Mitsubishi Electric FR-A800

Frequency inverter that controls motor speed and torque in pumps, fans, conveyors and machines.

The Mitsubishi Electric FR-A800 is a frequency inverter that controls the speed and torque of motors in pumps, fans, conveyors and machines. This Modbus RTU template reads frequency, current, voltage, power, energy, temperatures and the fault history, and lets you write run commands, the frequency setpoint and every drive parameter from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
1067, read and write
Key readings
Output frequency · Output current · Output voltage · Input power · Cumulative energy · Heat sink temperature · Motor thermal load · Fault history
Available commands
Run and direction command · Frequency setpoint · Operation mode · PID set point · Acceleration and deceleration time · Inverter reset
Compatible models
FR-A820 · FR-A840 · FR-A842 · FR-A846 · FR-A800-GF
Last updated

Registers (1067)

1061 read, 956 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Output FrequencyHzRead200FC03uint16
Output CurrentARead201FC03uint16
Output VoltageVRead202FC03uint16
Control Input Command / Inverter StatusRead and write8FC03 / FC06uint16
Operation ModeRead and write9FC03 / FC06uint16
Set Frequency RAMHzRead and write
Set Frequency EEPROMHzWrite
Set FrequencyHzRead
Operation SpeedrpmRead
Motor Torque%Read
Converter Output VoltageVRead
Regenerative Brake Duty%Read
Electronic Thermal O/L Relay Load Factor%Read
Output Current Peak ValueARead
Converter Output Voltage Peak ValueVRead
Input PowerkWRead
Output PowerkWRead
Load Meter%Read
Motor Excitation CurrentARead
Position PulseRead
Cumulative Energization TimehRead
Orientation StatusRead
Actual Operation TimehRead
Motor Load Factor%Read
Cumulative EnergykWhRead
Position Command Lower DigitsRead
Position Command Upper DigitsRead
Current Position Lower DigitsRead
Current Position Upper DigitsRead
Droop Pulse Lower DigitsRead
Droop Pulse Upper DigitsRead
Torque Command%Read
Torque Current Command%Read
Motor OutputkWRead
Feedback PulseRead
Torque%Read
Heat Sink Temperature°CRead
Trace StatusRead
SSCNET III Communication StatusRead
PLC Function User Monitor 1Read
PLC Function User Monitor 2Read
PLC Function User Monitor 3Read
Station Number RS-485 TerminalsRead
Station Number PURead
Station Number CC-LinkRead
Motor Temperature°CRead
Energy Saving EffectRead
Cumulative Saved EnergyRead
PID Set Point%Read
PID Measured Value%Read
PID Deviation%Read
Option Input Terminal Status 1Read
Option Input Terminal Status 2Read
Option Output Terminal StatusRead
Motor Thermal Load Factor%Read
Inverter Thermal Load Factor%Read
PTC Thermistor ResistancekΩRead
PID Measured Value 2%Read
Emergency Drive StatusRead
Cumulative PulseRead
Cumulative Pulse Overflow TimesRead
Cumulative Pulse Control Terminal OptionRead
Cumulative Pulse Overflow Times Control Terminal OptionRead
Multi-Revolution CounterRead
Remote Output Value 1%Read
Remote Output Value 2%Read
Remote Output Value 3%Read
Remote Output Value 4%Read
PID Manipulated Amount%Read
Second PID Set Point%Read
Second PID Measured Value%Read
Second PID Deviation%Read
Second PID Measured Value 2%Read
Second PID Manipulated Amount%Read
Dancer Main Set SpeedHzRead
Control Circuit Temperature°CRead
Input Terminal StatusRead
Output Terminal StatusRead
32-Bit Cumulative Energy kWhkWhRead
32-Bit Cumulative EnergykWhRead
Fault Record 1Read and write
Fault Record 2Read
Fault Record 3Read
Fault Record 4Read
Fault Record 5Read
Fault Record 6Read
Fault Record 7Read
Fault Record 8Read
Inverter ResetWrite
Parameter ClearWrite
All Parameter ClearWrite
Parameter Clear Except CommunicationWrite
All Parameter Clear Except CommunicationWrite
Torque Boost%Read and write
Maximum FrequencyHzRead and write
Minimum FrequencyHzRead and write
Base FrequencyHzRead and write
Multi-Speed Setting (High Speed)HzRead and write
Multi-Speed Setting (Middle Speed)HzRead and write
Multi-Speed Setting (Low Speed)HzRead and write
Acceleration TimesRead and write
Deceleration TimesRead and write
Electronic Thermal O/L Relay (Rated Motor Current)ARead and write
DC Injection Brake Operation FrequencyHzRead and write
DC Injection Brake Operation TimesRead and write
DC Injection Brake Operation Voltage%Read and write
Starting FrequencyHzRead and write
Load Pattern SelectionRead and write
Jog FrequencyHzRead and write
Jog Acceleration/Deceleration TimesRead and write
MRS Input SelectionRead and write
High Speed Maximum FrequencyHzRead and write
Base Frequency VoltageVRead and write
Acceleration/Deceleration Reference FrequencyHzRead and write
Acceleration/Deceleration Time IncrementsRead and write
Stall Prevention Operation Level (Torque Limit Level)%Read and write
Stall Prevention Level Compensation Factor at Double Speed%Read and write
Multi-Speed Setting (Speed 4)HzRead and write
Multi-Speed Setting (Speed 5)HzRead and write
Multi-Speed Setting (Speed 6)HzRead and write
Multi-Speed Setting (Speed 7)HzRead and write
Multi-Speed Input Compensation SelectionRead and write
Acceleration/Deceleration Pattern SelectionRead and write
Regenerative Function SelectionRead and write
Frequency Jump 1AHzRead and write
Frequency Jump 1BHzRead and write
Frequency Jump 2AHzRead and write
Frequency Jump 2BHzRead and write
Frequency Jump 3AHzRead and write
Frequency Jump 3BHzRead and write
Speed DisplayRead and write
Up-To-Frequency Sensitivity%Read and write
Output Frequency DetectionHzRead and write
Output Frequency Detection for Reverse RotationHzRead and write
Second Acceleration/Deceleration TimesRead and write
Second Deceleration TimesRead and write
Second Torque Boost%Read and write
Second V/F (Base Frequency)HzRead and write
Second Stall Prevention Operation Level%Read and write
Second Stall Prevention Operation FrequencyHzRead and write
Second Output Frequency DetectionHzRead and write
Second Electronic Thermal O/L RelayARead and write
Operation Panel Main Monitor SelectionRead and write
FM/CA Terminal Function SelectionRead and write
Frequency Monitoring ReferenceHzRead and write
Current Monitoring ReferenceARead and write
Restart Coasting TimesRead and write
Restart Cushion TimesRead and write
Remote Function SelectionRead and write
Energy Saving Control SelectionRead and write
Reference CurrentARead and write
Reference Value at Acceleration%Read and write
Reference Value at Deceleration%Read and write
Starting Frequency for Elevator ModeHzRead and write
Retry SelectionRead and write
Stall Prevention Operation Reduction Starting FrequencyHzRead and write
Number of Retries at Fault OccurrenceRead and write
Retry Waiting TimesRead and write
Retry Count Display EraseRead and write
Special Regenerative Brake Duty%Read and write
Applied MotorRead and write
PWM Frequency SelectionRead and write
Analog Input SelectionRead and write
Input Filter Time ConstantRead and write
Reset Selection / Disconnected PU Detection / PU StopRead and write
Fault Code Output SelectionRead and write
Parameter Write SelectionRead and write
Reverse Rotation Prevention SelectionRead and write
Operation Mode SelectionRead and write
Motor CapacitykWRead and write
Number of Motor PolesRead and write
Motor Excitation Current (Pr.82)ARead and write
