smart-me smart-me electricity meter / Modbus TCP Template Modbus TCP template

smart-me electricity meter / Modbus TCP Template

Monitors smart-me 3-phase energy meters via Modbus TCP.

This template reads 3-phase energy data from smart-me electricity meters via Modbus TCP. It covers voltage, current, power, power factor, and active/reactive energy registers across all three phases. Compatible with the smart-me Telstar 80A, Telstar CT, and Kamstrup Module.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
30, read only
Key readings
Voltage L1 to L3 · Current L1 to L3 · Power total and per phase · Power factor L1 to L3 · Active energy import/export totals · Reactive energy Q1 to Q4
Compatible models
smart-me Telstar 3-Phase Meter (80A) · smart-me Telstar CT · smart-me Kamstrup Module
Last updated

Registers (30)

30 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Serial NumberRead
Date Time (UTC)<v.u>Read
Power Total (All Phases)mWRead
Voltage Phase L1mVRead
Current Phase L1mARead
Power Factor (cos phi) L1cosΦRead
Active Energy Import TotalWhRead
Reactive Energy Q1mVarhRead
Current Phase L2mARead
Current Phase L3mARead
Voltage Phase L2mVRead
Voltage Phase L3mVRead
Power Phase L1mWRead
Power Phase L2mWRead
Power Phase L3mWRead
Reactive Power Total (All Phases)mVarRead
Reactive Power Phase L1mVarRead
Reactive Power Phase L2mVarRead
Reactive Power Phase L3mVarRead
Power Factor (cos phi) L2cosΦRead
Power Factor (cos phi) L3cosΦRead
Reactive Energy Q2mVarhRead
Reactive Energy Q3mVarhRead
Reactive Energy Q4mVarhRead
Active Energy Import T1WhRead
Active Energy Import T2WhRead
Active TariffRead
Active Energy Export T1WhRead
Active Energy Export T2WhRead
Active Energy Export TotalWhRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time voltage, current, and power per phase on a live cloud dashboard for your customer.
  • Track active energy import and export totals to verify self-consumption of a PV installation.
  • Create an alert when power factor on any phase drops below a defined threshold for more than five minutes.
  • Compare T1 and T2 tariff consumption over time to optimize energy cost strategies.
  • Generate monthly energy reports showing total consumption and grid feed-in for billing verification.
  • Detect phase imbalance by comparing per-phase power readings on a single dashboard.

Installation

  1. Connect the smart-me meter to the local network via Ethernet or Wi-Fi and confirm that Modbus TCP is enabled in the smart-me device settings.

  2. Note the IP address assigned to the smart-me meter and verify connectivity by pinging it from a device on the same network.

  3. Connect your ModbusCloud Gateway to the same local network as the smart-me meter.

  4. Import the smart-me electricity meter Modbus TCP template into your ModbusCloud project and enter the meter IP address and Modbus TCP port (default 502).

  5. Apply scaling factors in ModbusCloud to convert milliwatts, millivolts, milliamps, and millivar-hours to standard units (divide raw values by 1000).

  6. Verify that live readings appear on the ModbusCloud dashboard and match the values shown on the meter display or smart-me cloud portal.

Things to watch for

Why do the readings in ModbusCloud show very large numbers instead of normal values?

smart-me meters report values in milli-units. Voltages are in millivolts, currents in milliamps, and power in milliwatts. Apply a scaling factor of 0.001 (divide by 1000) in ModbusCloud to convert to volts, amps, and watts.

Which Modbus TCP port does the smart-me meter use?

The default Modbus TCP port is 502. Ensure this port is not blocked by any firewall rules on your local network.

Do I need to set a Modbus slave address for the smart-me meter?

Modbus TCP typically uses unit ID 1 by default. Check the smart-me device configuration or the official Modbus TCP wiki if your setup uses a different unit ID.

Can I use this template for single-phase smart-me meters?

This template is designed for 3-phase smart-me models (Telstar 80A, Telstar CT, Kamstrup Module). Single-phase meters may use a different register map and are not guaranteed to work with this template without modifications.

Want to see how it works?

Electrician working in an open distribution board