Weishaupt WEM-Modbus Gateway
Gateway for Weishaupt WTC condensing boilers with boiler temperatures, heat output and heating setpoints.
The Weishaupt WEM-Modbus gateway is a protocol converter that makes WTC gas condensing boilers and the WEM system device readable over Modbus TCP in homes and commercial buildings. This Modbus TCP template reads boiler and flow temperatures, heat output, pressure and faults, and lets you write operating modes and setpoints from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 464, read and write
- Brand
- Weishaupt
- Key readings
- Boiler temperature · Heat output · Flow temperature · Outdoor temperature · Hot water temperature · System pressure · Fault number
- Available commands
- Operating mode · Room setpoints · Flow setpoints · Hot water setpoints · Hot water push
- Compatible models
- Gateway WEM-Modbus · Weishaupt WTC gas condensing boiler via WEM-SG system device
- Last updated
Registers (464)
464 read, 128 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| WTC1 Boiler Temperature | °C | Read | 164 | FC03 | int16 |
| WTC1 Flow Setpoint | °C | Read | 163 | FC03 | int16 |
| WTC1 Heat Output | kW | Read | 170 | FC03 | uint32 |
| WTC1 Flow Rate | l/h | Read | 165 | FC03 | uint16 |
| WTC1 System Pressure | bar | Read | 166 | FC03 | uint16 |
| WTC1 Operating Phase | Read | ||||
| WTC1 Burner Phase | Read | ||||
| WTC1 Heat Yesterday Total | kWh | Read | |||
| WTC1 Heat Yesterday Heating | kWh | Read | |||
| WTC1 Heat Yesterday Hot Water | kWh | Read | |||
| WTC2 Boiler Temperature | °C | Read | |||
| WTC2 Flow Setpoint | °C | Read | |||
| WTC2 Heat Output | kW | Read | |||
| WTC2 Flow Rate | l/h | Read | |||
| WTC2 System Pressure | bar | Read | |||
| WTC2 Operating Phase | Read | ||||
| WTC2 Burner Phase | Read | ||||
| WTC2 Heat Yesterday Total | kWh | Read | |||
| WTC2 Heat Yesterday Heating | kWh | Read | |||
| WTC2 Heat Yesterday Hot Water | kWh | Read | |||
| WTC3 Boiler Temperature | °C | Read | |||
| WTC3 Flow Setpoint | °C | Read | |||
| WTC3 Heat Output | kW | Read | |||
| WTC3 Flow Rate | l/h | Read | |||
| WTC3 System Pressure | bar | Read | |||
| WTC3 Operating Phase | Read | ||||
| WTC3 Burner Phase | Read | ||||
| WTC3 Heat Yesterday Total | kWh | Read | |||
| WTC3 Heat Yesterday Heating | kWh | Read | |||
| WTC3 Heat Yesterday Hot Water | kWh | Read | |||
| WTC4 Boiler Temperature | °C | Read | |||
| WTC4 Flow Setpoint | °C | Read | |||
| WTC4 Heat Output | kW | Read | |||
| WTC4 Flow Rate | l/h | Read | |||
| WTC4 System Pressure | bar | Read | |||
| WTC4 Operating Phase | Read | ||||
| WTC4 Burner Phase | Read | ||||
| WTC4 Heat Yesterday Total | kWh | Read | |||
| WTC4 Heat Yesterday Heating | kWh | Read | |||
| WTC4 Heat Yesterday Hot Water | kWh | Read | |||
| WTC5 Boiler Temperature | °C | Read | |||
| WTC5 Flow Setpoint | °C | Read | |||
| WTC5 Heat Output | kW | Read | |||
| WTC5 Flow Rate | l/h | Read | |||
| WTC5 System Pressure | bar | Read | |||
| WTC5 Operating Phase | Read | ||||
| WTC5 Burner Phase | Read | ||||
| WTC5 Heat Yesterday Total | kWh | Read | |||
| WTC5 Heat Yesterday Heating | kWh | Read | |||
| WTC5 Heat Yesterday Hot Water | kWh | Read | |||
| WTC6 Boiler Temperature | °C | Read | |||
| WTC6 Flow Setpoint | °C | Read | |||
| WTC6 Heat Output | kW | Read | |||
| WTC6 Flow Rate | l/h | Read | |||
| WTC6 System Pressure | bar | Read | |||
| WTC6 Operating Phase | Read | ||||
| WTC6 Burner Phase | Read | ||||
| WTC6 Heat Yesterday Total | kWh | Read | |||
| WTC6 Heat Yesterday Heating | kWh | Read | |||
