
| AUI Analog Negative Input Gain | % | Read and write | |||
| AVI Analog Input Filter Time | s | Read and write | |||
| ACI Analog Input Filter Time | s | Read and write | |||
| AUI Analog Input Filter Time | s | Read and write | |||
| Analog Input Addition Function | Read and write | ||||
| Signal Loss Selection for the Analog Input 4 to 20 mA | Read and write | ||||
| AFM1 Multi-Function Output 1 | Read and write | ||||
| AFM2 Multi-Function Output 2 | Read and write | ||||
| AFM1 Analog Output Gain 1 | % | Read and write | |||
| AFM1 Analog Output 1 in REV Direction | Read and write | ||||
| AFM2 Analog Output Gain 2 | % | Read and write | |||
| AFM2 Analog Output 2 in REV Direction | Read and write | ||||
| AFM2 Output Bias | % | Read and write | |||
| AVI Terminal Input Selection | Read and write | ||||
| ACI Terminal Input Selection | Read and write | ||||
| PLC Analog Output Terminal Status | Read | ||||
| AFM2 Output Selection | Read and write | ||||
| AFM1 DC Output Setting Level | % | Read and write | |||
| AFM2 DC Output Setting Level | % | Read and write | |||
| AFM1 Output Filter Time | s | Read and write | |||
| AFM2 Output Filter Time | s | Read and write | |||
| Multi-Function Output (MO) By AI Level Source | Read and write | ||||
| AI Upper Level (MO) | % | Read and write | |||
| AI Lower Level (MO) | % | Read and write | |||
| Analog Input Curve Selection | Read and write | ||||
| AVI Lowest Point | V | Read and write | |||
| AVI Proportional Lowest Point | % | Read and write | |||
| AVI Mid-Point | V | Read and write | |||
| AVI Proportional Mid-Point | % | Read and write | |||
| AVI Highest Point | V | Read and write | |||
| AVI Proportional Highest Point | % | Read and write | |||
| ACI Lowest Point | mA | Read and write | |||
| ACI Proportional Lowest Point | % | Read and write | |||
| ACI Mid-Point | mA | Read and write | |||
| ACI Proportional Mid-Point | % | Read and write | |||
| ACI Highest Point | mA | Read and write | |||
| ACI Proportional Highest Point | % | Read and write | |||
| Positive AUI Voltage Lowest Point | V | Read and write | |||
| Positive AUI Voltage Proportional Lowest Point | % | Read and write | |||
| Positive AUI Voltage Mid-Point | V | Read and write | |||
| Positive AUI Voltage Proportional Mid-Point | % | Read and write | |||
| Positive AUI Voltage Highest Point | V | Read and write | |||
| Positive AUI Voltage Proportional Highest Point | % | Read and write | |||
| Negative AUI Voltage Highest Point | V | Read and write | |||
| Negative AUI Voltage Proportional Highest Point | % | Read and write | |||
| Negative AUI Voltage Mid-Point | V | Read and write | |||
| Negative AUI Voltage Proportional Mid-Point | % | Read and write | |||
| Negative AUI Voltage Lowest Point | V | Read and write | |||
| Negative AUI Voltage Proportional Lowest Point | % | Read and write | |||
| 1st Step Speed Frequency | Hz | Read and write | |||
| 2nd Step Speed Frequency | Hz | Read and write | |||
| 3rd Step Speed Frequency | Hz | Read and write | |||
| 4th Step Speed Frequency | Hz | Read and write | |||
| 5th Step Speed Frequency | Hz | Read and write | |||
| 6th Step Speed Frequency | Hz | Read and write | |||
| 7th Step Speed Frequency | Hz | Read and write | |||
| 8th Step Speed Frequency | Hz | Read and write | |||
| 9th Step Speed Frequency | Hz | Read and write | |||
| 10th Step Speed Frequency | Hz | Read and write | |||
| 11th Step Speed Frequency | Hz | Read and write | |||
| 12th Step Speed Frequency | Hz | Read and write | |||
| 13th Step Speed Frequency | Hz | Read and write | |||
| 14th Step Speed Frequency | Hz | Read and write | |||
| 15th Step Speed Frequency | Hz | Read and write | |||
| Position Command 1 (Rotation) | Read and write | ||||
| Position Command 1 (Pulse) | Read and write | ||||
| Position Command 2 (Rotation) | Read and write | ||||
| Position Command 2 (Pulse) | Read and write | ||||
| Position Command 3 (Rotation) | Read and write | ||||
| Position Command 3 (Pulse) | Read and write | ||||
| Position Command 4 (Rotation) | Read and write | ||||
| Position Command 4 (Pulse) | Read and write | ||||
| Position Command 5 (Rotation) | Read and write | ||||
