Thermokon NOVOS 3

Room sensor and operating unit for temperature, humidity, CO2 and VOC with set point and fan stage.

The Thermokon NOVOS 3 is a room sensor and room operating unit that measures temperature and, depending on the version, humidity, CO2 and VOC in offices and classrooms. This Modbus RTU template reads all measured values, occupancy and fan stage and lets you write set points, offsets and display settings from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
152, read and write
Key readings
Temperature · Relative humidity · CO2 · VOC · Dew point · Room occupancy
Available commands
Set point · Room occupancy · Fan stage feedback · LED colour · Display icons
Compatible models
NOVOS 3 RS485 Modbus · NOVOS 3 x RS485 Modbus · NOVOS 3 INC x RS485 Modbus
Last updated

Registers (152)

152 read, 138 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Temperature°CRead
Relative Humidity%RHRead
CO2ppmRead
VOC%Read
CO2 VOC Mix%Read
Absolute Humidityg/m³Read
EnthalpyRead
Dew Point°CRead
Digital InputRead
Room OccupancyRead and write
ECO FunctionRead and write
Set Point Effective°CRead and write
Fan Stage User SetRead
Fan Stage Feedback BMSRead and write
Set Point Display ModeRead and write
Base Set Point°CRead and write
Set Point Adjustment RangeKRead and write
Set Point Step WidthKRead and write
ECO Button FunctionRead and write
Occupancy Button FunctionRead and write
Room Occupancy After ResetRead and write
Fan Stage DisplayRead and write
Number of Fan StagesRead and write
Fan Stage Auto AvailableRead and write
Minimum Fan StageRead and write
Fan Stage After ResetRead and write
LED Illumination ModeRead and write
LED Illumination ColourRead and write
Unit SystemRead and write
Display ModeRead and write
Offset Temperature°CRead and write
Offset Relative Humidity%RHRead and write
Offset CO2ppmRead and write
Offset VOC%Read and write
Temperature Lower Limit°CRead and write
Temperature Upper Limit°CRead and write
Display TemperatureRead and write
TLF Temperature OnRead and write
TLF Temperature Range 1 ColourRead and write
TLF Temperature Range 2 ColourRead and write
TLF Temperature Range 3 ColourRead and write
TLF Temperature Range 4 ColourRead and write
TLF Temperature Range 5 ColourRead and write
TLF Temperature Threshold 1-2Read and write
TLF Temperature Threshold 2-3Read and write
TLF Temperature Threshold 3-4Read and write
TLF Temperature Threshold 4-5Read and write
Relative Humidity Lower Limit%RHRead and write
Relative Humidity Upper Limit%RHRead and write
Display Relative HumidityRead and write
TLF Relative Humidity OnRead and write
TLF Relative Humidity Range 1 ColourRead and write
TLF Relative Humidity Range 2 ColourRead and write
TLF Relative Humidity Range 3 ColourRead and write
TLF Relative Humidity Range 4 ColourRead and write
TLF Relative Humidity Range 5 ColourRead and write
TLF Relative Humidity Threshold 1-2Read and write
TLF Relative Humidity Threshold 2-3Read and write
TLF Relative Humidity Threshold 3-4Read and write
TLF Relative Humidity Threshold 4-5Read and write
Absolute Humidity Lower Limitg/m³Read and write
Absolute Humidity Upper Limitg/m³Read and write
Display Absolute HumidityRead and write
TLF Absolute Humidity OnRead and write
TLF Absolute Humidity Range 1 ColourRead and write
TLF Absolute Humidity Range 2 ColourRead and write
TLF Absolute Humidity Range 3 ColourRead and write
TLF Absolute Humidity Range 4 ColourRead and write
TLF Absolute Humidity Range 5 ColourRead and write
TLF Absolute Humidity Threshold 1-2Read and write
TLF Absolute Humidity Threshold 2-3Read and write
TLF Absolute Humidity Threshold 3-4Read and write
TLF Absolute Humidity Threshold 4-5Read and write
Enthalpy Lower LimitRead and write
Enthalpy Upper LimitRead and write
Display EnthalpyRead and write
TLF Enthalpy OnRead and write
TLF Enthalpy Range 1 ColourRead and write
TLF Enthalpy Range 2 ColourRead and write
TLF Enthalpy Range 3 ColourRead and write
TLF Enthalpy Range 4 ColourRead and write
TLF Enthalpy Range 5 ColourRead and write
TLF Enthalpy Threshold 1-2Read and write
TLF Enthalpy Threshold 2-3Read and write
TLF Enthalpy Threshold 3-4Read and write
TLF Enthalpy Threshold 4-5Read and write
Dew Point Lower Limit°CRead and write