Rated Motor VoltageVRead and write
Rated Motor FrequencyHzRead and write
Excitation Current Break PointHzRead and write
Excitation Current Low-Speed Scaling Factor%Read and write
Speed Control Gain (Advanced Magnetic Flux Vector)%Read and write
Motor Constant (R1)ΩRead and write
Motor Constant (R2)ΩRead and write
Motor Constant (L1)/D-Axis Inductance (Ld)Read and write
Motor Constant (L2)/Q-Axis Inductance (Lq)Read and write
Motor Constant (X)%Read and write
Online Auto Tuning SelectionRead and write
Auto Tuning Setting/StatusRead and write
V/F1 (First Frequency)HzRead and write
V/F1 (First Frequency Voltage)VRead and write
V/F2 (Second Frequency)HzRead and write
V/F2 (Second Frequency Voltage)VRead and write
V/F3 (Third Frequency)HzRead and write
V/F3 (Third Frequency Voltage)VRead and write
V/F4 (Fourth Frequency)HzRead and write
V/F4 (Fourth Frequency Voltage)VRead and write
V/F5 (Fifth Frequency)HzRead and write
V/F5 (Fifth Frequency Voltage)VRead and write
Third Acceleration/Deceleration TimesRead and write
Third Deceleration TimesRead and write
Third Torque Boost%Read and write
Third V/F (Base Frequency)HzRead and write
Third Stall Prevention Operation Level%Read and write
Third Stall Prevention Operation FrequencyHzRead and write
Third Output Frequency DetectionHzRead and write
PU Communication Station NumberRead and write
PU Communication SpeedRead and write
PU Communication Stop Bit Length / Data LengthRead and write
PU Communication Parity CheckRead and write
PU Communication Retry CountRead and write
PU Communication Check Time IntervalsRead and write
PU Communication Waiting Time SettingmsRead and write
PU Communication CR/LF SelectionRead and write
Terminal 2 Frequency Setting Gain FrequencyHzRead and write
Terminal 4 Frequency Setting Gain FrequencyHzRead and write
PID Control Automatic Switchover FrequencyHzRead and write
PID Action SelectionRead and write
PID Proportional Band%Read and write
PID Integral TimesRead and write
PID Upper Limit%Read and write
PID Lower Limit%Read and write
PID Action Set Point%Read and write
PID Differential TimesRead and write
Electronic Bypass Sequence SelectionRead and write
MC Switchover Interlock TimesRead and write
Start Waiting TimesRead and write
Bypass Selection at a FaultRead and write
Automatic Switchover Frequency Inverter to BypassHzRead and write
Backlash Acceleration Stopping FrequencyHzRead and write
Backlash Acceleration Stopping TimesRead and write
Backlash Deceleration Stopping FrequencyHzRead and write
Backlash Deceleration Stopping TimesRead and write
Speed Setting SwitchoverRead and write
PU Display Language SelectionRead and write
Acceleration/Deceleration Time Switching FrequencyHzRead and write
Stall Prevention Level at 0 V Input%Read and write
Stall Prevention Level at 10 V Input%Read and write
Output Current Detection Level%Read and write
Output Current Detection Signal Delay TimesRead and write
Zero Current Detection Level%Read and write
Zero Current Detection TimesRead and write
Voltage Reduction Selection during Stall Prevention OperationRead and write
RT Signal Function Validity Condition SelectionRead and write
Stall Prevention Operation SelectionRead and write
OL Signal Output TimersRead and write
AM Terminal Function SelectionRead and write
Automatic Switchover Frequency Range Bypass to InverterHzRead and write
User Group Read SelectionRead and write
Frequency Setting/Key Lock Operation SelectionRead and write
Automatic Restart after Instantaneous Power Failure SelectionRead and write
First Cushion Time for RestartsRead and write
First Cushion Voltage for Restart%Read and write
Stall Prevention Operation Level for Restart%Read and write
Output Current Detection Signal Retention TimesRead and write
Output Current Detection Operation SelectionRead and write
Watt-Hour Meter ClearRead and write
Operation Hour Meter ClearRead and write
User Group Registered Display/Batch ClearRead and write
User Group RegistrationRead and write
User Group ClearRead and write
STF Terminal Function SelectionRead and write
STR Terminal Function SelectionRead and write
RL Terminal Function SelectionRead and write
RM Terminal Function SelectionRead and write
RH Terminal Function SelectionRead and write
RT Terminal Function SelectionRead and write
AU Terminal Function SelectionRead and write
JOG Terminal Function SelectionRead and write
CS Terminal Function SelectionRead and write
MRS Terminal Function SelectionRead and write
STOP Terminal Function SelectionRead and write
RES Terminal Function SelectionRead and write
RUN Terminal Function SelectionRead and write
SU Terminal Function SelectionRead and write
IPF Terminal Function SelectionRead and write
OL Terminal Function SelectionRead and write
FU Terminal Function SelectionRead and write
ABC1 Terminal Function SelectionRead and write
ABC2 Terminal Function SelectionRead and write
Excitation Current Compensation Point 1%Read and write
Inductance Compensation Rate 1%Read and write
Excitation Current Compensation Point 2%Read and write
Inductance Compensation Rate 2%Read and write
Excitation Current Compensation Point 3%Read and write
Inductance Compensation Rate 3%Read and write
Excitation Current Compensation Point 4%Read and write
Inductance Compensation Rate 4%Read and write
Multi-Speed Setting (Speed 8)HzRead and write
Multi-Speed Setting (Speed 9)HzRead and write
Multi-Speed Setting (Speed 10)HzRead and write
Multi-Speed Setting (Speed 11)HzRead and write
Multi-Speed Setting (Speed 12)HzRead and write
Multi-Speed Setting (Speed 13)HzRead and write
Multi-Speed Setting (Speed 14)HzRead and write
Multi-Speed Setting (Speed 15)HzRead and write
Soft-PWM Operation SelectionRead and write
Analog Input Display Unit SwitchoverRead and write
Terminal 1 Added Compensation Amount (Terminal 2)%Read and write
Terminal 1 Added Compensation Amount (Terminal 4)%Read and write
Cooling Fan Operation SelectionRead and write
Rated Slip%Read and write
Slip Compensation Time ConstantsRead and write
Constant Output Range Slip Compensation SelectionRead and write
Self Power Management SelectionRead and write
Earth (Ground) Fault Detection at StartRead and write
Stop SelectionsRead and write
Output Phase Loss Protection SelectionRead and write
Override Bias%Read and write
Override Gain%Read and write
Main Circuit Power OFF Waiting TimesRead and write
Life Alarm Status DisplayRead
Inrush Current Limit Circuit Life Display%Read
Control Circuit Capacitor Life Display%Read
Main Circuit Capacitor Life Display%Read
Main Circuit Capacitor Life MeasuringRead and write
PWM Frequency Automatic SwitchoverRead and write
Power Failure Stop SelectionRead and write
Subtracted Frequency at Deceleration StartHzRead and write
Subtraction Starting FrequencyHzRead and write
Power-Failure Deceleration Time 1sRead and write
Power-Failure Deceleration Time 2sRead and write
Power Failure Deceleration Time Switchover FrequencyHzRead and write
Terminal 4 Input SelectionRead and write
Monitor Decimal Digits SelectionRead and write
Stop-On Contact/Load Torque High-Speed Control SelectionRead and write
High-Speed Setting Maximum Current%Read and write
Middle-Speed Setting Minimum Current%Read and write
Current Averaging RangeHzRead and write
