S&P S & P DOMEO 210 RD Modbus RTU template

S & P DOMEO 210 RD

Controls S&P Domeo 210 RD heat recovery ventilation unit via Modbus RTU

This template connects to the S&P Domeo 210 RD heat recovery ventilation unit via Modbus RTU. It reads temperatures, fan speeds, bypass and battery status, and provides control over airflow, heating setpoints, and bypass operation. All registers use uint16 format.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
61, read and write
Brand
S&P
Key readings
Interior and exterior temperatures · Impulsion and discharge temperatures · Extraction and impulse engine RPM · Bypass state · Pre/post heating battery status · Dirty filter alarm status
Available commands
Bypass manual/automatic control · Post-heating battery control · Flow and free cooling selection · CLP control
Compatible models
Domeo 210 RD
Last updated

Registers (61)

61 read, 15 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
2 CLP CONTROLRead and write
5 THAW MODERead
7 IMPULSION MOTOR STATUSRead and write
10 INTERIOR TEMPERATURE PROBE STATUSRead
11 DISCHARGE TEMPERATURE PROBE STATUSRead
12 OUTDOOR TEMPERATURE PROBE STATUS RRead and write
13 STATUS PROBE IMPULSION TEMPERATURERead
14 ALARM STATUS OF DIRTY FILTERRead
6 ENGINE EXTRACTION STATUSRead and write
2 BATTERY PRE-HEATING R_W 0Read
3 BATTERY POST-HEATING R_W 0Read and write
4 POTENTIAL FREE CONTACT CONTROL SELECTION R_W 0Read and write
6 VERSION SELECTOR R_W 0Read
7 MODE ACTIVATION R_W 0Read
8 AUTOMATIC CONTROL BYPASS R_W 0Read and write
9 BYPASS MANUAL R_W 0Read and write
12 DIRTY FILTER ALARM RESET (BY TIME)Read
13 RESTORE FACTORY PARAMETERS WRead
1 VERSION RRead
6 SOFTWARE VERSION CENTRAL UNITYRead
7 REMOTE SOFTWARE VERSIONRead
8 CONSOLE PROGRAMMING SOFTWARE VERSIONRead and write
9 TYPE OF DOUBLE FLOWRead and write
10 TIPE OF REGULATIONRead and write
12 FLOW OFFSETRead
13 MINIMUM FLOWRead
14 TIMED HIGH FLOW 1_2H _ BOOSTRead
15 HIGH FLOW _ FREE COOLINGRead and write
16 ACTUAL FLOWRead and write
17 MEASURED TENSION 0-10VVRead and write
19 EXTRACTION ENGINE REVOLUTIONSrpmRead
20 IMPULSE ENGINE REVOLUTIONSrpmRead
21 TEMPERATURE INT°CRead
22 TEMPERATURE EXT°CRead
23 TEMPERATURE Tex°CRead
24 IMPULSION TEMPERATURE°CRead
25 BYPASS STATERead
26 BATTERY STATUS PREHEATINGRead
27 POST HEATING BATTERY STATUSRead
37 ALARM TIME OF DIRTY FILTERhRead
36 TEMPERATURE Tin BATTERY PREHEATING°CRead
38 TEMPERATURE Tout PREHEATING BATTERY°CRead
39 TEMPERATURE Tin POST HEATING BATTERY°CRead
40 TEMPERATURE Tout POST HEATING BATTERY_°CRead
0 INTERFACE MODBUS NODERead
1 BAUDRATE MODBUSRead
8 SELECTION OF FLOW OFFSETRead
9 LOW FLOW SELECTIONRead
10 SELECTION OF TIMED HIGH FLOW 1_2 H _ BOOSTRead
11 HIGH FLOW RATE SELECTION _ FREECOOLINGRead and write
15 FLOW SETPOINTRead
16 MINIMUM SETPOINT IN 0‐10V_VRead
17 MAXIMUM SETPOINT IN 0‐10VVRead
22 BYPASS AUTO: Text MINIMUM°CRead
23 BYPASS AUTO: MINIMUM Tint_°CRead
24 TIME BYPASS MANUALminRead
25 PRE-HEATING BATTERY Tº ON°CRead
26 PRE-HEATING BATTERY Tº OFF°CRead
27 PRE-HEATING BATTERY CONSTANT Tº°CRead
28 POST-HEATING BATTERY CONSTANT Tº°CRead
31 TIME SELECTION ALARM OF DIRTY FILTERhRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor interior and exterior temperatures on a live dashboard to verify heat recovery performance.
  • Create an alert when the dirty filter alarm activates so maintenance can be scheduled promptly.
  • Adjust post-heating battery setpoints remotely to optimize comfort without an on-site visit.
  • Log extraction and impulse fan RPM over time to detect motor degradation or airflow imbalance.
  • Switch bypass control between manual and automatic mode based on seasonal requirements.
  • Track bypass state and free cooling operation to validate energy savings during mild weather.

Installation

  1. Connect the ModbusCloud Gateway to the S&P Domeo 210 RD RS-485 terminals using a twisted pair cable with correct A/B polarity.

  2. Set the Modbus RTU baud rate to 19200 and parity to odd on both the gateway and the Domeo 210 RD unit.

  3. Assign a unique Modbus slave address on the Domeo 210 RD and note it for gateway configuration.

  4. Import the S&P Domeo 210 RD template from the ModbusCloud template library into your project.

  5. Enter the configured slave address in the template settings on the ModbusCloud platform.

  6. Verify communication by checking that temperature readings and fan RPM values appear on the dashboard.

Things to watch for

I see no data after connecting. What should I check first?

Verify that the baud rate is set to 19200 and parity to odd (1 stop bit) on both the gateway and the Domeo 210 RD. Also confirm that the RS-485 A and B wires are not swapped.

Some registers seem to overlap. Is that normal?

Yes. Some register addresses appear in both read and write function code groups. The template handles this by using the correct function codes for each operation. Do not manually duplicate these registers.

Can I change heating setpoints remotely?

Yes. The template includes writable registers for pre-heating and post-heating battery temperature setpoints. You can adjust these values directly from the ModbusCloud dashboard.

How do I know if the filter needs replacing?

The template reads the dirty filter alarm register. You can set up an alert in ModbusCloud to notify you when this alarm activates, so you can schedule maintenance before airflow is significantly reduced.

Want to see how it works?

Electrician working in an open distribution board