| WTC6 Heat Yesterday Hot Water | kWh | Read | |||
| WTC7 Boiler Temperature | °C | Read | |||
| WTC7 Flow Setpoint | °C | Read | |||
| WTC7 Heat Output | kW | Read | |||
| WTC7 Flow Rate | l/h | Read | |||
| WTC7 System Pressure | bar | Read | |||
| WTC7 Operating Phase | Read | ||||
| WTC7 Burner Phase | Read | ||||
| WTC7 Heat Yesterday Total | kWh | Read | |||
| WTC7 Heat Yesterday Heating | kWh | Read | |||
| WTC7 Heat Yesterday Hot Water | kWh | Read | |||
| WTC8 Boiler Temperature | °C | Read | |||
| WTC8 Flow Setpoint | °C | Read | |||
| WTC8 Heat Output | kW | Read | |||
| WTC8 Flow Rate | l/h | Read | |||
| WTC8 System Pressure | bar | Read | |||
| WTC8 Operating Phase | Read | ||||
| WTC8 Burner Phase | Read | ||||
| WTC8 Heat Yesterday Total | kWh | Read | |||
| WTC8 Heat Yesterday Heating | kWh | Read | |||
| WTC8 Heat Yesterday Hot Water | kWh | Read | |||
| Outdoor Temperature | °C | Read | |||
| Flow Temperature HC1 | °C | Read | |||
| Flow Setpoint HC1 | °C | Read | |||
| Room Setpoint HC1 | °C | Read | |||
| Hot Water Temperature | °C | Read | |||
| Hot Water Setpoint | °C | Read | |||
| Circulation Return Temperature | °C | Read | |||
| Plate Heat Exchanger Temperature | °C | Read | |||
| Buffer Tank Top Temperature | °C | Read | |||
| Buffer Tank Bottom Temperature | °C | Read | |||
| Heat Demand Heating | °C | Read | |||
| Heat Demand Hot Water | °C | Read | |||
| Fault Or Warning Pending | Read | ||||
| Fault Number | Read | ||||
| Fault Module | Read | ||||
| Hot Water Status | Read | ||||
| Hot Water Pump | Read | ||||
| Operating Mode HC1 Actual | Read | ||||
| Status HC1 | Read | ||||
| Cascade Balancing Temperature | °C | Read | |||
| Cascade Target Modulation Heating | % | Read | |||
| Cascade Target Modulation Hot Water | % | Read | |||
| Cascade System Setpoint Heating | °C | Read | |||
| Cascade System Setpoint Hot Water | °C | Read | |||
| Operating Mode HC1 Setpoint | Read and write | ||||
| Summer Winter Switch HC1 | Read and write | ||||
| System Operating Mode | Read and write | ||||
| Room Setpoint Comfort HC1 | °C | Read and write | |||
| Room Setpoint Normal HC1 | °C | Read and write | |||
| Room Setpoint Setback HC1 | °C | Read and write | |||
| Flow Setpoint Comfort HC1 | °C | Read and write | |||
| Flow Setpoint Normal HC1 | °C | Read and write | |||
| Flow Setpoint Setback HC1 | °C | Read and write | |||
| Flow Setpoint Special Level HC1 | °C | Read and write | |||
| N1 Demand Via Ethernet | % | Read and write | |||
| Hot Water Push | Read and write | ||||
| Hot Water Setpoint Normal | °C | Read and write | |||
| Hot Water Setpoint Setback | °C | Read and write | |||
| Sequence Change | Read and write | ||||
| Sequence Change Time | h | Read and write | |||
| CANopen Specific | Read | ||||
| Time Of Day Word 1 | Read | ||||
| Time Of Day Word 2 | Read | ||||
| Date Word 1 | Read | ||||
| Date Word 2 | Read | ||||
| Date Word 3 | Read | ||||
| SG2 Outdoor Temperature | °C | Read | |||
| SG2 Flow Temperature HC1 | °C | Read | |||
| SG2 Flow Setpoint HC1 | °C | Read | |||
| SG2 Room Setpoint HC1 | °C | Read | |||
| SG2 Hot Water Temperature | °C | Read | |||
| SG2 Hot Water Setpoint | °C | Read | |||
| SG2 Circulation Return Temperature | °C | Read | |||
| SG2 Plate Heat Exchanger Temperature | °C | Read | |||
| SG2 Buffer Tank Top Temperature | °C | Read | |||
| SG2 Buffer Tank Bottom Temperature | °C | Read | |||
| SG2 Heat Demand Heating | °C | Read | |||
| SG2 Heat Demand Hot Water | °C | Read | |||
| SG2 Fault Or Warning Pending | Read | ||||
