Weishaupt Weishaupt WEM-Modbus Gateway Modbus TCP template

Weishaupt WEM-Modbus Gateway

Gateway for Weishaupt WTC condensing boilers with boiler temperatures, heat output and heating setpoints.

The Weishaupt WEM-Modbus gateway is a protocol converter that makes WTC gas condensing boilers and the WEM system device readable over Modbus TCP in homes and commercial buildings. This Modbus TCP template reads boiler and flow temperatures, heat output, pressure and faults, and lets you write operating modes and setpoints from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
464, read and write
Key readings
Boiler temperature · Heat output · Flow temperature · Outdoor temperature · Hot water temperature · System pressure · Fault number
Available commands
Operating mode · Room setpoints · Flow setpoints · Hot water setpoints · Hot water push
Compatible models
Gateway WEM-Modbus · Weishaupt WTC gas condensing boiler via WEM-SG system device
Last updated

Registers (464)

464 read, 128 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
WTC1 Boiler Temperature°CRead164FC03int16
WTC1 Flow Setpoint°CRead163FC03int16
WTC1 Heat OutputkWRead170FC03uint32
WTC1 Flow Ratel/hRead165FC03uint16
WTC1 System PressurebarRead166FC03uint16
WTC1 Operating PhaseRead
WTC1 Burner PhaseRead
WTC1 Heat Yesterday TotalkWhRead
WTC1 Heat Yesterday HeatingkWhRead
WTC1 Heat Yesterday Hot WaterkWhRead
WTC2 Boiler Temperature°CRead
WTC2 Flow Setpoint°CRead
WTC2 Heat OutputkWRead
WTC2 Flow Ratel/hRead
WTC2 System PressurebarRead
WTC2 Operating PhaseRead
WTC2 Burner PhaseRead
WTC2 Heat Yesterday TotalkWhRead
WTC2 Heat Yesterday HeatingkWhRead
WTC2 Heat Yesterday Hot WaterkWhRead
WTC3 Boiler Temperature°CRead
WTC3 Flow Setpoint°CRead
WTC3 Heat OutputkWRead
WTC3 Flow Ratel/hRead
WTC3 System PressurebarRead
WTC3 Operating PhaseRead
WTC3 Burner PhaseRead
WTC3 Heat Yesterday TotalkWhRead
WTC3 Heat Yesterday HeatingkWhRead
WTC3 Heat Yesterday Hot WaterkWhRead
WTC4 Boiler Temperature°CRead
WTC4 Flow Setpoint°CRead
WTC4 Heat OutputkWRead
WTC4 Flow Ratel/hRead
WTC4 System PressurebarRead
WTC4 Operating PhaseRead
WTC4 Burner PhaseRead
WTC4 Heat Yesterday TotalkWhRead
WTC4 Heat Yesterday HeatingkWhRead
WTC4 Heat Yesterday Hot WaterkWhRead
WTC5 Boiler Temperature°CRead
WTC5 Flow Setpoint°CRead
WTC5 Heat OutputkWRead
WTC5 Flow Ratel/hRead
WTC5 System PressurebarRead
WTC5 Operating PhaseRead
WTC5 Burner PhaseRead
WTC5 Heat Yesterday TotalkWhRead
WTC5 Heat Yesterday HeatingkWhRead
WTC5 Heat Yesterday Hot WaterkWhRead
WTC6 Boiler Temperature°CRead
WTC6 Flow Setpoint°CRead
WTC6 Heat OutputkWRead
WTC6 Flow Ratel/hRead
WTC6 System PressurebarRead
WTC6 Operating PhaseRead
WTC6 Burner PhaseRead
WTC6 Heat Yesterday TotalkWhRead
WTC6 Heat Yesterday HeatingkWhRead
WTC6 Heat Yesterday Hot WaterkWhRead
WTC7 Boiler Temperature°CRead
WTC7 Flow Setpoint°CRead
WTC7 Heat OutputkWRead
WTC7 Flow Ratel/hRead
WTC7 System PressurebarRead
WTC7 Operating PhaseRead
WTC7 Burner PhaseRead
WTC7 Heat Yesterday TotalkWhRead
WTC7 Heat Yesterday HeatingkWhRead
WTC7 Heat Yesterday Hot WaterkWhRead
WTC8 Boiler Temperature°CRead
WTC8 Flow Setpoint°CRead
WTC8 Heat OutputkWRead
WTC8 Flow Ratel/hRead
WTC8 System PressurebarRead
WTC8 Operating PhaseRead
WTC8 Burner PhaseRead
WTC8 Heat Yesterday TotalkWhRead
WTC8 Heat Yesterday HeatingkWhRead
WTC8 Heat Yesterday Hot WaterkWhRead
Outdoor Temperature°CRead
Flow Temperature HC1°CRead
