SAX SAX Power Home (Plus) (grid)
The SAX Power Home (Plus) is a single-phase AC-coupled battery storage system with an integrated inverter, designed for residential photovoltaic installations. The SAX Power Home (Plus) communicates over Modbus TCP on port 502 and exposes register data across multiple slave entities. This template reads the grid power register (address 48) from the smartmeter slave, giving you real-time visibility of power flow at the grid connection point. Monitoring this value through the ModbusCloud Gateway lets installers and building owners track self-consumption and detect unexpected grid import or export at a glance.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 1, read only
- Brand
- SAX
- Last updated
Registers (1)
1 read, 0 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| power | W | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Monitor real-time grid power flow to verify the SAX Power Home (Plus) is correctly offsetting household consumption.
- Track grid import trends over time to evaluate whether battery capacity needs to be expanded.
- Alert on sustained grid export above a threshold to catch inverter or smartmeter configuration faults.
- Compare grid power readings before and after firmware updates to verify consistent measurement behaviour.
- Report daily grid import and export totals to building owners for energy cost reconciliation.
Installation
Enable Modbus TCP on the SAX Power Home (Plus) via the device web interface under the communication or Modbus section, and confirm port 502 is accessible on the local network.
Connect the ModbusCloud Gateway to the same LAN as the SAX Power Home (Plus) using an Ethernet cable, ensuring both devices obtain IP addresses on the same subnet.
In the ModbusCloud portal, add the gateway, import this template, and set the Modbus unit ID to 40 (decimal), which is the slave ID for the integrated smartmeter entity on SAX Power devices.
Trigger a manual poll of register 48 in the portal and verify the returned watt value matches the power reading shown on the SAX Power device display or web interface.
Things to watch for
Why does register 48 return a value around 16384 instead of the actual grid power?
The SAX Power register map documents an offset of 16384 for register 48. The raw uint16 reading includes this fixed offset, so you must subtract 16384 from the raw value to obtain the real grid power in watts. Configure this offset in your ModbusCloud channel scaling settings.
The gateway connects but register 48 returns zero or an error. What should I check?
Verify that the Modbus unit ID is set to 40 (decimal, equivalent to 0x28 hex) in the ModbusCloud portal. The smartmeter values on the SAX Power Home (Plus) are exposed on slave ID 40, not the default ID 1. Using the wrong unit ID is the most common cause of empty readings.
Why does the grid power value fluctuate wildly between polls?
The SAX Power Home (Plus) delivers all register values as 16-bit unsigned integers. Ensure the data type in the portal is set to uint16 (big-endian). Using a 32-bit type or wrong byte order will cause the value to appear random or wrap incorrectly across positive and negative power flows.
Modbus TCP connection drops intermittently. How can I stabilise it?
The SAX Power device runs its Modbus server on port 502. Avoid polling intervals below 2 seconds, as the embedded TCP stack can reject rapid successive connections. Set the ModbusCloud Gateway poll interval to at least 5 seconds and enable connection keep-alive if supported, to reduce reconnect overhead.