| SG2 Fault Number | Read | ||||
| SG2 Fault Module | Read | ||||
| SG2 Hot Water Status | Read | ||||
| SG2 Hot Water Pump | Read | ||||
| SG2 Operating Mode HC1 Actual | Read | ||||
| SG2 Status HC1 | Read | ||||
| SG2 Cascade Balancing Temperature | °C | Read | |||
| SG2 Cascade Target Modulation Heating | % | Read | |||
| SG2 Cascade Target Modulation Hot Water | % | Read | |||
| SG2 Cascade System Setpoint Heating | °C | Read | |||
| SG2 Cascade System Setpoint Hot Water | °C | Read | |||
| SG2 Operating Mode HC1 Setpoint | Read and write | ||||
| SG2 Summer Winter Switch HC1 | Read and write | ||||
| SG2 System Operating Mode | Read and write | ||||
| SG2 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG2 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG2 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG2 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG2 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG2 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG2 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG2 N1 Demand Via Ethernet | % | Read and write | |||
| SG2 Hot Water Push | Read and write | ||||
| SG2 Hot Water Setpoint Normal | °C | Read and write | |||
| SG2 Hot Water Setpoint Setback | °C | Read and write | |||
| SG2 Sequence Change | Read and write | ||||
| SG2 Sequence Change Time | h | Read and write | |||
| SG2 CANopen Specific | Read | ||||
| SG2 Time Of Day Word 1 | Read | ||||
| SG2 Time Of Day Word 2 | Read | ||||
| SG2 Date Word 1 | Read | ||||
| SG2 Date Word 2 | Read | ||||
| SG2 Date Word 3 | Read | ||||
| SG3 Outdoor Temperature | °C | Read | |||
| SG3 Flow Temperature HC1 | °C | Read | |||
| SG3 Flow Setpoint HC1 | °C | Read | |||
| SG3 Room Setpoint HC1 | °C | Read | |||
| SG3 Hot Water Temperature | °C | Read | |||
| SG3 Hot Water Setpoint | °C | Read | |||
| SG3 Circulation Return Temperature | °C | Read | |||
| SG3 Plate Heat Exchanger Temperature | °C | Read | |||
| SG3 Buffer Tank Top Temperature | °C | Read | |||
| SG3 Buffer Tank Bottom Temperature | °C | Read | |||
| SG3 Heat Demand Heating | °C | Read | |||
| SG3 Heat Demand Hot Water | °C | Read | |||
| SG3 Fault Or Warning Pending | Read | ||||
| SG3 Fault Number | Read | ||||
| SG3 Fault Module | Read | ||||
| SG3 Hot Water Status | Read | ||||
| SG3 Hot Water Pump | Read | ||||
| SG3 Operating Mode HC1 Actual | Read | ||||
| SG3 Status HC1 | Read | ||||
| SG3 Cascade Balancing Temperature | °C | Read | |||
| SG3 Cascade Target Modulation Heating | % | Read | |||
| SG3 Cascade Target Modulation Hot Water | % | Read | |||
| SG3 Cascade System Setpoint Heating | °C | Read | |||
| SG3 Cascade System Setpoint Hot Water | °C | Read | |||
| SG3 Operating Mode HC1 Setpoint | Read and write | ||||
| SG3 Summer Winter Switch HC1 | Read and write | ||||
| SG3 System Operating Mode | Read and write | ||||
| SG3 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG3 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG3 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG3 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG3 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG3 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG3 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG3 N1 Demand Via Ethernet | % | Read and write | |||
| SG3 Hot Water Push | Read and write | ||||
| SG3 Hot Water Setpoint Normal | °C | Read and write | |||
| SG3 Hot Water Setpoint Setback | °C | Read and write | |||
| SG3 Sequence Change | Read and write | ||||