Flow Setpoint HC1°CRead
Room Setpoint HC1°CRead
Hot Water Temperature°CRead
Hot Water Setpoint°CRead
Circulation Return Temperature°CRead
Plate Heat Exchanger Temperature°CRead
Buffer Tank Top Temperature°CRead
Buffer Tank Bottom Temperature°CRead
Heat Demand Heating°CRead
Heat Demand Hot Water°CRead
Fault Or Warning PendingRead
Fault NumberRead
Fault ModuleRead
Hot Water StatusRead
Hot Water PumpRead
Operating Mode HC1 ActualRead
Status HC1Read
Cascade Balancing Temperature°CRead
Cascade Target Modulation Heating%Read
Cascade Target Modulation Hot Water%Read
Cascade System Setpoint Heating°CRead
Cascade System Setpoint Hot Water°CRead
Operating Mode HC1 SetpointRead and write
Summer Winter Switch HC1Read and write
System Operating ModeRead and write
Room Setpoint Comfort HC1°CRead and write
Room Setpoint Normal HC1°CRead and write
Room Setpoint Setback HC1°CRead and write
Flow Setpoint Comfort HC1°CRead and write
Flow Setpoint Normal HC1°CRead and write
Flow Setpoint Setback HC1°CRead and write
Flow Setpoint Special Level HC1°CRead and write
N1 Demand Via Ethernet%Read and write
Hot Water PushRead and write
Hot Water Setpoint Normal°CRead and write
Hot Water Setpoint Setback°CRead and write
Sequence ChangeRead and write
Sequence Change TimehRead and write
CANopen SpecificRead
Time Of Day Word 1Read
Time Of Day Word 2Read
Date Word 1Read
Date Word 2Read
Date Word 3Read
SG2 Outdoor Temperature°CRead
SG2 Flow Temperature HC1°CRead
SG2 Flow Setpoint HC1°CRead
SG2 Room Setpoint HC1°CRead
SG2 Hot Water Temperature°CRead
SG2 Hot Water Setpoint°CRead
SG2 Circulation Return Temperature°CRead
SG2 Plate Heat Exchanger Temperature°CRead
SG2 Buffer Tank Top Temperature°CRead
SG2 Buffer Tank Bottom Temperature°CRead
SG2 Heat Demand Heating°CRead
SG2 Heat Demand Hot Water°CRead
SG2 Fault Or Warning PendingRead
SG2 Fault NumberRead
SG2 Fault ModuleRead
SG2 Hot Water StatusRead
SG2 Hot Water PumpRead
SG2 Operating Mode HC1 ActualRead
SG2 Status HC1Read
SG2 Cascade Balancing Temperature°CRead
SG2 Cascade Target Modulation Heating%Read
SG2 Cascade Target Modulation Hot Water%Read
SG2 Cascade System Setpoint Heating°CRead
SG2 Cascade System Setpoint Hot Water°CRead
SG2 Operating Mode HC1 SetpointRead and write
SG2 Summer Winter Switch HC1Read and write
SG2 System Operating ModeRead and write
SG2 Room Setpoint Comfort HC1°CRead and write
SG2 Room Setpoint Normal HC1°CRead and write
SG2 Room Setpoint Setback HC1°CRead and write
SG2 Flow Setpoint Comfort HC1°CRead and write
SG2 Flow Setpoint Normal HC1°CRead and write
SG2 Flow Setpoint Setback HC1°CRead and write
SG2 Flow Setpoint Special Level HC1°CRead and write
SG2 N1 Demand Via Ethernet%Read and write
SG2 Hot Water PushRead and write
SG2 Hot Water Setpoint Normal°CRead and write
SG2 Hot Water Setpoint Setback°CRead and write
SG2 Sequence ChangeRead and write
SG2 Sequence Change TimehRead and write
SG2 CANopen SpecificRead
SG2 Time Of Day Word 1Read
SG2 Time Of Day Word 2Read
SG2 Date Word 1Read
SG2 Date Word 2Read
SG2 Date Word 3Read
SG3 Outdoor Temperature°CRead
SG3 Flow Temperature HC1°CRead
SG3 Flow Setpoint HC1°CRead
SG3 Room Setpoint HC1°CRead
SG3 Hot Water Temperature°CRead
SG3 Hot Water Setpoint°CRead
SG3 Circulation Return Temperature°CRead
SG3 Plate Heat Exchanger Temperature°CRead
SG3 Buffer Tank Top Temperature°CRead
SG3 Buffer Tank Bottom Temperature°CRead
SG3 Heat Demand Heating°CRead
SG3 Heat Demand Hot Water°CRead