Current Averaging Filter Time ConstantRead and write
Stop-On Contact Excitation Current Low-Speed Scaling Factor%Read and write
PWM Carrier Frequency at Stop-On ContactRead and write
Brake Opening FrequencyHzRead and write
Brake Opening Current%Read and write
Brake Opening Current Detection TimesRead and write
Brake Operation Time at StartsRead and write
Brake Operation FrequencyHzRead and write
Brake Operation Time at StopsRead and write
Deceleration Detection Function SelectionRead and write
Overspeed Detection FrequencyHzRead and write
Droop Gain%Read and write
Droop Filter Time ConstantsRead and write
Droop Function Activation SelectionRead and write
Inverter Output Terminal FiltermsRead and write
Monitor Negative Output SelectionRead and write
Pulse Train I/O SelectionRead and write
Automatic Acceleration/DecelerationRead and write
Acceleration/Deceleration Separate SelectionRead and write
UV Avoidance Voltage Gain%Read and write
Frequency Change Increment Amount SettingRead and write
Password Lock LevelRead and write
Password Lock/UnlockRead and write
Frequency Search GainRead and write
Rotation Direction Detection Selection at RestartingRead and write
DO0 Output SelectionRead and write
DO1 Output SelectionRead and write
DO2 Output SelectionRead and write
DO3 Output SelectionRead and write
DO4 Output SelectionRead and write
DO5 Output SelectionRead and write
DO6 Output SelectionRead and write
RA1 Output SelectionRead and write
RA2 Output SelectionRead and write
RA3 Output SelectionRead and write
Inverter/Converter SwitchingRead and write
RS-485 Communication Station NumberRead and write
RS-485 Communication SpeedRead and write
RS-485 Communication Stop Bit Length / Data LengthRead and write
RS-485 Communication Parity Check SelectionRead and write
RS-485 Communication Retry CountRead and write
RS-485 Communication Check Time IntervalsRead and write
RS-485 Communication Waiting Time SettingmsRead and write
Communication Operation Command SourceRead and write
Communication Speed Command SourceRead and write
Communication Startup Mode SelectionRead and write
RS-485 Communication CR/LF SelectionRead and write
Communication EEPROM Write SelectionRead and write
Communication Error CountRead
Communication Reset SelectionRead and write
Stop Position Command SelectionRead and write
Orientation SpeedHzRead and write
Creep SpeedHzRead and write
Creep Switchover PositionRead and write
Position Loop Switchover PositionRead and write
DC Injection Brake Start PositionRead and write
Internal Stop Position CommandRead and write
Orientation In-Position ZoneRead and write
Servo Torque SelectionRead and write
Encoder Rotation DirectionRead and write
16-Bit Data SelectionRead and write
Position ShiftRead and write
Orientation Position Loop GainRead and write
Completion Signal Output Delay TimesRead and write
Encoder Stop Check TimesRead and write
Orientation LimitsRead and write
Recheck TimesRead and write
Speed Feedback RangeHzRead and write
Feedback GainRead and write
Number of Encoder PulsesRead and write
Encoder Position Tuning Setting/StatusRead and write
Overspeed Detection LevelHzRead and write
Encoder Signal Loss Detection Enable/Disable SelectionRead and write
Acceleration S-Pattern 1%Read and write
Deceleration S-Pattern 1%Read and write
Acceleration S-Pattern 2%Read and write
Deceleration S-Pattern 2%Read and write
Input Pulse Division Scaling FactorRead and write
Frequency for Zero Input PulseHzRead and write
Frequency for Maximum Input PulseHzRead and write
Orientation SelectionRead and write
Number of Machine Side Gear TeethRead and write
Number of Motor Side Gear TeethRead and write
Orientation Speed Gain (P Term)Read and write
Orientation Speed Integral TimesRead and write
Orientation Speed Gain (D Term)Read and write
Orientation Deceleration RatioRead and write
Encoder Pulse Division RatioRead and write
PLC Function Operation SelectionRead and write
Inverter Operation Lock Mode SettingRead and write
Pre-Scale Function SelectionRead and write
Pre-Scale Setting ValueRead and write
Position Command Source SelectionRead and write
Command Pulse Scaling Factor NumeratorRead and write
Command Pulse Multiplication DenominatorRead and write
Position Control GainRead and write
Position Feed Forward Gain%Read and write
Position Command Acceleration/Deceleration Time ConstantsRead and write
Position Feed Forward Command FiltersRead and write
In-Position WidthRead and write
Excessive Level ErrorRead and write
Command Pulse SelectionRead and write
Clear Signal SelectionRead and write
Pulse Monitor SelectionRead and write
Pulse Train Torque Command Bias%Read and write
Pulse Train Torque Command Gain%Read and write
Network Number (CC-Link IE)Read and write
Station Number (CC-Link IE)Read and write
Model Position Control GainRead and write
Second Applied MotorRead and write
Second Motor Control Method SelectionRead and write
Second Motor CapacitykWRead and write
Number of Second Motor PolesRead and write
Second Motor Excitation CurrentARead and write
Rated Second Motor VoltageVRead and write
Rated Second Motor FrequencyHzRead and write
Second Motor Constant (R1)ΩRead and write
Second Motor Constant (R2)ΩRead and write
Second Motor Constant (L1)/D-Axis Inductance (Ld)Read and write
Second Motor Constant (L2)/Q-Axis Inductance (Lq)Read and write
Second Motor Constant (X)%Read and write
Second Motor Auto Tuning Setting/StatusRead and write
Digital Position Control Sudden Stop Deceleration TimesRead and write
First Target Position Lower 4 DigitsRead and write
First Target Position Upper 4 DigitsRead and write
Second Target Position Lower 4 DigitsRead and write
Second Target Position Upper 4 DigitsRead and write
Third Target Position Lower 4 DigitsRead and write
Third Target Position Upper 4 DigitsRead and write
Fourth Target Position Lower 4 DigitsRead and write
Fourth Target Position Upper 4 DigitsRead and write
Fifth Target Position Lower 4 DigitsRead and write
Fifth Target Position Upper 4 DigitsRead and write
Sixth Target Position Lower 4 DigitsRead and write
Sixth Target Position Upper 4 DigitsRead and write
Seventh Target Position Lower 4 DigitsRead and write
Seventh Target Position Upper 4 DigitsRead and write
Eighth Target Position Lower 4 DigitsRead and write
Eighth Target Position Upper 4 DigitsRead and write
Ninth Target Position Lower 4 DigitsRead and write
Ninth Target Position Upper 4 DigitsRead and write
Tenth Target Position Lower 4 DigitsRead and write
Tenth Target Position Upper 4 DigitsRead and write
Eleventh Target Position Lower 4 DigitsRead and write
Eleventh Target Position Upper 4 DigitsRead and write
Twelfth Target Position Lower 4 DigitsRead and write
Twelfth Target Position Upper 4 DigitsRead and write
Thirteenth Target Position Lower 4 DigitsRead and write
Thirteenth Target Position Upper 4 DigitsRead and write
Fourteenth Target Position Lower 4 DigitsRead and write
Fourteenth Target Position Upper 4 DigitsRead and write
Fifteenth Target Position Lower 4 DigitsRead and write
Fifteenth Target Position Upper 4 DigitsRead and write
Remote Output SelectionRead and write
Remote Output Data 1Read and write
Remote Output Data 2Read and write
PLC Function Flash Memory ClearRead and write
