Finder Finder 7E.78 / 7E.86 Modbus RTU template

Finder 7E.78 / 7E.86

Three-phase MID energy meter that measures power, energy per phase and per tariff, and grid quality.

The Finder 7E.78 and 7E.86 are MID-certified three-phase energy meters for DIN rail that measure voltage, current, power and energy per phase, directly up to 80 A or through current transformers. This Modbus RTU template reads all power values, energy counters per tariff and alarm bits, and lets you set the Modbus address and control the partial counters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
233, read and write
Brand
Finder
Key readings
Voltage per phase · Current per phase · Active power · Power factor · Frequency · Imported energy · Exported energy · Tariff counters
Available commands
Modbus address · Communication speed · Partial counter start and stop
Compatible models
7E.78.8.400.0212 · 7E.86.8.400.0212 · Finder 7E.78.8.400.0412 · Finder 7E.86.8.400.0412
Last updated

Registers (233)

230 read, 6 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Phase 1 VoltageVRead
Phase 2 VoltageVRead
Phase 3 VoltageVRead
L1-L2 VoltageVRead
L2-L3 VoltageVRead
L3-L1 VoltageVRead
System VoltageVRead
Phase 1 CurrentARead
Phase 2 CurrentARead
Phase 3 CurrentARead
Neutral CurrentARead
System CurrentARead
Phase 1 Power FactorRead
Phase 2 Power FactorRead
Phase 3 Power FactorRead
System Power FactorRead
Phase 1 Active PowerWRead
Phase 2 Active PowerWRead
Phase 3 Active PowerWRead
System Active PowerWRead
Phase 1 Apparent PowerVARead
Phase 2 Apparent PowerVARead
Phase 3 Apparent PowerVARead
System Apparent PowerVARead
Phase 1 Reactive PowervarRead
Phase 2 Reactive PowervarRead
Phase 3 Reactive PowervarRead
System Reactive PowervarRead
FrequencyHzRead
Phase SequenceRead
Phase 1 Import Active EnergyWhRead
Phase 2 Import Active EnergyWhRead
Phase 3 Import Active EnergyWhRead
System Import Active EnergyWhRead
Phase 1 Export Active EnergyWhRead
Phase 2 Export Active EnergyWhRead
Phase 3 Export Active EnergyWhRead
System Export Active EnergyWhRead
Phase 1 Import Lag Apparent EnergyVAhRead
Phase 2 Import Lag Apparent EnergyVAhRead
Phase 3 Import Lag Apparent EnergyVAhRead
System Import Lag Apparent EnergyVAhRead
Phase 1 Export Lag Apparent EnergyVAhRead
Phase 2 Export Lag Apparent EnergyVAhRead
Phase 3 Export Lag Apparent EnergyVAhRead
System Export Lag Apparent EnergyVAhRead
Phase 1 Import Lead Apparent EnergyVAhRead
Phase 2 Import Lead Apparent EnergyVAhRead
Phase 3 Import Lead Apparent EnergyVAhRead
System Import Lead Apparent EnergyVAhRead
Phase 1 Export Lead Apparent EnergyVAhRead
Phase 2 Export Lead Apparent EnergyVAhRead
Phase 3 Export Lead Apparent EnergyVAhRead
System Export Lead Apparent EnergyVAhRead
Phase 1 Import Lag Reactive EnergyvarhRead
Phase 2 Import Lag Reactive EnergyvarhRead
Phase 3 Import Lag Reactive EnergyvarhRead
System Import Lag Reactive EnergyvarhRead
Phase 1 Export Lag Reactive EnergyvarhRead
Phase 2 Export Lag Reactive EnergyvarhRead
Phase 3 Export Lag Reactive EnergyvarhRead
System Export Lag Reactive EnergyvarhRead
Phase 1 Import Lead Reactive EnergyvarhRead
Phase 2 Import Lead Reactive EnergyvarhRead
Phase 3 Import Lead Reactive EnergyvarhRead
System Import Lead Reactive EnergyvarhRead
Phase 1 Export Lead Reactive EnergyvarhRead
Phase 2 Export Lead Reactive EnergyvarhRead
Phase 3 Export Lead Reactive EnergyvarhRead
System Export Lead Reactive EnergyvarhRead
Phase 1 Import Active Energy T1WhRead
Phase 2 Import Active Energy T1WhRead
Phase 3 Import Active Energy T1WhRead
System Import Active Energy T1WhRead
Phase 1 Export Active Energy T1WhRead
Phase 2 Export Active Energy T1WhRead
Phase 3 Export Active Energy T1WhRead
System Export Active Energy T1WhRead
Phase 1 Import Lag Apparent Energy T1VAhRead
Phase 2 Import Lag Apparent Energy T1VAhRead
Phase 3 Import Lag Apparent Energy T1VAhRead
System Import Lag Apparent Energy T1VAhRead
Phase 1 Export Lag Apparent Energy T1VAhRead
Phase 2 Export Lag Apparent Energy T1VAhRead
Phase 3 Export Lag Apparent Energy T1VAhRead
System Export Lag Apparent Energy T1VAhRead
Phase 1 Import Lead Apparent Energy T1VAhRead
Phase 2 Import Lead Apparent Energy T1VAhRead
Phase 3 Import Lead Apparent Energy T1VAhRead
System Import Lead Apparent Energy T1VAhRead
Phase 1 Export Lead Apparent Energy T1VAhRead
Phase 2 Export Lead Apparent Energy T1VAhRead
Phase 3 Export Lead Apparent Energy T1VAhRead
System Export Lead Apparent Energy T1VAhRead
Phase 1 Import Lag Reactive Energy T1varhRead
Phase 2 Import Lag Reactive Energy T1varhRead
Phase 3 Import Lag Reactive Energy T1varhRead
System Import Lag Reactive Energy T1varhRead
Phase 1 Export Lag Reactive Energy T1varhRead
Phase 2 Export Lag Reactive Energy T1varhRead
Phase 3 Export Lag Reactive Energy T1varhRead
System Export Lag Reactive Energy T1varhRead
Phase 1 Import Lead Reactive Energy T1varhRead
Phase 2 Import Lead Reactive Energy T1varhRead
Phase 3 Import Lead Reactive Energy T1varhRead
System Import Lead Reactive Energy T1varhRead