SG3 Fault Or Warning PendingRead
SG3 Fault NumberRead
SG3 Fault ModuleRead
SG3 Hot Water StatusRead
SG3 Hot Water PumpRead
SG3 Operating Mode HC1 ActualRead
SG3 Status HC1Read
SG3 Cascade Balancing Temperature°CRead
SG3 Cascade Target Modulation Heating%Read
SG3 Cascade Target Modulation Hot Water%Read
SG3 Cascade System Setpoint Heating°CRead
SG3 Cascade System Setpoint Hot Water°CRead
SG3 Operating Mode HC1 SetpointRead and write
SG3 Summer Winter Switch HC1Read and write
SG3 System Operating ModeRead and write
SG3 Room Setpoint Comfort HC1°CRead and write
SG3 Room Setpoint Normal HC1°CRead and write
SG3 Room Setpoint Setback HC1°CRead and write
SG3 Flow Setpoint Comfort HC1°CRead and write
SG3 Flow Setpoint Normal HC1°CRead and write
SG3 Flow Setpoint Setback HC1°CRead and write
SG3 Flow Setpoint Special Level HC1°CRead and write
SG3 N1 Demand Via Ethernet%Read and write
SG3 Hot Water PushRead and write
SG3 Hot Water Setpoint Normal°CRead and write
SG3 Hot Water Setpoint Setback°CRead and write
SG3 Sequence ChangeRead and write
SG3 Sequence Change TimehRead and write
SG3 CANopen SpecificRead
SG3 Time Of Day Word 1Read
SG3 Time Of Day Word 2Read
SG3 Date Word 1Read
SG3 Date Word 2Read
SG3 Date Word 3Read
SG4 Outdoor Temperature°CRead
SG4 Flow Temperature HC1°CRead
SG4 Flow Setpoint HC1°CRead
SG4 Room Setpoint HC1°CRead
SG4 Hot Water Temperature°CRead
SG4 Hot Water Setpoint°CRead
SG4 Circulation Return Temperature°CRead
SG4 Plate Heat Exchanger Temperature°CRead
SG4 Buffer Tank Top Temperature°CRead
SG4 Buffer Tank Bottom Temperature°CRead
SG4 Heat Demand Heating°CRead
SG4 Heat Demand Hot Water°CRead
SG4 Fault Or Warning PendingRead
SG4 Fault NumberRead
SG4 Fault ModuleRead
SG4 Hot Water StatusRead
SG4 Hot Water PumpRead
SG4 Operating Mode HC1 ActualRead
SG4 Status HC1Read
SG4 Cascade Balancing Temperature°CRead
SG4 Cascade Target Modulation Heating%Read
SG4 Cascade Target Modulation Hot Water%Read
SG4 Cascade System Setpoint Heating°CRead
SG4 Cascade System Setpoint Hot Water°CRead
SG4 Operating Mode HC1 SetpointRead and write
SG4 Summer Winter Switch HC1Read and write
SG4 System Operating ModeRead and write
SG4 Room Setpoint Comfort HC1°CRead and write
SG4 Room Setpoint Normal HC1°CRead and write
SG4 Room Setpoint Setback HC1°CRead and write
SG4 Flow Setpoint Comfort HC1°CRead and write
SG4 Flow Setpoint Normal HC1°CRead and write
SG4 Flow Setpoint Setback HC1°CRead and write
SG4 Flow Setpoint Special Level HC1°CRead and write
SG4 N1 Demand Via Ethernet%Read and write
SG4 Hot Water PushRead and write
SG4 Hot Water Setpoint Normal°CRead and write
SG4 Hot Water Setpoint Setback°CRead and write
SG4 Sequence ChangeRead and write
SG4 Sequence Change TimehRead and write
SG4 CANopen SpecificRead
SG4 Time Of Day Word 1Read
SG4 Time Of Day Word 2Read
SG4 Date Word 1Read
SG4 Date Word 2Read
SG4 Date Word 3Read
SG5 Outdoor Temperature°CRead
SG5 Flow Temperature HC1°CRead
SG5 Flow Setpoint HC1°CRead
SG5 Room Setpoint HC1°CRead
SG5 Hot Water Temperature°CRead
SG5 Hot Water Setpoint°CRead
SG5 Circulation Return Temperature°CRead
SG5 Plate Heat Exchanger Temperature°CRead
SG5 Buffer Tank Top Temperature°CRead
SG5 Buffer Tank Bottom Temperature°CRead
SG5 Heat Demand Heating°CRead
SG5 Heat Demand Hot Water°CRead
SG5 Fault Or Warning PendingRead
SG5 Fault NumberRead
SG5 Fault ModuleRead
SG5 Hot Water StatusRead
SG5 Hot Water PumpRead
SG5 Operating Mode HC1 ActualRead