Communication Error Execution Waiting TimesRead and write
Communication Error Occurrence Count DisplayRead and write
Stop Mode Selection at Communication ErrorRead and write
Maintenance Timer 1Read and write
Maintenance Timer 1 Warning Output Set TimeRead and write
Speed Setting ReferenceHzRead and write
Display Estimated Main Circuit Capacitor Residual Life%Read
Display/Reset ABC1 Relay Contact Life%Read and write
Display/Reset ABC2 Relay Contact Life%Read and write
Emergency Drive Dedicated Retry Waiting TimesRead and write
Emergency Drive Dedicated Retry CountRead and write
S-Pattern Time at a Start of AccelerationsRead and write
S-Pattern Time at a Completion of AccelerationsRead and write
S-Pattern Time at a Start of DecelerationsRead and write
S-Pattern Time at a Completion of DecelerationsRead and write
Output Short-Circuit DetectionRead and write
Output Stop FrequencyHzRead and write
Emergency Drive Mode SelectionRead and write
Emergency Drive Running SpeedHzRead and write
MODBUS RTU Communication Check Time IntervalsRead and write
Frequency Command Sign SelectionRead and write
USB Communication Station NumberRead and write
USB Communication Check Time IntervalsRead and write
Protocol SelectionRead and write
NET Mode Operation Command Source SelectionRead and write
PU Mode Operation Command Source SelectionRead and write
Frequency Jump RangeHzRead and write
PID Deviation Limit%Read and write
PID Signal Operation SelectionRead and write
Current Average TimesRead and write
Data Output Mask TimesRead and write
Current Average Value Monitor Output Reference CurrentARead and write
Second Frequency Search GainRead and write
PTC Thermistor Protection LevelkΩRead and write
Energization Time Carrying-Over TimesRead
Operating Time Carrying-Over TimesRead
Second Motor Excitation Current Break PointHzRead and write
Second Motor Excitation Current Low-Speed Scaling Factor%Read and write
Second Motor Speed Control Gain%Read and write
Multiple Rating SettingRead and write
Holding Time at a StartsRead and write
4 mA Input Check SelectionRead and write
Second Motor Online Auto TuningRead and write
Output Interruption Detection TimesRead and write
Output Interruption Detection LevelHzRead and write
Output Interruption Cancel Level%Read and write
Traverse Function SelectionRead and write
Maximum Amplitude Amount%Read and write
Amplitude Compensation Amount during Deceleration%Read and write
Amplitude Compensation Amount during Acceleration%Read and write
Amplitude Acceleration TimesRead and write
Amplitude Deceleration TimesRead and write
Undervoltage LevelVRead and write
X10 Terminal Input SelectionRead and write
First Free Thermal Reduction Frequency 1HzRead and write
First Free Thermal Reduction Ratio 1%Read and write
First Free Thermal Reduction Frequency 2HzRead and write
First Free Thermal Reduction Ratio 2%Read and write
First Free Thermal Reduction Frequency 3HzRead and write
Power Failure Stop External Signal Input SelectionRead and write
Motor Permissible Load Level%Read and write
Second Motor Permissible Load Level%Read and write
PID Set Point/Deviation Input SelectionRead and write
PID Measured Value Input SelectionRead and write
Acceleration Time at a RestartsRead and write
Reverse Rotation Excitation Current Low-Speed Scaling Factor%Read and write
Cumulative Pulse Clear Signal SelectionRead and write
Cumulative Pulse Division Scaling FactorRead and write
Control Terminal Option Cumulative Pulse Division Scaling FactorRead and write
Cumulative Pulse StorageRead and write
Brake Opening Current SelectionRead and write
Brake Operation Frequency SelectionRead and write
Second Brake Sequence Operation SelectionRead and write
Second Brake Opening FrequencyHzRead and write
Second Brake Opening Current%Read and write
Second Brake Opening Current Detection TimesRead and write
Second Brake Operation Time at StartsRead and write
Second Brake Operation FrequencyHzRead and write
Second Brake Operation Time at StopsRead and write
Second Deceleration Detection Function SelectionRead and write
Second Brake Opening Current SelectionRead and write
Second Brake Operation Frequency SelectionRead and write
Speed Smoothing Control%Read and write
Speed Smoothing Cutoff FrequencyHzRead and write
Analog Remote Output SelectionRead and write
Analog Remote Output 1%Read and write
Analog Remote Output 2%Read and write
Analog Remote Output 3%Read and write
Analog Remote Output 4%Read and write
Increased Magnetic Excitation Deceleration Operation SelectionRead and write
Magnetic Excitation Increase Rate%Read and write
Increased Magnetic Excitation Current Level%Read and write
Control Circuit Temperature Signal Output Level°CRead and write
Regeneration Avoidance Frequency Gain%Read and write
Power Failure Stop Frequency Gain%Read and write
SF-PR Slip Amount Adjustment Operation SelectionRead and write
SF-PR Slip Amount Adjustment Gain%Read and write
User Parameter Auto Storage Function SelectionRead and write
Second Droop Gain%Read and write
Second Droop Filter Time ConstantsRead and write
Second Droop Function Activation SelectionRead and write
Second Droop Break Point Gain%Read and write
Second Droop Break Point Torque%Read and write
Tuning Data Unit SwitchoverRead and write
Maintenance Timer 2Read and write
Maintenance Timer 2 Warning Output Set TimeRead and write
Maintenance Timer 3Read and write
Maintenance Timer 3 Warning Output Set TimeRead and write
Deceleration Check TimesRead and write
Second Free Thermal Reduction Frequency 1HzRead and write
Second Free Thermal Reduction Ratio 1%Read and write
Second Free Thermal Reduction Frequency 2HzRead and write
Second Free Thermal Reduction Ratio 2%Read and write
Second Free Thermal Reduction Frequency 3HzRead and write
Input Terminal FiltermsRead and write
Maximum Motor FrequencyHzRead and write
Induced Voltage Constant (Phi F)mVRead and write
Motor Inertia (Integer)Read and write
Motor Ld Decay Ratio%Read and write
Motor Lq Decay Ratio%Read and write
Starting Resistance Tuning Compensation%Read and write
Starting Magnetic Pole Position Detection Pulse WidthRead and write
Motor Inertia (Exponent)Read and write
Motor Protection Current Level%Read and write
Second Motor Induced Voltage Constant (Phi F)mVRead and write
Second Motor Ld Decay Ratio%Read and write
Second Motor Lq Decay Ratio%Read and write
Second Starting Resistance Tuning Compensation%Read and write
Second Motor Magnetic Pole Detection Pulse WidthRead and write
Second Motor Maximum FrequencyHzRead and write
Second Motor Inertia (Integer)Read and write
Second Motor Inertia (Exponent)Read and write
Second Motor Protection Current Level%Read and write
Second Motor Low-Speed Range Torque Characteristic SelectionRead and write
Second PID Action SelectionRead and write
Second PID Control Automatic Switchover FrequencyHzRead and write
Second PID Action Set Point%Read and write
Second PID Proportional Band%Read and write
Second PID Integral TimesRead and write
Second PID Differential TimesRead and write
PID Unit SelectionRead and write
Pre-Charge Fault SelectionRead and write
Pre-Charge Ending Level%Read and write
Pre-Charge Ending TimesRead and write
Pre-Charge Upper Detection Level%Read and write
Pre-Charge Time LimitsRead and write