| Position Command 5 (Pulse) | Read and write | ||||
| Position Command 6 (Rotation) | Read and write | ||||
| Position Command 6 (Pulse) | Read and write | ||||
| Position Command 7 (Rotation) | Read and write | ||||
| Position Command 7 (Pulse) | Read and write | ||||
| Position Command 8 (Rotation) | Read and write | ||||
| Position Command 8 (Pulse) | Read and write | ||||
| Position Command 9 (Rotation) | Read and write | ||||
| Position Command 9 (Pulse) | Read and write | ||||
| Position Command 10 (Rotation) | Read and write | ||||
| Position Command 10 (Pulse) | Read and write | ||||
| Position Command 11 (Rotation) | Read and write | ||||
| Position Command 11 (Pulse) | Read and write | ||||
| Position Command 12 (Rotation) | Read and write | ||||
| Position Command 12 (Pulse) | Read and write | ||||
| Position Command 13 (Rotation) | Read and write | ||||
| Position Command 13 (Pulse) | Read and write | ||||
| Position Command 14 (Rotation) | Read and write | ||||
| Position Command 14 (Pulse) | Read and write | ||||
| Position Command 15 (Rotation) | Read and write | ||||
| Position Command 15 (Pulse) | Read and write | ||||
| PLC Buffer 0 | Read and write | ||||
| PLC Buffer 1 | Read and write | ||||
| PLC Buffer 2 | Read and write | ||||
| PLC Buffer 3 | Read and write | ||||
| PLC Buffer 4 | Read and write | ||||
| PLC Buffer 5 | Read and write | ||||
| PLC Buffer 6 | Read and write | ||||
| PLC Buffer 7 | Read and write | ||||
| PLC Buffer 8 | Read and write | ||||
| PLC Buffer 9 | Read and write | ||||
| PLC Buffer 10 | Read and write | ||||
| PLC Buffer 11 | Read and write | ||||
| PLC Buffer 12 | Read and write | ||||
| PLC Buffer 13 | Read and write | ||||
| PLC Buffer 14 | Read and write | ||||
| PLC Buffer 15 | Read and write | ||||
| PLC Buffer 16 | Read and write | ||||
| PLC Buffer 17 | Read and write | ||||
| PLC Buffer 18 | Read and write | ||||
| PLC Buffer 19 | Read and write | ||||
| PLC Application Parameter 0 | Read and write | ||||
| PLC Application Parameter 1 | Read and write | ||||
| PLC Application Parameter 2 | Read and write | ||||
| PLC Application Parameter 3 | Read and write | ||||
| PLC Application Parameter 4 | Read and write | ||||
| PLC Application Parameter 5 | Read and write | ||||
| PLC Application Parameter 6 | Read and write | ||||
| PLC Application Parameter 7 | Read and write | ||||
| PLC Application Parameter 8 | Read and write | ||||
| PLC Application Parameter 9 | Read and write | ||||
| PLC Application Parameter 10 | Read and write | ||||
| PLC Application Parameter 11 | Read and write | ||||
| PLC Application Parameter 12 | Read and write | ||||
| PLC Application Parameter 13 | Read and write | ||||
| PLC Application Parameter 14 | Read and write | ||||
| PLC Application Parameter 15 | Read and write | ||||
| PLC Application Parameter 16 | Read and write | ||||
| PLC Application Parameter 17 | Read and write | ||||
| PLC Application Parameter 18 | Read and write | ||||
| PLC Application Parameter 19 | Read and write | ||||
| PLC Application Parameter 20 | Read and write | ||||
| PLC Application Parameter 21 | Read and write | ||||
| PLC Application Parameter 22 | Read and write | ||||
| PLC Application Parameter 23 | Read and write | ||||
| PLC Application Parameter 24 | Read and write | ||||
| PLC Application Parameter 25 | Read and write | ||||
| PLC Application Parameter 26 | Read and write | ||||
| PLC Application Parameter 27 | Read and write | ||||
| PLC Application Parameter 28 | Read and write | ||||
| PLC Application Parameter 29 | Read and write | ||||
| Motor Parameter Auto-Tuning | Read and write | ||||
| Full-Load Current for Induction Motor 1 (A) | Read and write | ||||
| Rated Power for Induction Motor 1 (kW) | kW | Read and write | |||
| Rated Speed for Induction Motor 1 (rpm) | Read and write | ||||
| Number of Poles for Induction Motor 1 | Read and write | ||||
| No-Load Current for Induction Motor 1 (A) | Read and write | ||||
| Stator Resistance (Rs) for Induction Motor 1 | Read and write | ||||
| Rotor Resistance (Rr) for Induction Motor 1 | Read and write | ||||
