Accuenergy Accuenergy Acuvim II Max/Min Logs Modbus RTU template

Accuenergy Acuvim II Max/Min Logs

Recorded maximum and minimum values of an Acuvim II power meter, each with date and time.

The Accuenergy Acuvim II is a panel-mounted power meter that records the highest and lowest values of voltage, current, power and power quality in low-voltage switchboards. This Modbus RTU template reads those maximum and minimum values, each with the date and time it occurred, into ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
1302, read only
Key readings
Maximum phase voltage · Minimum phase voltage · Maximum phase current · Peak power demand · Maximum THD · Time of each extreme value
Compatible models
Acuvim II · Acuvim IIR · Acuvim IIE · Acuvim IIW
Last updated

Registers (1302)

1302 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Va Max IntVRead16694FC03int16
Va Max Int YearRead16695FC03uint16
Va Max Int MonthRead16696FC03uint16
Va Max Int DayRead16697FC03uint16
Va Max Int HourRead16698FC03uint16
Va Max Int MinuteRead
Va Max Int SecondRead
Vb Max IntVRead
Vb Max Int YearRead
Vb Max Int MonthRead
Vb Max Int DayRead
Vb Max Int HourRead
Vb Max Int MinuteRead
Vb Max Int SecondRead
V3 Max IntVRead
V3 Max Int YearRead
V3 Max Int MonthRead
V3 Max Int DayRead
V3 Max Int HourRead
V3 Max Int MinuteRead
V3 Max Int SecondRead
Vab Max IntVRead
Vab Max Int YearRead
Vab Max Int MonthRead
Vab Max Int DayRead
Vab Max Int HourRead
Vab Max Int MinuteRead
Vab Max Int SecondRead
Vbc Max IntVRead
Vbc Max Int YearRead
Vbc Max Int MonthRead
Vbc Max Int DayRead
Vbc Max Int HourRead
Vbc Max Int MinuteRead
Vbc Max Int SecondRead
Vca Max IntVRead
Vca Max Int YearRead
Vca Max Int MonthRead
Vca Max Int DayRead
Vca Max Int HourRead
Vca Max Int MinuteRead
Vca Max Int SecondRead
Ia Max IntARead
Ia Max Int YearRead
Ia Max Int MonthRead
Ia Max Int DayRead
Ia Max Int HourRead
Ia Max Int MinuteRead
Ia Max Int SecondRead
Ib Max IntARead
Ib Max Int YearRead
Ib Max Int MonthRead
Ib Max Int DayRead
Ib Max Int HourRead
Ib Max Int MinuteRead
Ib Max Int SecondRead
Ic Max IntARead
Ic Max Int YearRead
Ic Max Int MonthRead
Ic Max Int DayRead
Ic Max Int HourRead
Ic Max Int MinuteRead
Ic Max Int SecondRead
Total Power Max IntkWRead
Total Power Max Int YearRead
Total Power Max Int MonthRead
Total Power Max Int DayRead
Total Power Max Int HourRead
Total Power Max Int MinuteRead
Total Power Max Int SecondRead
Total Reactive Power Max IntkvarRead
Total Reactive Power Max Int YearRead
Total Reactive Power Max Int MonthRead
Total Reactive Power Max Int DayRead
Total Reactive Power Max Int HourRead
Total Reactive Power Max Int MinuteRead
Total Reactive Power Max Int SecondRead
Total Apparent Power Max IntkVARead
Total Apparent Power Max Int YearRead
Total Apparent Power Max Int MonthRead
Total Apparent Power Max Int DayRead
Total Apparent Power Max Int HourRead
Total Apparent Power Max Int MinuteRead
Total Apparent Power Max Int SecondRead
Power Factor Max IntRead
Power Factor Max Int YearRead
Power Factor Max Int MonthRead
Power Factor Max Int DayRead
Power Factor Max Int HourRead
Power Factor Max Int MinuteRead
Power Factor Max Int SecondRead
Frequency Max IntHzRead
Frequency Max Int YearRead
Frequency Max Int MonthRead
Frequency Max Int DayRead
Frequency Max Int HourRead
Frequency Max Int MinuteRead
Frequency Max Int SecondRead
Power Demand Max IntkWRead
Power Demand Max Int YearRead
Power Demand Max Int MonthRead
Power Demand Max Int DayRead