Second Pre-Charge Fault SelectionRead and write
Second Pre-Charge Ending Level%Read and write
Second Pre-Charge Ending TimesRead and write
Second Pre-Charge Upper Detection Level%Read and write
Second Pre-Charge Time LimitsRead and write
Operation Panel Monitor Selection 1Read and write
Operation Panel Monitor Selection 2Read and write
Operation Panel Monitor Selection 3Read and write
4 mA Input Fault Operation FrequencyHzRead and write
4 mA Input Check FiltersRead and write
Operation Frequency during Communication ErrorHzRead and write
Low Speed Range Torque Characteristic SelectionRead and write
Acceleration Time in Low-Speed RangesRead and write
Deceleration Time in Low-Speed RangesRead and write
Pulse Increment Setting for Output PowerkWhRead and write
Control Method SelectionRead and write
Output Limit Level%Read and write
Pre-Excitation SelectionRead and write
Constant Output Range Torque Characteristic SelectionRead and write
Torque Command Source SelectionRead and write
Torque Command Value (RAM)%Read and write
Torque Command Value (RAM, EEPROM)%Read and write
Speed Limit SelectionRead and write
Forward Rotation Speed Limit/Speed LimitHzRead and write
Reverse Rotation Speed Limit/Reverse-Side Speed LimitHzRead and write
Torque Limit Input Method SelectionRead and write
Set Resolution SwitchoverRead and write
Torque Limit Level (Regeneration)%Read and write
Torque Limit Level (3rd Quadrant)%Read and write
Torque Limit Level (4th Quadrant)%Read and write
Torque Limit Level 2%Read and write
Torque Limit Level during Acceleration%Read and write
Torque Limit Level during Deceleration%Read and write
Easy Gain Tuning Response Level SettingRead and write
Easy Gain Tuning SelectionRead and write
Speed Control P Gain 1%Read and write
Speed Control Integral Time 1sRead and write
Speed Setting Filter 1sRead and write
Speed Detection Filter 1sRead and write
Torque Control P Gain 1 (Current Loop Proportional Gain)%Read and write
Torque Control Integral Time 1 (Current Loop Integral Time)msRead and write
Torque Setting Filter 1sRead and write
Torque Detection Filter 1sRead and write
Model Speed Control Gain%Read and write
Number of Machine End Encoder PulsesRead and write
Speed Control P Gain 2%Read and write
Speed Control Integral Time 2sRead and write
Speed Setting Filter 2sRead and write
Speed Detection Filter 2sRead and write
Torque Control P Gain 2 (Current Loop Proportional Gain)%Read and write
Torque Control Integral Time 2 (Current Loop Integral Time)msRead and write
Torque Setting Filter 2sRead and write
Torque Detection Filter 2sRead and write
Torque Bias SelectionRead and write
Torque Bias 1%Read and write
Torque Bias 2%Read and write
Torque Bias 3%Read and write
Torque Bias FiltersRead and write
Torque Bias Operation TimesRead and write
Torque Bias Balance CompensationVRead and write
Fall-Time Torque Bias Terminal 1 Bias%Read and write
Fall-Time Torque Bias Terminal 1 Gain%Read and write
Analog Input Offset Adjustment%Read and write
Brake Operation SelectionRead and write
Control Terminal Option Number of Encoder PulsesRead and write
Control Terminal Option Encoder Rotation DirectionRead and write
Speed Deviation TimesRead and write
Excitation Ratio%Read and write
Control Terminal Option Signal Loss Detection SelectionRead and write
Terminal 4 Function AssignmentRead and write
Torque Current/Rated PM Motor CurrentARead and write
Second Motor Torque Current/Rated PM Motor CurrentARead and write
Encoder Option SelectionRead and write
Control Terminal Option Encoder Pulse Division RatioRead and write
Torque Detection%Read and write
Low Speed DetectionHzRead and write
Torque Monitoring Reference%Read and write
AM Output FiltersRead and write
Terminal 1 Function AssignmentRead and write
Current Output FiltersRead and write
Speed Detection HysteresisHzRead and write
Control Terminal Option Encoder Position Tuning Setting/StatusRead and write
Input Phase Loss Protection SelectionRead and write
Speed LimitHzRead and write
OLT Level Setting%Read and write
Fault DefinitionRead and write
Thermal Protector InputRead and write
Speed Feed Forward/Model Adaptive Speed Control SelectionRead and write
Speed Feed Forward FiltersRead and write
Speed Feed Forward Torque Limit%Read and write
Load Inertia RatioRead and write
Speed Feed Forward Gain%Read and write
Regeneration Avoidance Operation SelectionRead and write
Regeneration Avoidance Operation LevelVRead and write
Regeneration Avoidance at Deceleration Detection SensitivityRead and write
Regeneration Avoidance Compensation Frequency Limit ValueHzRead and write
Regeneration Avoidance Voltage Gain%Read and write
Control Terminal Option Encoder Magnetic Pole Position OffsetRead and write
Free Parameter 1Read and write
Free Parameter 2Read and write
Internal Storage Device Status IndicationRead
Cumulative Power Monitor Digit Shifted TimesRead and write
Load Factor%Read and write
Energy Saving Monitor Reference (Motor Capacity)kWRead and write
Control Selection during Commercial Power-Supply OperationRead and write
Power Saving Rate Reference ValueRead and write
Power Unit CostRead and write
Power Saving Monitor Average TimehRead and write
Power Saving Cumulative Monitor ClearRead and write
Operation Time Rate (Estimated Value)%Read and write
Input Voltage Mode SelectionRead and write
Parameter Copy Alarm ReleaseRead and write
PU Buzzer ControlRead and write
PU Contrast AdjustmentRead and write
Operation Panel Setting Dial Push Monitor SelectionRead and write
Droop Break Point Gain%Read and write
Droop Break Point Torque%Read and write
Fault InitiationRead and write
PM Parameter InitializationRead and write
Automatic Parameter SettingRead and write
Direct Setting SelectionRead and write
Lq Tuning Target Current Adjustment Coefficient%Read and write
Notch Filter FrequencyHzRead and write
Notch Filter DepthRead and write
Notch Filter WidthRead and write
Clock (Year)Read and write
Clock (Month, Day)Read and write
Clock (Hour, Minute)Read and write
Running Speed after Emergency Drive Retry ResetHzRead and write
Integral Stop Selection at Limited FrequencyRead and write
PTC Thermistor Protection Detection TimesRead and write
Monitor with Sign SelectionRead and write
Trace Operation SelectionRead and write
Trace Mode SelectionRead and write
Sampling CycleRead and write
Number of Analog ChannelsRead and write
Sampling Auto StartRead and write
Trigger Mode SelectionRead and write
Number of Sampling before Trigger%Read and write
Analog Source Selection (1ch)Read and write
Analog Source Selection (2ch)Read and write
Analog Source Selection (3ch)Read and write
Analog Source Selection (4ch)Read and write
Analog Source Selection (5ch)Read and write
Analog Source Selection (6ch)Read and write
Analog Source Selection (7ch)Read and write
Analog Source Selection (8ch)Read and write
Analog Trigger ChannelRead and write
Analog Trigger Operation SelectionRead and write
Analog Trigger LevelRead and write
Digital Source Selection (1ch)Read and write
Digital Source Selection (2ch)Read and write
Digital Source Selection (3ch)Read and write
Digital Source Selection (4ch)Read and write
Digital Source Selection (5ch)Read and write
Digital Source Selection (6ch)Read and write