| Magnetizing Inductance (Lm) for Induction Motor 1 | Read and write | ||||
| Stator Inductance (Lx) for Induction Motor 1 | Read and write | ||||
| Full-Load Current for Induction Motor 2 (A) | Read and write | ||||
| Rated Power for Induction Motor 2 (kW) | kW | Read and write | |||
| Rated Speed for Induction Motor 2 (rpm) | Read and write | ||||
| Number of Poles for Induction Motor 2 | Read and write | ||||
| No-Load Current for Induction Motor 2 (A) | Read and write | ||||
| Stator Resistance (Rs) for Induction Motor 2 | Read and write | ||||
| Rotor Resistance (Rr) for Induction Motor 2 | Read and write | ||||
| Magnetizing Inductance (Lm) for Induction Motor 2 | Read and write | ||||
| Stator Inductance (Lx) for Induction Motor 2 | Read and write | ||||
| Induction Motor 1 / 2 Selection | Read and write | ||||
| Frequency for Y-Connection / ∆- Connection Switch for an | Hz | Read and write | |||
| Y-Connection / ∆-Connection Switch for an Induction Motor | Read and write | ||||
| Delay Time for Y-Connection / ∆- Connection Switch for an | s | Read and write | |||
| Accumulated Watt-Hour for a Running Motor (Wh) | Read | ||||
| Accumulated Kilowatt-Hour for a Running Motor (kWh) | Read | ||||
| Accumulated Megawatt-Hour for a Motor in High Word (MWh) | Read | ||||
| Accumulated Motor Running Time (Minutes) | Read and write | ||||
| Accumulated Motor Running Time (Days) | Read and write | ||||
| Induction Motor (IM) or Permanent Magnet Synchronous AC Motor | Read and write | ||||
| Full-Load Current for a Permanent Magnet Synchronous AC Motor | Read and write | ||||
| Rated Power for a Permanent Magnet Synchronous AC Motor | kW | Read and write | |||
| Rated Speed for a Permanent Magnet Synchronous AC Motor | rpm | Read and write | |||
| Number of Poles for a Permanent Magnet Synchronous AC Motor | Read and write | ||||
| System Inertia for a Permanent Magnet Synchronous AC Motor | Read and write | ||||
| Stator Resistance for a Permanent Magnet Synchronous AC Motor | Read and write | ||||
| Permanent Magnet Synchronous AC Motor / Reluctance Motor Ld | Read and write | ||||
| Permanent Magnet Synchronous AC Motor / Reluctance Motor Lq | Read and write | ||||
| PG Offset Angle for a Permanent Magnet Synchronous AC Motor | Read and write | ||||
| Ke Parameter of a Permanent Magnet Synchronous AC Motor | Read and write | ||||
| Low Voltage Level | V | Read and write | |||
| Over-Voltage Stall Prevention | V | Read and write | |||
| Selection for Over-Voltage Stall Prevention | Read and write | ||||
| Over-Current Stall Prevention during Acceleration | % | Read and write | |||
| Over-Current Stall Prevention during Operation | % | Read and write | |||
| Acceleration / Deceleration Time Selection for Stall Prevention | Read and write | ||||
| Over-Torque Detection Selection (OT1) | Read and write | ||||
| Over-Torque Detection Level (OT1) | % | Read and write | |||
| Over-Torque Detection Time (OT1) | s | Read and write | |||
| Over-Torque Detection Selection (OT2) | Read and write | ||||
| Over-Torque Detection Level (OT2) | % | Read and write | |||
| Over-Torque Detection Time (OT2) | s | Read and write | |||
| Current Limit | % | Read and write | |||
| Electronic Thermal Relay Selection 1 (Motor 1) | Read and write | ||||
| Electronic Thermal Relay Action Time 1 (Motor 1) | s | Read and write | |||
| Temperature Level Overheat (OH) Warning | °C | Read and write | |||
| Stall Prevention Limit Level | % | Read and write | |||
| Fault Record 1 | Read and write | ||||
| Fault Record 2 | Read and write | ||||
| Fault Record 3 | Read and write | ||||
| Fault Record 4 | Read and write | ||||
| Fault Record 5 | Read and write | ||||
| Fault Record 6 | Read and write | ||||
| Fault Output Option 1 | Read and write | ||||
| Fault Output Option 2 | Read and write | ||||
| Fault Output Option 3 | Read and write | ||||
| Fault Output Option 4 | Read and write | ||||
| Electronic Thermal Relay Selection 2 (Motor 2) | Read and write | ||||
| Electronic Thermal Relay Action Time 2 (Motor 2) | s | Read and write | |||
| PTC Detection Selection / PT100 Motion | Read and write | ||||
| PTC Level / KTY84 Level | % | Read and write | |||