Phase 1 Export Lead Reactive Energy T1varhRead
Phase 2 Export Lead Reactive Energy T1varhRead
Phase 3 Export Lead Reactive Energy T1varhRead
System Export Lead Reactive Energy T1varhRead
Phase 1 Import Active Energy T2WhRead
Phase 2 Import Active Energy T2WhRead
Phase 3 Import Active Energy T2WhRead
System Import Active Energy T2WhRead
Phase 1 Export Active Energy T2WhRead
Phase 2 Export Active Energy T2WhRead
Phase 3 Export Active Energy T2WhRead
System Export Active Energy T2WhRead
Phase 1 Import Lag Apparent Energy T2VAhRead
Phase 2 Import Lag Apparent Energy T2VAhRead
Phase 3 Import Lag Apparent Energy T2VAhRead
System Import Lag Apparent Energy T2VAhRead
Phase 1 Export Lag Apparent Energy T2VAhRead
Phase 2 Export Lag Apparent Energy T2VAhRead
Phase 3 Export Lag Apparent Energy T2VAhRead
System Export Lag Apparent Energy T2VAhRead
Phase 1 Import Lead Apparent Energy T2VAhRead
Phase 2 Import Lead Apparent Energy T2VAhRead
Phase 3 Import Lead Apparent Energy T2VAhRead
System Import Lead Apparent Energy T2VAhRead
Phase 1 Export Lead Apparent Energy T2VAhRead
Phase 2 Export Lead Apparent Energy T2VAhRead
Phase 3 Export Lead Apparent Energy T2VAhRead
System Export Lead Apparent Energy T2VAhRead
Phase 1 Import Lag Reactive Energy T2varhRead
Phase 2 Import Lag Reactive Energy T2varhRead
Phase 3 Import Lag Reactive Energy T2varhRead
System Import Lag Reactive Energy T2varhRead
Phase 1 Export Lag Reactive Energy T2varhRead
Phase 2 Export Lag Reactive Energy T2varhRead
Phase 3 Export Lag Reactive Energy T2varhRead
System Export Lag Reactive Energy T2varhRead
Phase 1 Import Lead Reactive Energy T2varhRead
Phase 2 Import Lead Reactive Energy T2varhRead
Phase 3 Import Lead Reactive Energy T2varhRead
System Import Lead Reactive Energy T2varhRead
Phase 1 Export Lead Reactive Energy T2varhRead
Phase 2 Export Lead Reactive Energy T2varhRead
Phase 3 Export Lead Reactive Energy T2varhRead
System Export Lead Reactive Energy T2varhRead
Partial Import Active EnergyWhRead
Partial Export Active EnergyWhRead
Partial Import Lag Apparent EnergyVAhRead
Partial Export Lag Apparent EnergyVAhRead
Partial Import Lead Apparent EnergyVAhRead
Partial Export Lead Apparent EnergyVAhRead
Partial Import Lag Reactive EnergyvarhRead
Partial Export Lag Reactive EnergyvarhRead
Partial Import Lead Reactive EnergyvarhRead
Partial Export Lead Reactive EnergyvarhRead
Balance Active EnergyWhRead
Balance Lag Apparent EnergyVAhRead
Balance Lead Apparent EnergyVAhRead
Balance Lag Reactive EnergyvarhRead
Balance Lead Reactive EnergyvarhRead
Phase 1 Voltage (Integer)VRead
Phase 2 Voltage (Integer)VRead
Phase 3 Voltage (Integer)VRead
L1-L2 Voltage (Integer)VRead
L2-L3 Voltage (Integer)VRead
L3-L1 Voltage (Integer)VRead
System Voltage (Integer)VRead
Phase 1 Current (Integer)ARead
Phase 2 Current (Integer)ARead
Phase 3 Current (Integer)ARead
Neutral Current (Integer)ARead
System Current (Integer)ARead
Phase 1 Power Factor (Integer)Read
Phase 2 Power Factor (Integer)Read
Phase 3 Power Factor (Integer)Read
System Power Factor (Integer)Read
Frequency (Integer)HzRead
Phase Sequence CodeRead
Counter Serial NumberRead
Counter ModelRead
Counter TypeRead
Counter Firmware Release 1Read
Counter Hardware VersionRead
Tariff In UseRead
Primary Secondary ValueRead
Error CodeRead
CT RatioRead
FSA ValueRead
Wiring ModeRead
Partial Counter StatusRead
Module Serial NumberRead
Signed Value RepresentationRead
Module Firmware ReleaseRead
Module Hardware VersionRead
RegSet In UseRead
Counter Firmware Release 2Read
Modbus AddressRead and write
Modbus ModeRead and write
Communication SpeedRead and write
Reset Energy CountersWrite
Partial Counter OperationWrite
RegSet SwitchingWrite
Frequency Out Of Range AlarmRead
System Current High AlarmRead
Phase 1 Current High AlarmRead
Phase 2 Current High AlarmRead
Phase 3 Current High AlarmRead
Neutral Current High AlarmRead
System Current Low AlarmRead
Phase 1 Current Low AlarmRead
Phase 2 Current Low AlarmRead
Phase 3 Current Low AlarmRead
Neutral Current Low AlarmRead
L1-L2 Voltage High AlarmRead
L2-L3 Voltage High AlarmRead
L3-L1 Voltage High AlarmRead
L1-L2 Voltage Low AlarmRead
L2-L3 Voltage Low AlarmRead
L3-L1 Voltage Low AlarmRead
IR Communication ErrorRead
System Voltage High AlarmRead
Phase 1 Voltage High AlarmRead
Phase 2 Voltage High AlarmRead
Phase 3 Voltage High AlarmRead
System Voltage Low AlarmRead
Phase 1 Voltage Low AlarmRead
Phase 2 Voltage Low AlarmRead
Phase 3 Voltage Low AlarmRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show power per phase and total consumption of a building or sub-distribution on a dashboard.
  • Compare day and night consumption with the tariff 1 and tariff 2 counters in the history.
  • Get an alert when a voltage or current alarm bit goes to 1, so you see a missing phase or overload early.
  • Track imported and exported energy of a PV installation with the balance counter.
  • Start a partial counter remotely to measure the consumption of one job or period.