Digital Source Selection (7ch)Read and write
Digital Source Selection (8ch)Read and write
Digital Trigger ChannelRead and write
Digital Trigger Operation SelectionRead and write
Display-Off Waiting TimeminRead and write
USB Host ResetRead and write
DC Brake Judgment Time for Anti-Sway Control OperationsRead and write
Anti-Sway Control Operation SelectionRead and write
Anti-Sway Control FrequencyHzRead and write
Anti-Sway Control DepthRead and write
Anti-Sway Control WidthRead and write
Rope LengthRead and write
Trolley WeightRead and write
Load WeightRead and write
Deceleration Time at Emergency StopsRead and write
Encoder Magnetic Pole Position OffsetRead and write
Torque Monitor FiltersRead and write
Running Speed Monitor FiltersRead and write
Excitation Current Monitor FiltersRead and write
Speed Limit Method SelectionRead and write
Torque Command Reverse SelectionRead and write
Speed Control Integral Term Clear TimemsRead and write
Constant Output Range Speed Control P Gain Compensation%Read and write
Speed Control P Gain 1 (Per-Unit System)Read and write
Speed Control P Gain 2 (Per-Unit System)Read and write
Model Speed Control Gain (Per-Unit System)Read and write
Per-Unit Speed Control Reference FrequencyHzRead and write
PID Upper Limit Manipulated Value%Read and write
PID Lower Limit Manipulated Value%Read and write
Second PID Display Bias CoefficientRead and write
Second PID Display Bias Analog Value%Read and write
Second PID Display Gain CoefficientRead and write
Second PID Display Gain Analog Value%Read and write
Second PID Set Point/Deviation Input SelectionRead and write
Second PID Measured Value Input SelectionRead and write
Second PID Unit SelectionRead and write
Second PID Upper Limit%Read and write
Second PID Lower Limit%Read and write
Second PID Deviation Limit%Read and write
Second PID Signal Operation SelectionRead and write
Second Output Interruption Detection TimesRead and write
Second Output Interruption Detection LevelHzRead and write
Second Output Interruption Cancel Level%Read and write
PLC Function User Parameter 1Read and write
PLC Function User Parameter 2Read and write
PLC Function User Parameter 3Read and write
PLC Function User Parameter 4Read and write
PLC Function User Parameter 5Read and write
PLC Function User Parameter 6Read and write
PLC Function User Parameter 7Read and write
PLC Function User Parameter 8Read and write
PLC Function User Parameter 9Read and write
PLC Function User Parameter 10Read and write
PLC Function User Parameter 11Read and write
PLC Function User Parameter 12Read and write
PLC Function User Parameter 13Read and write
PLC Function User Parameter 14Read and write
PLC Function User Parameter 15Read and write
PLC Function User Parameter 16Read and write
PLC Function User Parameter 17Read and write
PLC Function User Parameter 18Read and write
PLC Function User Parameter 19Read and write
PLC Function User Parameter 20Read and write
PLC Function User Parameter 21Read and write
PLC Function User Parameter 22Read and write
PLC Function User Parameter 23Read and write
PLC Function User Parameter 24Read and write
PLC Function User Parameter 25Read and write
PLC Function User Parameter 26Read and write
PLC Function User Parameter 27Read and write
PLC Function User Parameter 28Read and write
PLC Function User Parameter 29Read and write
PLC Function User Parameter 30Read and write
PLC Function User Parameter 31Read and write
PLC Function User Parameter 32Read and write
PLC Function User Parameter 33Read and write
PLC Function User Parameter 34Read and write
PLC Function User Parameter 35Read and write
PLC Function User Parameter 36Read and write
PLC Function User Parameter 37Read and write
PLC Function User Parameter 38Read and write
PLC Function User Parameter 39Read and write
PLC Function User Parameter 40Read and write
PLC Function User Parameter 41Read and write
PLC Function User Parameter 42Read and write
PLC Function User Parameter 43Read and write
PLC Function User Parameter 44Read and write
PLC Function User Parameter 45Read and write
PLC Function User Parameter 46Read and write
PLC Function User Parameter 47Read and write
PLC Function User Parameter 48Read and write
PLC Function User Parameter 49Read and write
PLC Function User Parameter 50Read and write
Target Position/Speed SelectionRead and write
Start Command Edge Detection SelectionRead and write
First Positioning Acceleration TimesRead and write
First Positioning Deceleration TimesRead and write
First Positioning Dwell TimemsRead and write
First Positioning Sub-FunctionRead and write
Second Positioning Acceleration TimesRead and write
Second Positioning Deceleration TimesRead and write
Second Positioning Dwell TimemsRead and write
Second Positioning Sub-FunctionRead and write
Third Positioning Acceleration TimesRead and write
Third Positioning Deceleration TimesRead and write
Third Positioning Dwell TimemsRead and write
Third Positioning Sub-FunctionRead and write
Fourth Positioning Acceleration TimesRead and write
Fourth Positioning Deceleration TimesRead and write
Fourth Positioning Dwell TimemsRead and write
Fourth Positioning Sub-FunctionRead and write
Fifth Positioning Acceleration TimesRead and write
Fifth Positioning Deceleration TimesRead and write
Fifth Positioning Dwell TimemsRead and write
Fifth Positioning Sub-FunctionRead and write
Sixth Positioning Acceleration TimesRead and write
Sixth Positioning Deceleration TimesRead and write
Sixth Positioning Dwell TimemsRead and write
Sixth Positioning Sub-FunctionRead and write
Seventh Positioning Acceleration TimesRead and write
Seventh Positioning Deceleration TimesRead and write
Seventh Positioning Dwell TimemsRead and write
Seventh Positioning Sub-FunctionRead and write
Eighth Positioning Acceleration TimesRead and write
Eighth Positioning Deceleration TimesRead and write
Eighth Positioning Dwell TimemsRead and write
Eighth Positioning Sub-FunctionRead and write
Ninth Positioning Acceleration TimesRead and write
Ninth Positioning Deceleration TimesRead and write
Ninth Positioning Dwell TimemsRead and write
Ninth Positioning Sub-FunctionRead and write
Tenth Positioning Acceleration TimesRead and write
Tenth Positioning Deceleration TimesRead and write
Tenth Positioning Dwell TimemsRead and write
Tenth Positioning Sub-FunctionRead and write
Eleventh Positioning Acceleration TimesRead and write
Eleventh Positioning Deceleration TimesRead and write
Eleventh Positioning Dwell TimemsRead and write
Eleventh Positioning Sub-FunctionRead and write
Twelfth Positioning Acceleration TimesRead and write
Twelfth Positioning Deceleration TimesRead and write
Twelfth Positioning Dwell TimemsRead and write
Twelfth Positioning Sub-FunctionRead and write
Thirteenth Positioning Acceleration TimesRead and write
Thirteenth Positioning Deceleration TimesRead and write
Thirteenth Positioning Dwell TimemsRead and write
Thirteenth Positioning Sub-FunctionRead and write
Fourteenth Positioning Acceleration TimesRead and write
Fourteenth Positioning Deceleration TimesRead and write
Fourteenth Positioning Dwell TimemsRead and write
Fourteenth Positioning Sub-FunctionRead and write
Fifteenth Positioning Acceleration TimesRead and write