Dew Point Upper Limit°CRead and write
Display Dew PointRead and write
TLF Dew Point OnRead and write
TLF Dew Point Range 1 ColourRead and write
TLF Dew Point Range 2 ColourRead and write
TLF Dew Point Range 3 ColourRead and write
TLF Dew Point Range 4 ColourRead and write
TLF Dew Point Range 5 ColourRead and write
TLF Dew Point Threshold 1-2Read and write
TLF Dew Point Threshold 2-3Read and write
TLF Dew Point Threshold 3-4Read and write
TLF Dew Point Threshold 4-5Read and write
CO2 Lower LimitppmRead and write
CO2 Upper LimitppmRead and write
Display CO2Read and write
TLF CO2 OnRead and write
TLF CO2 Range 1 ColourRead and write
TLF CO2 Range 2 ColourRead and write
TLF CO2 Range 3 ColourRead and write
TLF CO2 Range 4 ColourRead and write
TLF CO2 Range 5 ColourRead and write
TLF CO2 Threshold 1-2Read and write
TLF CO2 Threshold 2-3Read and write
TLF CO2 Threshold 3-4Read and write
TLF CO2 Threshold 4-5Read and write
VOC Lower Limit%Read and write
VOC Upper Limit%Read and write
Display VOCRead and write
TLF VOC OnRead and write
TLF VOC Range 1 ColourRead and write
TLF VOC Range 2 ColourRead and write
TLF VOC Range 3 ColourRead and write
TLF VOC Range 4 ColourRead and write
TLF VOC Range 5 ColourRead and write
TLF VOC Threshold 1-2Read and write
TLF VOC Threshold 2-3Read and write
TLF VOC Threshold 3-4Read and write
TLF VOC Threshold 4-5Read and write
CO2 VOC Mix Lower Limit%Read and write
CO2 VOC Mix Upper Limit%Read and write
Display CO2 VOC MixRead and write
TLF CO2 VOC Mix OnRead and write
TLF CO2 VOC Mix Range 1 ColourRead and write
TLF CO2 VOC Mix Range 2 ColourRead and write
TLF CO2 VOC Mix Range 3 ColourRead and write
TLF CO2 VOC Mix Range 4 ColourRead and write
TLF CO2 VOC Mix Range 5 ColourRead and write
TLF CO2 VOC Mix Threshold 1-2Read and write
TLF CO2 VOC Mix Threshold 2-3Read and write
TLF CO2 VOC Mix Threshold 3-4Read and write
TLF CO2 VOC Mix Threshold 4-5Read and write
Sensor SetupRead
Hardware VersionRead
Firmware Version Main SubRead
Firmware Version Revision BuildRead
Icon Dew PointRead and write
Icon Window OpenRead and write
Icon Calibration DueRead and write
Icon Communication Error BusRead and write
Icon ECORead and write
Icon Mode HeatingRead and write
Icon Mode CoolingRead and write
Icon Presence DetectionRead and write
Icon WarningRead and write
Icon Maintenance DueRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show temperature, humidity and CO2 per room on a ModbusCloud dashboard.
  • Get an email alert when CO2 in a meeting room stays above a threshold you set.
  • Keep a year of room climate history to check comfort and ventilation per season.
  • Adjust the base set point of a room from ModbusCloud without going on site.
  • Switch the warning or maintenance icon on the display from an automation.

Installation

  1. Connect A and B of the RS485 bus to the ModbusCloud Gateway with twisted pair cable and terminate both ends with 120 ohm.

  2. Set a unique address, the baud rate and parity with the DIP switches on the NOVOS 3.

  3. In ModbusCloud, add a Modbus device on the Gateway with that address and serial settings and import this template.

  4. Check that temperature and, if present, humidity and CO2 read plausible values.

Things to watch for

The unit does not answer. What should I check?

Check address, baud rate and parity on the DIP switches against ModbusCloud. Without parity the unit can use 1 or 2 stop bits, so match that too. Then check A and B and the 120 ohm termination at both bus ends.

Why do some registers read zero or nonsense?

Not every NOVOS 3 version has every sensor. A temperature-only unit has no humidity, CO2 or VOC. Read Sensor Setup to see which sensors are present and hide the registers you do not need.

Temperature reads in Fahrenheit. Why?

Register Unit System is set to 2, imperial. Set it to 1 for SI. Measuring limits are not converted when you switch, so check them afterwards.

Can I write the settings as often as I like?

No. Set points, offsets, limits and display settings are stored in EEPROM and must not be written in short cycles. Write them once when you configure the unit. The LED registers are not stored and must be written again after a restart.