SG5 Status HC1Read
SG5 Cascade Balancing Temperature°CRead
SG5 Cascade Target Modulation Heating%Read
SG5 Cascade Target Modulation Hot Water%Read
SG5 Cascade System Setpoint Heating°CRead
SG5 Cascade System Setpoint Hot Water°CRead
SG5 Operating Mode HC1 SetpointRead and write
SG5 Summer Winter Switch HC1Read and write
SG5 System Operating ModeRead and write
SG5 Room Setpoint Comfort HC1°CRead and write
SG5 Room Setpoint Normal HC1°CRead and write
SG5 Room Setpoint Setback HC1°CRead and write
SG5 Flow Setpoint Comfort HC1°CRead and write
SG5 Flow Setpoint Normal HC1°CRead and write
SG5 Flow Setpoint Setback HC1°CRead and write
SG5 Flow Setpoint Special Level HC1°CRead and write
SG5 N1 Demand Via Ethernet%Read and write
SG5 Hot Water PushRead and write
SG5 Hot Water Setpoint Normal°CRead and write
SG5 Hot Water Setpoint Setback°CRead and write
SG5 Sequence ChangeRead and write
SG5 Sequence Change TimehRead and write
SG5 CANopen SpecificRead
SG5 Time Of Day Word 1Read
SG5 Time Of Day Word 2Read
SG5 Date Word 1Read
SG5 Date Word 2Read
SG5 Date Word 3Read
SG6 Outdoor Temperature°CRead
SG6 Flow Temperature HC1°CRead
SG6 Flow Setpoint HC1°CRead
SG6 Room Setpoint HC1°CRead
SG6 Hot Water Temperature°CRead
SG6 Hot Water Setpoint°CRead
SG6 Circulation Return Temperature°CRead
SG6 Plate Heat Exchanger Temperature°CRead
SG6 Buffer Tank Top Temperature°CRead
SG6 Buffer Tank Bottom Temperature°CRead
SG6 Heat Demand Heating°CRead
SG6 Heat Demand Hot Water°CRead
SG6 Fault Or Warning PendingRead
SG6 Fault NumberRead
SG6 Fault ModuleRead
SG6 Hot Water StatusRead
SG6 Hot Water PumpRead
SG6 Operating Mode HC1 ActualRead
SG6 Status HC1Read
SG6 Cascade Balancing Temperature°CRead
SG6 Cascade Target Modulation Heating%Read
SG6 Cascade Target Modulation Hot Water%Read
SG6 Cascade System Setpoint Heating°CRead
SG6 Cascade System Setpoint Hot Water°CRead
SG6 Operating Mode HC1 SetpointRead and write
SG6 Summer Winter Switch HC1Read and write
SG6 System Operating ModeRead and write
SG6 Room Setpoint Comfort HC1°CRead and write
SG6 Room Setpoint Normal HC1°CRead and write
SG6 Room Setpoint Setback HC1°CRead and write
SG6 Flow Setpoint Comfort HC1°CRead and write
SG6 Flow Setpoint Normal HC1°CRead and write
SG6 Flow Setpoint Setback HC1°CRead and write
SG6 Flow Setpoint Special Level HC1°CRead and write
SG6 N1 Demand Via Ethernet%Read and write
SG6 Hot Water PushRead and write
SG6 Hot Water Setpoint Normal°CRead and write
SG6 Hot Water Setpoint Setback°CRead and write
SG6 Sequence ChangeRead and write
SG6 Sequence Change TimehRead and write
SG6 CANopen SpecificRead
SG6 Time Of Day Word 1Read
SG6 Time Of Day Word 2Read
SG6 Date Word 1Read
SG6 Date Word 2Read
SG6 Date Word 3Read
SG7 Outdoor Temperature°CRead
SG7 Flow Temperature HC1°CRead
SG7 Flow Setpoint HC1°CRead
SG7 Room Setpoint HC1°CRead
SG7 Hot Water Temperature°CRead
SG7 Hot Water Setpoint°CRead
SG7 Circulation Return Temperature°CRead
SG7 Plate Heat Exchanger Temperature°CRead
SG7 Buffer Tank Top Temperature°CRead
SG7 Buffer Tank Bottom Temperature°CRead
SG7 Heat Demand Heating°CRead
SG7 Heat Demand Hot Water°CRead
SG7 Fault Or Warning PendingRead
SG7 Fault NumberRead
SG7 Fault ModuleRead
SG7 Hot Water StatusRead
SG7 Hot Water PumpRead
SG7 Operating Mode HC1 ActualRead
SG7 Status HC1Read
SG7 Cascade Balancing Temperature°CRead
SG7 Cascade Target Modulation Heating%Read
SG7 Cascade Target Modulation Hot Water%Read