| Frequency Command at Malfunction | Hz | Read | |||
| Output Frequency at Malfunction | Hz | Read | |||
| Output Voltage at Malfunction | V | Read | |||
| DC Bus Voltage at Malfunction | V | Read | |||
| Output Current at Malfunction | Read | ||||
| IGBT Temperature at Malfunction | °C | Read | |||
| Capacitance Temperature at Malfunction | °C | Read | |||
| Motor Speed at Malfunction | rpm | Read | |||
| Torque Command at Malfunction | % | Read | |||
| Status of the Multi-Function Input Terminal at Malfunction | Read | ||||
| Status of the Multi-Function Output Terminal at Malfunction | Read | ||||
| Drive Status at Malfunction | Read | ||||
| STO Latch Selection | Read and write | ||||
| Output Phase Loss Detection Action (OPHL) | Read and write | ||||
| Detection Time for Output Phase Loss | s | Read and write | |||
| Current Detection Level for Output Phase Loss | % | Read and write | |||
| DC Brake Time for Output Phase Loss | s | Read and write | |||
| Lvx Auto-Reset | Read and write | ||||
| Time for Input Phase Loss Detection | s | Read and write | |||
| Capacitance oH Warning Level (Applied to 230V / 460V Models) | Read and write | ||||
| Ripple of Input Phase Loss | V | Read and write | |||
| Input Phase Loss Detection Action (OrP) | Read and write | ||||
| Derating Protection | Read and write | ||||
| PT100 Voltage Level 1 | V | Read and write | |||
| PT100 Voltage Level 2 | V | Read and write | |||
| PT100 Level 1 Frequency Protection | Hz | Read and write | |||
| PT100 Activation Level 1 Protection Frequency Delay Time | s | Read and write | |||
| Software Detection GFF Current Level | % | Read and write | |||
| Software Detection GFF Filter Time | s | Read and write | |||
| dEb Reset Bias Level (Applied to 230V / 460V Models) | V | Read and write | |||
| Operation Time of Fault Record 1 (Days) | Read | ||||
| Operation Time of Fault Record 1 (Minutes) | min | Read | |||
| Operation Time of Fault Record 2 (Days) | Read | ||||
| Operation Time of Fault Record 2 (Minutes) | min | Read | |||
| Operation Time of Fault Record 3 (Days) | Read | ||||
| Operation Time of Fault Record 3 (Minutes) | min | Read | |||
| Operation Time of Fault Record 4 (Days) | Read | ||||
| Operation Time of Fault Record 4 (Minutes) | min | Read | |||
| Low Current Setting Level | % | Read and write | |||
| Low Current Detection Time | s | Read and write | |||
| Low Current Action | Read and write | ||||
| PTC Type (Applied to 230V / 460V Models) | Read and write | ||||
| Software Brake Chopper Action Level | V | Read and write | |||
| DC Brake Current Level | % | Read and write | |||
| DC Brake Time at Start-Up | s | Read and write | |||
| DC Brake Time at STOP | s | Read and write | |||
| DC Brake Frequency at STOP | Hz | Read and write | |||
| Voltage Increasing Gain | % | Read and write | |||
| Restart after Momentary Power Loss | Read and write | ||||
| Allowed Power Loss Duration | s | Read and write | |||
| Base Block Time | s | Read and write | |||
| Current Limit of Speed Tracking | % | Read and write | |||
| Restart after Fault Action | Read and write | ||||
| Number of Times of Restart after Fault | Read and write | ||||
| Speed Tracking during Start-Up | Read and write | ||||
| dEb Function Selection | Read and write | ||||
| dEb Function Reset Time | s | Read and write | |||
| Dwell Time at Acceleration | s | Read and write | |||
| Dwell Frequency at Acceleration | Hz | Read and write | |||
| Dwell Time at Deceleration | s | Read and write | |||
| Dwell Frequency at Deceleration | Hz | Read and write | |||
| Fan Cooling Control | Read and write | ||||
| Emergency Stop (EF) & Force to Stop Selection | Read and write | ||||
| Automatic Energy-Saving Selection | Read and write | ||||
| Automatic Voltage Regulation (AVR) Function | Read and write | ||||
| Torque Command Filter Time | s | Read and write | |||
| Slip Compensation Filter Time | s | Read and write | |||
| Torque Compensation Gain | Read and write | ||||
| Slip Compensation Gain | Read and write | ||||
| Slip Deviation Level | % | Read and write | |||
| Over-Slip Deviation Detection Time | s | Read and write | |||
| Over-Slip Deviation Treatment | Read and write | ||||