| SG3 Sequence Change Time | h | Read and write | |||
| SG3 CANopen Specific | Read | ||||
| SG3 Time Of Day Word 1 | Read | ||||
| SG3 Time Of Day Word 2 | Read | ||||
| SG3 Date Word 1 | Read | ||||
| SG3 Date Word 2 | Read | ||||
| SG3 Date Word 3 | Read | ||||
| SG4 Outdoor Temperature | °C | Read | |||
| SG4 Flow Temperature HC1 | °C | Read | |||
| SG4 Flow Setpoint HC1 | °C | Read | |||
| SG4 Room Setpoint HC1 | °C | Read | |||
| SG4 Hot Water Temperature | °C | Read | |||
| SG4 Hot Water Setpoint | °C | Read | |||
| SG4 Circulation Return Temperature | °C | Read | |||
| SG4 Plate Heat Exchanger Temperature | °C | Read | |||
| SG4 Buffer Tank Top Temperature | °C | Read | |||
| SG4 Buffer Tank Bottom Temperature | °C | Read | |||
| SG4 Heat Demand Heating | °C | Read | |||
| SG4 Heat Demand Hot Water | °C | Read | |||
| SG4 Fault Or Warning Pending | Read | ||||
| SG4 Fault Number | Read | ||||
| SG4 Fault Module | Read | ||||
| SG4 Hot Water Status | Read | ||||
| SG4 Hot Water Pump | Read | ||||
| SG4 Operating Mode HC1 Actual | Read | ||||
| SG4 Status HC1 | Read | ||||
| SG4 Cascade Balancing Temperature | °C | Read | |||
| SG4 Cascade Target Modulation Heating | % | Read | |||
| SG4 Cascade Target Modulation Hot Water | % | Read | |||
| SG4 Cascade System Setpoint Heating | °C | Read | |||
| SG4 Cascade System Setpoint Hot Water | °C | Read | |||
| SG4 Operating Mode HC1 Setpoint | Read and write | ||||
| SG4 Summer Winter Switch HC1 | Read and write | ||||
| SG4 System Operating Mode | Read and write | ||||
| SG4 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG4 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG4 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG4 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG4 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG4 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG4 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG4 N1 Demand Via Ethernet | % | Read and write | |||
| SG4 Hot Water Push | Read and write | ||||
| SG4 Hot Water Setpoint Normal | °C | Read and write | |||
| SG4 Hot Water Setpoint Setback | °C | Read and write | |||
| SG4 Sequence Change | Read and write | ||||
| SG4 Sequence Change Time | h | Read and write | |||
| SG4 CANopen Specific | Read | ||||
| SG4 Time Of Day Word 1 | Read | ||||
| SG4 Time Of Day Word 2 | Read | ||||
| SG4 Date Word 1 | Read | ||||
| SG4 Date Word 2 | Read | ||||
| SG4 Date Word 3 | Read | ||||
| SG5 Outdoor Temperature | °C | Read | |||
| SG5 Flow Temperature HC1 | °C | Read | |||
| SG5 Flow Setpoint HC1 | °C | Read | |||
| SG5 Room Setpoint HC1 | °C | Read | |||
| SG5 Hot Water Temperature | °C | Read | |||
| SG5 Hot Water Setpoint | °C | Read | |||
| SG5 Circulation Return Temperature | °C | Read | |||
| SG5 Plate Heat Exchanger Temperature | °C | Read | |||
| SG5 Buffer Tank Top Temperature | °C | Read | |||
| SG5 Buffer Tank Bottom Temperature | °C | Read | |||
| SG5 Heat Demand Heating | °C | Read | |||
| SG5 Heat Demand Hot Water | °C | Read | |||
| SG5 Fault Or Warning Pending | Read | ||||
| SG5 Fault Number | Read | ||||
| SG5 Fault Module | Read | ||||
| SG5 Hot Water Status | Read | ||||
| SG5 Hot Water Pump | Read | ||||
| SG5 Operating Mode HC1 Actual | Read | ||||
| SG5 Status HC1 | Read | ||||
| SG5 Cascade Balancing Temperature | °C | Read | |||
| SG5 Cascade Target Modulation Heating | % | Read | |||
| SG5 Cascade Target Modulation Hot Water | % | Read | |||
| SG5 Cascade System Setpoint Heating | °C | Read | |||