Installation

  1. Connect the RS485 terminals of the meter to the RS485 port of the ModbusCloud Gateway, A to A and B to B, with a 120 ohm terminator at the end of the line.

  2. Check on the meter display that the Modbus mode is RTU (8N1), the speed 19200 bps and the address unique on the bus.

  3. In ModbusCloud, add a Modbus device with protocol RTU, the address of the meter, 19200 baud and 8N1, and import this template.

  4. Check that the phase voltages show around 230 V and that Counter Model matches your meter.

Things to watch for

The meter does not answer. What should I check?

Check address, 19200 baud and 8N1 on the meter display; the meter can also be set to ASCII mode (7E2), which the gateway does not use. Swap A and B if nothing comes back and terminate the line with 120 ohm.

Why do the integer current or power factor values show large numbers when they should be negative?

By default the meter codes negative integers with a sign bit instead of two's complement. Read Signed Value Representation; if it is 0, use the float values from the same table, which carry the sign correctly.

The 7E.86 shows currents that are far too low. Why?

The 7E.86 measures through current transformers. Set the CT ratio on the meter; the template reads it as CT Ratio. Primary Secondary Value shows whether the values are primary or secondary.

Can I write registers on this meter from ModbusCloud?

Yes: Modbus address, mode and speed, and partial counter commands. Writing is off per gateway by default; request it for the gateway in the portal. Change the address in ModbusCloud as well after writing it, otherwise the meter stops answering. Energy counters cannot be reset on MID meters.

Want to see how it works?

Electrician working in an open distribution board