| Motor Oscillation Compensation Factor | Read and write | ||||
| Auto-Restart Interval of Fault | s | Read and write | |||
| PMSVC Voltage Feed Forward Gain | Read and write | ||||
| Minimum Frequency for AES | Hz | Read and write | |||
| Delay Time for AES | s | Read and write | |||
| Targeted Power Factor Angle for AES | Read and write | ||||
| Maximum Voltage Drop for AES | % | Read and write | |||
| AES Coefficient | % | Read and write | |||
| dEb Gain (Kp) | Read and write | ||||
| dEb Gain (Ki) | Read and write | ||||
| Terminal Selection of PID Feedback | Read and write | ||||
| Proportional Gain (P) | Read and write | ||||
| Integral Time (I) | s | Read and write | |||
| Differential Time (D) | s | Read and write | |||
| Upper Limit of Integral Control | % | Read and write | |||
| PID Output Command Limit | % | Read and write | |||
| PID Feedback Value by Communication Protocol | % | Read | |||
| PID Delay Time | s | Read and write | |||
| Feedback Signal Detection Time | s | Read and write | |||
| Feedback Signal Fault Treatment | Read and write | ||||
| Sleep Level | Hz | Read and write | |||
| Wake-Up Level | Hz | Read and write | |||
| Sleep Delay Time | s | Read and write | |||
| PID Feedback Signal Error Deviation Level | % | Read and write | |||
| PID Feedback Signal Error Deviation Detection Time | s | Read and write | |||
| PID Compensation Selection | Read and write | ||||
| PID Compensation | % | Read and write | |||
| Sleep Mode Function Setting | Read and write | ||||
| Wake-Up Integral Limit | % | Read and write | |||
| PID Mode Selection | Read and write | ||||
| Enable PID to Change the Operation Direction | Read and write | ||||
| Wake-Up Delay Time | s | Read and write | |||
| PID Control Flag | Read and write | ||||
| Modbus Slave Communication Address | Read and write | ||||
| COM1 Modbus Transmission Speed | Read and write | ||||
| COM1 Modbus Transmission Fault Treatment | Read and write | ||||
| COM1 Modbus Time-Out Detection | s | Read and write | |||
| COM1 Modbus Communication Protocol | Read and write | ||||
| Modbus Communication Response Delay Time | ms | Read and write | |||
| Communication Main Frequency | Hz | Read and write | |||
| Block Transfer 1 | Read and write | ||||
| Block Transfer 2 | Read and write | ||||
| Block Transfer 3 | Read and write | ||||
| Block Transfer 4 | Read and write | ||||
| Block Transfer 5 | Read and write | ||||
| Block Transfer 6 | Read and write | ||||
| Block Transfer 7 | Read and write | ||||
| Block Transfer 8 | Read and write | ||||
| Block Transfer 9 | Read and write | ||||
| Block Transfer 10 | Read and write | ||||
| Block Transfer 11 | Read and write | ||||
| Block Transfer 12 | Read and write | ||||
| Block Transfer 13 | Read and write | ||||
| Block Transfer 14 | Read and write | ||||
| Block Transfer 15 | Read and write | ||||
| Block Transfer 16 | Read and write | ||||
| Communication Decoding Method | Read and write | ||||
| Internal Communication Protocol | Read and write | ||||
| PLC Command Force to 0 | Read and write | ||||
| PLC Address | Read and write | ||||
| CANopen Slave Address | Read and write | ||||
| CANopen Speed | Read and write | ||||
| CANopen Warning Record | Read | ||||
| CANopen Decoding Method | Read and write | ||||
| CANopen Communication Status | Read | ||||
| CANopen Control Status | Read | ||||
| CANopen Master Function | Read and write | ||||
| CANopen Master Address | Read and write | ||||
| CANopen Extension Setting | Read and write | ||||
| Communication Card Identification | Read | ||||
| Firmware Version of Communication Card | Read | ||||
| Product Code | Read | ||||
| Error Code | Read | ||||
| Communication Card Address (for DeviceNet or PROFIBUS) | Read and write | ||||
| Communication Card Speed Setting (for DeviceNet) | Read and write | ||||
| Additional Settings for Communication Card Speed (for DeviceNet) | Read and write | ||||
| Communication Card Control Flag | Read and write | ||||
| Communication Card IP Configuration (for EtherNet) | Read and write | ||||
| Communication Card IP Address 1 (for EtherNet) | Read and write | ||||