| SG5 Cascade System Setpoint Hot Water | °C | Read | |||
| SG5 Operating Mode HC1 Setpoint | Read and write | ||||
| SG5 Summer Winter Switch HC1 | Read and write | ||||
| SG5 System Operating Mode | Read and write | ||||
| SG5 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG5 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG5 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG5 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG5 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG5 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG5 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG5 N1 Demand Via Ethernet | % | Read and write | |||
| SG5 Hot Water Push | Read and write | ||||
| SG5 Hot Water Setpoint Normal | °C | Read and write | |||
| SG5 Hot Water Setpoint Setback | °C | Read and write | |||
| SG5 Sequence Change | Read and write | ||||
| SG5 Sequence Change Time | h | Read and write | |||
| SG5 CANopen Specific | Read | ||||
| SG5 Time Of Day Word 1 | Read | ||||
| SG5 Time Of Day Word 2 | Read | ||||
| SG5 Date Word 1 | Read | ||||
| SG5 Date Word 2 | Read | ||||
| SG5 Date Word 3 | Read | ||||
| SG6 Outdoor Temperature | °C | Read | |||
| SG6 Flow Temperature HC1 | °C | Read | |||
| SG6 Flow Setpoint HC1 | °C | Read | |||
| SG6 Room Setpoint HC1 | °C | Read | |||
| SG6 Hot Water Temperature | °C | Read | |||
| SG6 Hot Water Setpoint | °C | Read | |||
| SG6 Circulation Return Temperature | °C | Read | |||
| SG6 Plate Heat Exchanger Temperature | °C | Read | |||
| SG6 Buffer Tank Top Temperature | °C | Read | |||
| SG6 Buffer Tank Bottom Temperature | °C | Read | |||
| SG6 Heat Demand Heating | °C | Read | |||
| SG6 Heat Demand Hot Water | °C | Read | |||
| SG6 Fault Or Warning Pending | Read | ||||
| SG6 Fault Number | Read | ||||
| SG6 Fault Module | Read | ||||
| SG6 Hot Water Status | Read | ||||
| SG6 Hot Water Pump | Read | ||||
| SG6 Operating Mode HC1 Actual | Read | ||||
| SG6 Status HC1 | Read | ||||
| SG6 Cascade Balancing Temperature | °C | Read | |||
| SG6 Cascade Target Modulation Heating | % | Read | |||
| SG6 Cascade Target Modulation Hot Water | % | Read | |||
| SG6 Cascade System Setpoint Heating | °C | Read | |||
| SG6 Cascade System Setpoint Hot Water | °C | Read | |||
| SG6 Operating Mode HC1 Setpoint | Read and write | ||||
| SG6 Summer Winter Switch HC1 | Read and write | ||||
| SG6 System Operating Mode | Read and write | ||||
| SG6 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG6 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG6 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG6 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG6 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG6 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG6 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG6 N1 Demand Via Ethernet | % | Read and write | |||
| SG6 Hot Water Push | Read and write | ||||
| SG6 Hot Water Setpoint Normal | °C | Read and write | |||
| SG6 Hot Water Setpoint Setback | °C | Read and write | |||
| SG6 Sequence Change | Read and write | ||||
| SG6 Sequence Change Time | h | Read and write | |||
| SG6 CANopen Specific | Read | ||||
| SG6 Time Of Day Word 1 | Read | ||||
| SG6 Time Of Day Word 2 | Read | ||||
| SG6 Date Word 1 | Read | ||||
| SG6 Date Word 2 | Read | ||||
| SG6 Date Word 3 | Read | ||||
| SG7 Outdoor Temperature | °C | Read | |||
| SG7 Flow Temperature HC1 | °C | Read | |||
| SG7 Flow Setpoint HC1 | °C | Read | |||
| SG7 Room Setpoint HC1 | °C | Read | |||
| SG7 Hot Water Temperature | °C | Read | |||