Fifteenth Positioning Deceleration TimesRead and write
Fifteenth Positioning Dwell TimemsRead and write
Fifteenth Positioning Sub-FunctionRead and write
Home Position Return Method SelectionRead and write
Home Position Return SpeedHzRead and write
Home Position Return Creep SpeedHzRead and write
Home Position Shift Amount Lower 4 DigitsRead and write
Home Position Shift Amount Upper 4 DigitsRead and write
Travel Distance after Proximity Dog on Lower 4 DigitsRead and write
Travel Distance after Proximity Dog on Upper 4 DigitsRead and write
Home Position Return Stopper Torque%Read and write
Home Position Return Stopper Waiting TimesRead and write
Position Control Terminal Input SelectionRead and write
Roll Feeding Mode SelectionRead and write
Position Detection Lower 4 DigitsRead and write
Position Detection Upper 4 DigitsRead and write
Position Detection SelectionRead and write
Position Detection Hysteresis WidthRead and write
Second Position Control GainRead and write
Second Pre-Excitation SelectionRead and write
Communication Option Parameter 1300Read and write
Communication Option Parameter 1301Read and write
Communication Option Parameter 1302Read and write
Communication Option Parameter 1303Read and write
Communication Option Parameter 1304Read and write
Communication Option Parameter 1305Read and write
Communication Option Parameter 1306Read and write
Communication Option Parameter 1307Read and write
Communication Option Parameter 1308Read and write
Communication Option Parameter 1309Read and write
Communication Option Parameter 1310Read and write
Communication Option Parameter 1311Read and write
Communication Option Parameter 1312Read and write
Communication Option Parameter 1313Read and write
Communication Option Parameter 1314Read and write
Communication Option Parameter 1315Read and write
Communication Option Parameter 1316Read and write
Communication Option Parameter 1317Read and write
Communication Option Parameter 1318Read and write
Communication Option Parameter 1319Read and write
Communication Option Parameter 1320Read and write
Communication Option Parameter 1321Read and write
Communication Option Parameter 1322Read and write
Communication Option Parameter 1323Read and write
Communication Option Parameter 1324Read and write
Communication Option Parameter 1325Read and write
Communication Option Parameter 1326Read and write
Communication Option Parameter 1327Read and write
Communication Option Parameter 1328Read and write
Communication Option Parameter 1329Read and write
Communication Option Parameter 1330Read and write
Communication Option Parameter 1331Read and write
Communication Option Parameter 1332Read and write
Communication Option Parameter 1333Read and write
Communication Option Parameter 1334Read and write
Communication Option Parameter 1335Read and write
Communication Option Parameter 1336Read and write
Communication Option Parameter 1337Read and write
Communication Option Parameter 1338Read and write
Communication Option Parameter 1339Read and write
Communication Option Parameter 1340Read and write
Communication Option Parameter 1341Read and write
Communication Option Parameter 1342Read and write
Communication Option Parameter 1343Read and write
P/PI Control Switchover FrequencyHzRead and write
Emergency Stop Operation SelectionRead and write
Communication Option Parameter 1350Read and write
Communication Option Parameter 1351Read and write
Communication Option Parameter 1352Read and write
Communication Option Parameter 1353Read and write
Communication Option Parameter 1354Read and write
Communication Option Parameter 1355Read and write
Communication Option Parameter 1356Read and write
Communication Option Parameter 1357Read and write
Communication Option Parameter 1358Read and write
Communication Option Parameter 1359Read and write
C2 Terminal 2 Frequency Setting Bias FrequencyHzRead and write
C3 Terminal 2 Frequency Setting Bias%Read and write
C3 Terminal 2 Bias Terminal Analog ValueRead
Terminal 2 Frequency Setting Gain Frequency (Pr.903)HzRead and write
C4 Terminal 2 Frequency Setting Gain%Read and write
C4 Terminal 2 Gain Terminal Analog ValueRead
C5 Terminal 4 Frequency Setting Bias FrequencyHzRead and write
C6 Terminal 4 Frequency Setting Bias%Read and write
C6 Terminal 4 Bias Terminal Analog ValueRead
Terminal 4 Frequency Setting Gain Frequency (Pr.905)HzRead and write
C7 Terminal 4 Frequency Setting Gain%Read and write
C7 Terminal 4 Gain Terminal Analog ValueRead
C12 Terminal 1 Bias Frequency (Speed)HzRead and write
C13 Terminal 1 Bias (Speed)%Read and write
C13 Terminal 1 Bias Speed Terminal Analog ValueRead
C14 Terminal 1 Gain Frequency (Speed)HzRead and write
C15 Terminal 1 Gain (Speed)%Read and write
C15 Terminal 1 Gain Speed Terminal Analog ValueRead
C16 Terminal 1 Bias Command (Torque/Magnetic Flux)%Read and write
C17 Terminal 1 Bias (Torque/Magnetic Flux)%Read and write
C17 Terminal 1 Bias Torque Terminal Analog ValueRead
C18 Terminal 1 Gain Command (Torque/Magnetic Flux)%Read and write
C19 Terminal 1 Gain (Torque/Magnetic Flux)%Read and write
C19 Terminal 1 Gain Torque Terminal Analog ValueRead
C29 Motor Temperature Detection CalibrationRead and write
C29 Motor Temperature Terminal Analog ValueRead
C30 Terminal 6 Bias Frequency (Speed)Read and write
C31 Terminal 6 Bias (Speed)Read and write
C31 Terminal 6 Bias Speed Terminal Analog ValueRead
C32 Terminal 6 Gain Frequency (Speed)Read and write
C33 Terminal 6 Gain (Speed)Read and write
C33 Terminal 6 Gain Speed Terminal Analog ValueRead
C34 Terminal 6 Bias Command (Torque)Read and write
C35 Terminal 6 Bias (Torque)Read and write
C35 Terminal 6 Bias Torque Terminal Analog ValueRead
C36 Terminal 6 Gain Command (Torque)Read and write
C37 Terminal 6 Gain (Torque)Read and write
C37 Terminal 6 Gain Torque Terminal Analog ValueRead
C8 Current Output Bias Signal%Read and write
C9 Current Output Bias Current%Read and write
C10 Current Output Gain Signal%Read and write
C11 Current Output Gain Current%Read and write
C38 Terminal 4 Bias Command (Torque/Magnetic Flux)%Read and write
C39 Terminal 4 Bias (Torque/Magnetic Flux)%Read and write
C39 Terminal 4 Bias Torque Terminal Analog ValueRead
C40 Terminal 4 Gain Command (Torque/Magnetic Flux)%Read and write
C41 Terminal 4 Gain (Torque/Magnetic Flux)%Read and write
C41 Terminal 4 Gain Torque Terminal Analog ValueRead
C42 PID Display Bias CoefficientRead and write
C43 PID Display Bias Analog Value%Read and write
C43 PID Display Bias Terminal Analog ValueRead
C44 PID Display Gain CoefficientRead and write
C45 PID Display Gain Analog Value%Read and write
C45 PID Display Gain Terminal Analog ValueRead
ModelRead
CapacityRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show output frequency, current and power of every drive on a dashboard and compare pumps or fans across sites.
  • Get an email alert when a new fault appears in Fault Record 1 or the heat sink temperature passes your threshold.
  • Keep cumulative energy and operating hours in the history to report consumption and plan maintenance.
  • Change the frequency setpoint or acceleration time remotely instead of driving to the control panel.
  • Use an automation with a time schedule to write a lower frequency setpoint at night.