| Communication Card IP Address 2 (for EtherNet) | Read and write | ||||
| Communication Card IP Address 3 (for EtherNet) | Read and write | ||||
| Communication Card IP Address 4 (for EtherNet) | Read and write | ||||
| Communication Card Address Mask 1 (for EtherNet) | Read and write | ||||
| Communication Card Address Mask 2 (for EtherNet) | Read and write | ||||
| Communication Card Address Mask 3 (for EtherNet) | Read and write | ||||
| Communication Card Address Mask 4 (for EtherNet) | Read and write | ||||
| Communication Card Gateway Address 1 (for EtherNet) | Read and write | ||||
| Communication Card Gateway Address 2 (for EtherNet) | Read and write | ||||
| Communication Card Gateway Address 3 (for EtherNet) | Read and write | ||||
| Communication Card Gateway Address 4 (for EtherNet) | Read and write | ||||
| Communication Card Password (Low Word) (for EtherNet) | Read and write | ||||
| Communication Card Password (High Word) (for EtherNet) | Read and write | ||||
| Reset Communication Card (for EtherNet) | Read and write | ||||
| Additional Settings for the Communication Card (for EtherNet) | Read and write | ||||
| Communication Card Status (for EtherNet) | Read and write | ||||
| Encoder Type Selection | Read and write | ||||
| Encoder Pulses Per Revolution | Read and write | ||||
| Encoder Input Type Setting | Read and write | ||||
| Frequency Division Output Setting (Denominator) | Read and write | ||||
| Mechanical Gear at Load Side A1 | Read and write | ||||
| Mechanical Gear at Motor Side B1 | Read and write | ||||
| Mechanical Gear at Load Side A2 | Read and write | ||||
| Mechanical Gear at Motor Side B2 | Read and write | ||||
| Treatment for Encoder / Speed Observer Feedback Fault | Read and write | ||||
| Detection Time of Encoder / Speed Observer Feedback Fault | s | Read and write | |||
| Encoder / Speed Observer Stall Level | % | Read and write | |||
| Detection Time of Encoder / Speed Observer Stall | s | Read and write | |||
| Encoder / Speed Observer Stall Action | Read and write | ||||
| Encoder / Speed Observer Slip Range | % | Read and write | |||
| Detection Time of Encoder / Speed Observer Slip | s | Read and write | |||
| Encoder / Speed Observer Stall and Slip Error Action | Read and write | ||||
| Pulse Input Type Setting | Read and write | ||||
| Electrical Gear A | Read and write | ||||
| Electrical Gear B | Read and write | ||||
| Encoder Single-Turn Resolution | Read and write | ||||
| Encoder Multi-Turn Resolution | Read and write | ||||
| PG2 Pulse Input Speed Command Low Pass Filter Time | s | Read and write | |||
| PG Control Flag | Read and write | ||||
| FOC & TQC Function Control | Read and write | ||||
| FOC Bandwidth for Speed Observer | Hz | Read and write | |||
| FOC Minimum Stator Frequency | % | Read and write | |||
| FOC Low-Pass Filter Time Constant | ms | Read and write | |||
| FOC Gain for Excitation Current Rise Time | % | Read and write | |||
| Upper Limit of Frequency Deviation | Hz | Read and write | |||
| Resolver Pole Pair | Read and write | ||||
| I/F Mode, Current Command | % | Read and write | |||
| PM FOC Sensorless Speed Estimator Bandwidth (High Speed) | Hz | Read and write | |||
| PM FOC Sensorless Speed Estimator Bandwidth (Low Speed) | Hz | Read and write | |||
| PM Sensorless Speed Estimator Low-Pass Filter Gain | Read and write | ||||
| AMR (Kp) Gain | Read and write | ||||
| AMR (Ki) Gain | Read and write | ||||
| PM Sensorless Control Word | Read and write | ||||
| Frequency to Switch from I/F Mode to PM Sensorless Mode | Hz | Read and write | |||
| Frequency to Switch from PM Sensorless Mode to I/F Mode | Hz | Read and write | |||
| I/F Mode, Id Current Low Pass-Filter Time | s | Read and write | |||
| Initial Angle Detection Pulse Value | Read and write | ||||
| PG Card Version | Read | ||||
| PG1 Pulse Imputation Scaling Factor | Read and write | ||||
| Zero Voltage Time During Start-Up | s | Read and write | |||
| Reverse Angle Limit (Electrical Angle) | Read and write | ||||
| Injection Frequency | Hz | Read and write | |||
| Injection Magnitude | V | Read and write | |||
| PM Initial Rotor Position Detection Method | Read and write | ||||