SG7 Cascade System Setpoint Heating°CRead
SG7 Cascade System Setpoint Hot Water°CRead
SG7 Operating Mode HC1 SetpointRead and write
SG7 Summer Winter Switch HC1Read and write
SG7 System Operating ModeRead and write
SG7 Room Setpoint Comfort HC1°CRead and write
SG7 Room Setpoint Normal HC1°CRead and write
SG7 Room Setpoint Setback HC1°CRead and write
SG7 Flow Setpoint Comfort HC1°CRead and write
SG7 Flow Setpoint Normal HC1°CRead and write
SG7 Flow Setpoint Setback HC1°CRead and write
SG7 Flow Setpoint Special Level HC1°CRead and write
SG7 N1 Demand Via Ethernet%Read and write
SG7 Hot Water PushRead and write
SG7 Hot Water Setpoint Normal°CRead and write
SG7 Hot Water Setpoint Setback°CRead and write
SG7 Sequence ChangeRead and write
SG7 Sequence Change TimehRead and write
SG7 CANopen SpecificRead
SG7 Time Of Day Word 1Read
SG7 Time Of Day Word 2Read
SG7 Date Word 1Read
SG7 Date Word 2Read
SG7 Date Word 3Read
SG8 Outdoor Temperature°CRead
SG8 Flow Temperature HC1°CRead
SG8 Flow Setpoint HC1°CRead
SG8 Room Setpoint HC1°CRead
SG8 Hot Water Temperature°CRead
SG8 Hot Water Setpoint°CRead
SG8 Circulation Return Temperature°CRead
SG8 Plate Heat Exchanger Temperature°CRead
SG8 Buffer Tank Top Temperature°CRead
SG8 Buffer Tank Bottom Temperature°CRead
SG8 Heat Demand Heating°CRead
SG8 Heat Demand Hot Water°CRead
SG8 Fault Or Warning PendingRead
SG8 Fault NumberRead
SG8 Fault ModuleRead
SG8 Hot Water StatusRead
SG8 Hot Water PumpRead
SG8 Operating Mode HC1 ActualRead
SG8 Status HC1Read
SG8 Cascade Balancing Temperature°CRead
SG8 Cascade Target Modulation Heating%Read
SG8 Cascade Target Modulation Hot Water%Read
SG8 Cascade System Setpoint Heating°CRead
SG8 Cascade System Setpoint Hot Water°CRead
SG8 Operating Mode HC1 SetpointRead and write
SG8 Summer Winter Switch HC1Read and write
SG8 System Operating ModeRead and write
SG8 Room Setpoint Comfort HC1°CRead and write
SG8 Room Setpoint Normal HC1°CRead and write
SG8 Room Setpoint Setback HC1°CRead and write
SG8 Flow Setpoint Comfort HC1°CRead and write
SG8 Flow Setpoint Normal HC1°CRead and write
SG8 Flow Setpoint Setback HC1°CRead and write
SG8 Flow Setpoint Special Level HC1°CRead and write
SG8 N1 Demand Via Ethernet%Read and write
SG8 Hot Water PushRead and write
SG8 Hot Water Setpoint Normal°CRead and write
SG8 Hot Water Setpoint Setback°CRead and write
SG8 Sequence ChangeRead and write
SG8 Sequence Change TimehRead and write
SG8 CANopen SpecificRead
SG8 Time Of Day Word 1Read
SG8 Time Of Day Word 2Read
SG8 Date Word 1Read
SG8 Date Word 2Read
SG8 Date Word 3Read
Cascade Sensor T1°CRead
Cascade Sensor T2°CRead
Cascade Pump PWM%Read
Collector Temperature°CRead
Solar Tank Bottom Temperature°CRead
Solar Yield TotalkWhRead
Solar Yield TodaykWhRead
Solar Yield YesterdaykWhRead
Gateway WEM ConnectionRead
Gateway Firmware VersionRead
Detected WTC And ModulesRead
Detected EM-HKRead
Detected EM-WWRead
Detected RG1Read
Detected RG2Read
Detected RFRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Watch boiler temperature, heat output and burner phase of every WTC in a cascade on one dashboard.
  • Get an alert when the fault register reports an active fault or when system pressure drops.
  • Compare daily heat quantities for heating and hot water over the season.
  • Switch the system to summer or standby mode remotely when a building is empty.
  • Adjust the room or flow setpoint of heating circuit 1 after a comfort complaint.