| SG7 Hot Water Setpoint | °C | Read | |||
| SG7 Circulation Return Temperature | °C | Read | |||
| SG7 Plate Heat Exchanger Temperature | °C | Read | |||
| SG7 Buffer Tank Top Temperature | °C | Read | |||
| SG7 Buffer Tank Bottom Temperature | °C | Read | |||
| SG7 Heat Demand Heating | °C | Read | |||
| SG7 Heat Demand Hot Water | °C | Read | |||
| SG7 Fault Or Warning Pending | Read | ||||
| SG7 Fault Number | Read | ||||
| SG7 Fault Module | Read | ||||
| SG7 Hot Water Status | Read | ||||
| SG7 Hot Water Pump | Read | ||||
| SG7 Operating Mode HC1 Actual | Read | ||||
| SG7 Status HC1 | Read | ||||
| SG7 Cascade Balancing Temperature | °C | Read | |||
| SG7 Cascade Target Modulation Heating | % | Read | |||
| SG7 Cascade Target Modulation Hot Water | % | Read | |||
| SG7 Cascade System Setpoint Heating | °C | Read | |||
| SG7 Cascade System Setpoint Hot Water | °C | Read | |||
| SG7 Operating Mode HC1 Setpoint | Read and write | ||||
| SG7 Summer Winter Switch HC1 | Read and write | ||||
| SG7 System Operating Mode | Read and write | ||||
| SG7 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG7 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG7 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG7 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG7 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG7 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG7 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG7 N1 Demand Via Ethernet | % | Read and write | |||
| SG7 Hot Water Push | Read and write | ||||
| SG7 Hot Water Setpoint Normal | °C | Read and write | |||
| SG7 Hot Water Setpoint Setback | °C | Read and write | |||
| SG7 Sequence Change | Read and write | ||||
| SG7 Sequence Change Time | h | Read and write | |||
| SG7 CANopen Specific | Read | ||||
| SG7 Time Of Day Word 1 | Read | ||||
| SG7 Time Of Day Word 2 | Read | ||||
| SG7 Date Word 1 | Read | ||||
| SG7 Date Word 2 | Read | ||||
| SG7 Date Word 3 | Read | ||||
| SG8 Outdoor Temperature | °C | Read | |||
| SG8 Flow Temperature HC1 | °C | Read | |||
| SG8 Flow Setpoint HC1 | °C | Read | |||
| SG8 Room Setpoint HC1 | °C | Read | |||
| SG8 Hot Water Temperature | °C | Read | |||
| SG8 Hot Water Setpoint | °C | Read | |||
| SG8 Circulation Return Temperature | °C | Read | |||
| SG8 Plate Heat Exchanger Temperature | °C | Read | |||
| SG8 Buffer Tank Top Temperature | °C | Read | |||
| SG8 Buffer Tank Bottom Temperature | °C | Read | |||
| SG8 Heat Demand Heating | °C | Read | |||
| SG8 Heat Demand Hot Water | °C | Read | |||
| SG8 Fault Or Warning Pending | Read | ||||
| SG8 Fault Number | Read | ||||
| SG8 Fault Module | Read | ||||
| SG8 Hot Water Status | Read | ||||
| SG8 Hot Water Pump | Read | ||||
| SG8 Operating Mode HC1 Actual | Read | ||||
| SG8 Status HC1 | Read | ||||
| SG8 Cascade Balancing Temperature | °C | Read | |||
| SG8 Cascade Target Modulation Heating | % | Read | |||
| SG8 Cascade Target Modulation Hot Water | % | Read | |||
| SG8 Cascade System Setpoint Heating | °C | Read | |||
| SG8 Cascade System Setpoint Hot Water | °C | Read | |||
| SG8 Operating Mode HC1 Setpoint | Read and write | ||||
| SG8 Summer Winter Switch HC1 | Read and write | ||||
| SG8 System Operating Mode | Read and write | ||||
| SG8 Room Setpoint Comfort HC1 | °C | Read and write | |||
| SG8 Room Setpoint Normal HC1 | °C | Read and write | |||
| SG8 Room Setpoint Setback HC1 | °C | Read and write | |||
| SG8 Flow Setpoint Comfort HC1 | °C | Read and write | |||
| SG8 Flow Setpoint Normal HC1 | °C | Read and write | |||