| Magnetic Flux Linkage Estimate Low-Speed Gain | % | Read and write | |||
| Magnetic Flux Linkage Estimate High-Speed Gain | % | Read and write | |||
| Kp of Phase-Locked Loop | % | Read and write | |||
| Ki of Phase-Locked Loop | % | Read and write | |||
| Mutual Inductance Gain Compensation | Read and write | ||||
| Coordinate Axis System Setting | Read and write | ||||
| Mechanical Cycle Range (High Word) | Read and write | ||||
| Mechanical Cycle Range (Low Word) | Read and write | ||||
| System Control | Read and write | ||||
| Per-Unit of System Inertia | Read and write | ||||
| ASR1 / ASR2 Switch Frequency | Hz | Read and write | |||
| ASR1 Low-Speed Bandwidth | Read and write | ||||
| ASR2 High-Speed Bandwidth | Read and write | ||||
| Zero-Speed Bandwidth | Read and write | ||||
| ASR 1 Gain | Hz | Read and write | |||
| ASR 1 Integral Time | s | Read and write | |||
| ASR 2 Gain | Hz | Read and write | |||
| ASR 2 Integral Time | s | Read and write | |||
| ASR Gain of Zero Speed | Hz | Read and write | |||
| ASR1 Integral Time of Zero Speed | s | Read and write | |||
| Gain for ASR Speed Feed Forward | % | Read and write | |||
| PDFF Gain Value | % | Read and write | |||
| ASR Output Low Pass Filter Time | s | Read and write | |||
| Notch Filter Depth | Read and write | ||||
| Notch Filter Frequency | Hz | Read and write | |||
| Forward Motor Torque Limit Quadrant I | % | Read and write | |||
| Forward Regenerative Torque Limit Quadrant II | % | Read and write | |||
| Reverse Motor Torque Limit Quadrant III | % | Read and write | |||
| Reverse Regenerative Torque Limit Quadrant IV | % | Read and write | |||
| Flux Weakening Curve for Motor 1 Gain Value | % | Read and write | |||
| Flux Weakening Curve for Motor 2 Gain Value | % | Read and write | |||
| Flux Weakening Area Speed Response | % | Read and write | |||
| APR Gain | Hz | Read and write | |||
| Gain Value for the APR Feed Forward | Read and write | ||||
| APR Feedforward Low Pass Filter Bandwidth | s | Read and write | |||
| Maximum Torque Command | % | Read and write | |||
| Torque Offset Source | Read and write | ||||
| Torque Offset Setting | % | Read and write | |||
| High Torque Offset | % | Read and write | |||
| Middle Torque Offset | % | Read and write | |||
| Low Torque Offset | % | Read and write | |||
| Torque Command Source | Read and write | ||||
| Torque Command (11-34) | % | Read and write | |||
| Torque Command Filter Time (11-35) | s | Read and write | |||
| Speed Limit Selection | Read and write | ||||
| Forward Speed Limit (Torque Mode) | % | Read and write | |||
| Reverse Speed Limit (Torque Mode) | % | Read and write | |||
| Zero Torque Command Mode Selection | Read and write | ||||
| Position Control Command Source | Read and write | ||||
| System Control Flag | Read and write | ||||
| Position Control Maximum Frequency | Hz | Read and write | |||
| Position Control Acceleration Time | s | Read and write | |||
| Position Control Deceleration Time | s | Read and write | |||
| Torque Output Filter Time (Applied to 230V / 460V Models) | s | Read and write | |||
| Notch Filter Bandwidth | Hz | Read and write | |||
| ASR Feed Forward Filter Time | s | Read and write | |||
| Inertia Estimation Filter Time | s | Read and write | |||
| APR S-Curve Time | Read and write | ||||
| Maximum Allowable Position Error | Read and write | ||||
| Allowable Position Error Range | Read and write | ||||
| Allowable Position Error Cumulative Time | s | Read and write | |||
| Treatment to the Large Position Control Error | Read and write | ||||
| Software Positive Limit (High Word) | Read and write | ||||
| Software Positive Limit (Low Word) | Read and write | ||||
| Software Negative Limit (High Word) | Read and write | ||||
| Software Negative Limit (Low Word) | Read and write | ||||
| Position Control Bit | Read and write | ||||
| Encoder at Load Side ppr Number (High Byte) | Read and write | ||||
| Encoder at Load Side ppr Number (Low Byte) | Read and write | ||||
| Single-Point Positioning Rising Speed | Read and write | ||||
| Single-Point Positioning Position (High Byte) | Read and write | ||||