Installation

  1. Connect the WEM-Modbus gateway to the WEM system device and to the network, and give it a fixed IP address.

  2. In the gateway web frontend, run the automatic WEM device search and enable the registers you want to convert.

  3. Connect the ModbusCloud Gateway to the same network so it can reach the gateway on port 502.

  4. In ModbusCloud, add a Modbus TCP device with the gateway IP address, port 502, and import this template.

  5. Check that outdoor temperature and WTC1 boiler temperature show realistic values; disabled registers return no data.

Things to watch for

Some registers return no value at all. Why?

The gateway only serves registers that are enabled for data conversion in its web frontend, and only for WEM devices found by the automatic device search. Run the search again after replacing a module, then enable the missing registers.

Values change slowly or seem old. Is that normal?

The gateway reads the WEM system at its own update rates (short, medium or long per value, up to 10 minutes) and stores the result. A Modbus read returns the stored value, so faster polling does not give newer data.

How do I write a setpoint correctly?

Use the registers marked writable, such as operating mode, room, flow and hot water setpoints. Temperatures are written in 0.1 °C, so 21.5 °C is 215. The gateway passes the value to the WEM system only when it differs from the stored one, and setpoints follow the steps of 0.5 K or 1 K.

Where are the heating circuit modules and room units?

EM-HK, EM-WW and room unit registers share one numbering range in the order the devices are found, so their meaning depends on the installation. They are not in this template; check the device table in the gateway web frontend for their addresses.