smart-me Pico smart-me EV Charger - Modbus Template Modbus TCP template

Pico smart-me EV Charger - Modbus Template

Monitors and controls smart-me Pico EV charger via Modbus TCP

Template for the smart-me Pico EV charger via Modbus TCP. Reads energy metering data including voltage, current, power, and charging status per phase. Supports writing a dynamic maximum charging current setpoint for load management.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
34, read and write
Key readings
Voltage L1 to L3 · Current L1 to L3 · Power total and per phase · Active energy import total · Car connected and charging status · Loadmanagement group max current
Available commands
Dynamic max current (station or group)
Compatible models
Pico · smart-me Pico
Last updated

Registers (34)

33 read, 1 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Serial NumberRead
Date Time (UTC)<v.u>Read
Power Total (All Phases)mWRead
Is Car connectedRead
Is charging activeRead
Voltage Phase L1mVRead
Current Phase L1mARead
Power Factor (cos phi) L1cosΦRead
Active Energy Import TotalWhRead
Reactive Energy Q1VarhRead
Energy used in active chargingmWhRead
Min. station charging currentmARead
Max. station charging currentmARead
Current Phase L2mARead
Current Phase L3mARead
Voltage Phase L2mVRead
Voltage Phase L3mVRead
Power Phase L1mWRead
Power Phase L2mWRead
Power Phase L3mWRead
Reactive Power Total (All Phases)mVarRead
Reactive Power Phase L1mVarRead
Reactive Power Phase L2mVarRead
Reactive Power Phase L3mVarRead
Power Factor (cos phi) L2cosΦRead
Power Factor (cos phi) L3cosΦRead
Reactive Energy Q2VarhRead
Reactive Energy Q3VarhRead
Reactive Energy Q4VarhRead
Is in Loadmanagent GroupRead
Loadmanagement group max. currentmARead
Active Energy Import T1WhRead
Active Energy Import T2WhRead
Dynamic max. current (single station or loadmanagment group)mAWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time voltage, current, and power per phase on a live dashboard for each smart-me Pico charger.
  • Create an alert when a car is connected but not charging to detect potential faults or authorization issues.
  • Log active energy import per tariff period for accurate billing and cost allocation to tenants.
  • Write a dynamic maximum charging current to implement load management across multiple charging stations.
  • Track charging session status remotely to verify uptime and utilization of installed EV chargers.
  • Compare per-phase power distribution to detect load imbalance across the three phases.

Installation

  1. Connect the ModbusCloud Gateway to the same local network as the smart-me Pico charger.

  2. Enable Modbus TCP on the smart-me Pico via its web interface or configuration tool, and note the IP address and Modbus port.

  3. Set a unique Modbus unit ID on the charger if multiple devices share the same network segment.

  4. Import the smart-me Pico EV Charger template in the ModbusCloud portal and assign it to the gateway.

  5. Enter the charger IP address, port, and unit ID in the template connection settings and verify that live data appears on the dashboard.

  6. Confirm that register scaling is correct by comparing dashboard values with the charger display or a reference meter.

Things to watch for

Why do my readings show very large numbers instead of realistic values?

Register values from the smart-me Pico are in mW, mV, mA, and mWh. Make sure the template scaling factors are applied. If you customized registers, divide by 1000 where needed to convert to standard units.

Why does active energy during charging show zero or incorrect values?

Active charging energy is stored as a uint64 value across four consecutive registers. Ensure your register configuration reads all four registers and interprets them as an unsigned 64-bit integer.

I cannot connect to the charger via Modbus TCP. What should I check?

Verify that Modbus TCP is enabled in the Pico settings. Check that the gateway and the charger are on the same subnet and that no firewall rules block the configured TCP port. Confirm the correct IP address and unit ID.

Can I control the maximum charging current for a group of chargers?

Yes. The template includes a writable register for load management group max current. Writing to this register limits the combined current for all chargers in the same group as configured on the smart-me side.

Want to see how it works?

Electrician working in an open distribution board