| Single-Point Positioning Position (Low Byte) | Read and write | ||||
| Homing Method | Read and write | ||||
| Homing Control Time Out | s | Read and write | |||
| Homing Control 1st Step Speed | Hz | Read and write | |||
| Homing Control 2nd Step Speed | Hz | Read and write | |||
| Homing Control Acceleration / Deceleration Time 1st | s | Read and write | |||
| Homing Control Offset (Revolution) | Read and write | ||||
| Homing Control Offset (Pulse) | Read and write | ||||
| Position Record (Revolution) | Read and write | ||||
| Position Record (Pulse) | Read and write | ||||
| HALT Revived Selection | Read and write | ||||
| Industry-Specific Parameter Application | Read and write | ||||
| Extension Card Input Terminal Selection (AI10) | Read and write | ||||
| Extension Card Input Terminal Selection (AI11) | Read and write | ||||
| Analog Input Filter Time (AI10) | s | Read and write | |||
| Analog Input Filter Time (AI11) | s | Read and write | |||
| Analog Input 4 to 20 mA Signal Loss Selection (AI10) | Read and write | ||||
| Analog Input 4 to 20 mA Signal Loss Selection (AI11) | Read and write | ||||
| Extension Card Output Terminal Selection (AO10) | Read and write | ||||
| Extension Card Output Terminal Selection (AO11) | Read and write | ||||
| Analog Output 1 Gain Output (AO10) | % | Read and write | |||
| Analog Output 1 Gain Output (AO11) | % | Read and write | |||
| Analog Output 1 in 0 to 10 V REV Direction (AO10) | Read and write | ||||
| Analog Output 1 in 0 to 10 V REV Direction (AO11) | Read and write | ||||
| Extension Card Input Selection (AI10) | Read and write | ||||
| Extension Card Input Selection (AI11) | Read and write | ||||
| AO10 DC Output Setting Level | % | Read and write | |||
| AO11 DC Output Setting Level | % | Read and write | |||
| AO10 Filter Output Time | s | Read and write | |||
| AO11 Filter Output Time | s | Read and write | |||
| AO10 Output Selection | Read and write | ||||
| AO11 Output Selection | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show output frequency, current and power of every drive on a ModbusCloud dashboard.
- Send an email when the fault code is not 0, so you know a drive has tripped.
- Track IGBT temperature and DC bus voltage in the history to spot cooling or supply problems.
- Change the frequency command or a PID setpoint remotely from ModbusCloud.
- Compare kWh and motor speed over months to see how a pump or fan is used.
Installation
Connect SG+ and SG- of the RS-485 port to A and B on the ModbusCloud Gateway and terminate the end of the bus.
Set Pr.09-00 to the Modbus address, Pr.09-01 to the speed and Pr.09-04 to 13 (RTU 8N2) or another RTU format.
Set Pr.09-30 to 0, and Pr.00-21 to 2 and Pr.00-20 to 1 if ModbusCloud should start the drive and set the speed.
In ModbusCloud, add a Modbus device with the same address and serial settings and import this template.
Check that output frequency and drive status come in before writing commands.
Things to watch for
The drive does not answer at all. What should I check?
The factory protocol of Pr.09-04 is ASCII, which a Modbus RTU master cannot read. Set Pr.09-04 to an RTU format such as 13 (8N2) and match speed and address with Pr.09-01 and Pr.09-00. Then check that SG+ and SG- are not swapped and that the bus is terminated.
Writing the operation command or frequency does nothing.
Pr.09-30 must be 0 so the drive accepts commands on 2000H to 2002H; the factory setting 1 uses another address range. The command source must be RS-485 (Pr.00-21 = 2) and the frequency source RS-485 (Pr.00-20 = 1), otherwise the drive ignores bus commands.
Why is the current value off by a factor of ten?
On large drives the number of decimals of the output current changes with the model; the high byte of 211FH tells which. Check the reading against the keypad and adjust the scale of that register if needed.
Is it safe to write drive parameters from ModbusCloud?
Each write changes the drive right away and is stored in its memory. Read the parameter first, change only what you understand, and avoid motor data and protection settings while the motor runs. Some parameters can only be changed when the drive is stopped.