Installation

  1. Connect the RS-485 terminals of the inverter to RS485 A and B of the ModbusCloud Gateway. For a two-wire bus, bridge the send and receive terminals as shown in the Mitsubishi manual.

  2. Set the terminating resistor switch to 100 ohm on the inverter at the end of the bus.

  3. On the inverter set Pr.549 to 1 (Modbus RTU), Pr.331 to a station number from 1 to 247, and check Pr.332 to Pr.334 (9600 baud, even parity, 1 stop bit by default).

  4. In ModbusCloud, add a Modbus device with the same station number and serial settings and import this template.

  5. Check that Output Frequency, Output Current and Model show sensible values.

  6. To control the drive over Modbus, set Pr.79 and Pr.340 so the inverter runs in NET operation mode.

Things to watch for

The inverter does not answer. What should I check?

Pr.549 must be 1, otherwise the inverter speaks the Mitsubishi computer link protocol. Station number 0 is broadcast and never replies, so set Pr.331 to a value from 1 to 247. Match Pr.332 to Pr.334 with the Gateway (factory setting 9600 baud, even parity, 1 stop bit), then check A and B and the terminating resistor switch.

Why does the inverter ignore my run command or frequency setpoint?

Commands over RS-485 only take effect in NET operation mode. Set Pr.79 and Pr.340 so the inverter starts in NET mode, or write the Operation Mode register. Pr.338 and Pr.339 decide whether the start command and the speed come from communication or from the terminals.

Current, power and energy look ten times too high on a large drive.

Inverters of 75K and larger report current, power and energy in steps of 0.1 instead of 0.01. The template uses the steps of 55K and smaller models. On a larger drive, change the scale of those registers to 0.1.

The inverter trips with E.SER after switching to NET mode.

Pr.539 is the Modbus communication check time. With a value other than 9999 the inverter trips when no message arrives in time, and 0 trips at once in NET mode. ModbusCloud reads every 5 minutes by default, so leave Pr.539 at 9999 or set it longer than the read interval.

Is it safe to write parameters from ModbusCloud?

Every parameter is writable, including the reset and parameter clear registers. Write only values inside the range in the Mitsubishi manual, check Pr.77 if writes are refused, and use Pr.342 to choose whether a write goes to EEPROM or only to RAM. Never write the clear registers on a running installation.

More Mitsubishi Electric templates

Want to see how it works?

Electrician working in an open distribution board