| SG8 Flow Setpoint Setback HC1 | °C | Read and write | |||
| SG8 Flow Setpoint Special Level HC1 | °C | Read and write | |||
| SG8 N1 Demand Via Ethernet | % | Read and write | |||
| SG8 Hot Water Push | Read and write | ||||
| SG8 Hot Water Setpoint Normal | °C | Read and write | |||
| SG8 Hot Water Setpoint Setback | °C | Read and write | |||
| SG8 Sequence Change | Read and write | ||||
| SG8 Sequence Change Time | h | Read and write | |||
| SG8 CANopen Specific | Read | ||||
| SG8 Time Of Day Word 1 | Read | ||||
| SG8 Time Of Day Word 2 | Read | ||||
| SG8 Date Word 1 | Read | ||||
| SG8 Date Word 2 | Read | ||||
| SG8 Date Word 3 | Read | ||||
| Cascade Sensor T1 | °C | Read | |||
| Cascade Sensor T2 | °C | Read | |||
| Cascade Pump PWM | % | Read | |||
| Collector Temperature | °C | Read | |||
| Solar Tank Bottom Temperature | °C | Read | |||
| Solar Yield Total | kWh | Read | |||
| Solar Yield Today | kWh | Read | |||
| Solar Yield Yesterday | kWh | Read | |||
| Gateway WEM Connection | Read | ||||
| Gateway Firmware Version | Read | ||||
| Detected WTC And Modules | Read | ||||
| Detected EM-HK | Read | ||||
| Detected EM-WW | Read | ||||
| Detected RG1 | Read | ||||
| Detected RG2 | Read | ||||
| Detected RF | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Watch boiler temperature, heat output and burner phase of every WTC in a cascade on one dashboard.
- Get an alert when the fault register reports an active fault or when system pressure drops.
- Compare daily heat quantities for heating and hot water over the season.
- Switch the system to summer or standby mode remotely when a building is empty.
- Adjust the room or flow setpoint of heating circuit 1 after a comfort complaint.
Installation
Connect the WEM-Modbus gateway to the WEM system device and to the network, and give it a fixed IP address.
In the gateway web frontend, run the automatic WEM device search and enable the registers you want to convert.
Connect the ModbusCloud Gateway to the same network so it can reach the gateway on port 502.
In ModbusCloud, add a Modbus TCP device with the gateway IP address, port 502, and import this template.
Check that outdoor temperature and WTC1 boiler temperature show realistic values; disabled registers return no data.
Things to watch for
Some registers return no value at all. Why?
The gateway only serves registers that are enabled for data conversion in its web frontend, and only for WEM devices found by the automatic device search. Run the search again after replacing a module, then enable the missing registers.
Values change slowly or seem old. Is that normal?
The gateway reads the WEM system at its own update rates (short, medium or long per value, up to 10 minutes) and stores the result. A Modbus read returns the stored value, so faster polling does not give newer data.
How do I write a setpoint correctly?
Use the registers marked writable, such as operating mode, room, flow and hot water setpoints. Temperatures are written in 0.1 °C, so 21.5 °C is 215. The gateway passes the value to the WEM system only when it differs from the stored one, and setpoints follow the steps of 0.5 K or 1 K.
Where are the heating circuit modules and room units?
EM-HK, EM-WW and room unit registers share one numbering range in the order the devices are found, so their meaning depends on the installation. They are not in this template; check the device table in the gateway web frontend for their addresses.
More Weishaupt templates
Want to see how it works?