Power Demand Max Int HourRead
Power Demand Max Int MinuteRead
Power Demand Max Int SecondRead
Reactive Power Demand Max IntkvarRead
Reactive Power Demand Max Int YearRead
Reactive Power Demand Max Int MonthRead
Reactive Power Demand Max Int DayRead
Reactive Power Demand Max Int HourRead
Reactive Power Demand Max Int MinuteRead
Reactive Power Demand Max Int SecondRead
Apparent Demand Max IntkVARead
Apparent Demand Max Int YearRead
Apparent Demand Max Int MonthRead
Apparent Demand Max Int DayRead
Apparent Demand Max Int HourRead
Apparent Demand Max Int MinuteRead
Apparent Demand Max Int SecondRead
Phase A Current Demand Max IntARead
Phase A Current Demand Max Int YearRead
Phase A Current Demand Max Int MonthRead
Phase A Current Demand Max Int DayRead
Phase A Current Demand Max Int HourRead
Phase A Current Demand Max Int MinuteRead
Phase A Current Demand Max Int SecondRead
Phase B Current Demand Max IntARead
Phase B Current Demand Max Int YearRead
Phase B Current Demand Max Int MonthRead
Phase B Current Demand Max Int DayRead
Phase B Current Demand Max Int HourRead
Phase B Current Demand Max Int MinuteRead
Phase B Current Demand Max Int SecondRead
Phase C Current Demand Max IntARead
Phase C Current Demand Max Int YearRead
Phase C Current Demand Max Int MonthRead
Phase C Current Demand Max Int DayRead
Phase C Current Demand Max Int HourRead
Phase C Current Demand Max Int MinuteRead
Phase C Current Demand Max Int SecondRead
Voltage Unbalance Max Int%Read
Voltage Unbalance Max Int YearRead
Voltage Unbalance Max Int MonthRead
Voltage Unbalance Max Int DayRead
Voltage Unbalance Max Int HourRead
Voltage Unbalance Max Int MinuteRead
Voltage Unbalance Max Int SecondRead
Current Unbalance Max Int%Read
Current Unbalance Max Int YearRead
Current Unbalance Max Int MonthRead
Current Unbalance Max Int DayRead
Current Unbalance Max Int HourRead
Current Unbalance Max Int MinuteRead
Current Unbalance Max Int SecondRead
THD_Va(Vab) Max Int%Read
THD_Va(Vab) Max Int YearRead
THD_Va(Vab) Max Int MonthRead
THD_Va(Vab) Max Int DayRead
THD_Va(Vab) Max Int HourRead
THD_Va(Vab) Max Int MinuteRead
THD_Va(Vab) Max Int SecondRead
THD_Vb(Vca) Max Int%Read
THD_Vb(Vca) Max Int YearRead
THD_Vb(Vca) Max Int MonthRead
THD_Vb(Vca) Max Int DayRead
THD_Vb(Vca) Max Int HourRead
THD_Vb(Vca) Max Int MinuteRead
THD_Vb(Vca) Max Int SecondRead
THD_Vc(Vbc) Max Int%Read
THD_Vc(Vbc) Max Int YearRead
THD_Vc(Vbc) Max Int MonthRead
THD_Vc(Vbc) Max Int DayRead
THD_Vc(Vbc) Max Int HourRead
THD_Vc(Vbc) Max Int MinuteRead
THD_Vc(Vbc) Max Int SecondRead
THD_Ia Max Int%Read
THD_Ia Max Int YearRead
THD_Ia Max Int MonthRead
THD_Ia Max Int DayRead
THD_Ia Max Int HourRead
THD_Ia Max Int MinuteRead
THD_Ia Max Int SecondRead
THD_Ib Max Int%Read
THD_Ib Max Int YearRead
THD_Ib Max Int MonthRead
THD_Ib Max Int DayRead
THD_Ib Max Int HourRead
THD_Ib Max Int MinuteRead
THD_Ib Max Int SecondRead
THD_Ic Max Int%Read
THD_Ic Max Int YearRead
THD_Ic Max Int MonthRead
THD_Ic Max Int DayRead
THD_Ic Max Int HourRead
THD_Ic Max Int MinuteRead
THD_Ic Max Int SecondRead
Va Min IntVRead
Va Min Int YearRead
Va Min Int MonthRead
Va Min Int DayRead
Va Min Int HourRead
Va Min Int MinuteRead
Va Min Int SecondRead
Vb Min IntVRead
Vb Min Int YearRead
Vb Min Int MonthRead
Vb Min Int DayRead
Vb Min Int HourRead
Vb Min Int MinuteRead
Vb Min Int SecondRead
Vc Min IntVRead
Vc Min Int YearRead
Vc Min Int MonthRead
Vc Min Int DayRead
Vc Min Int HourRead
Vc Min Int MinuteRead
Vc Min Int SecondRead
Vab Min IntVRead
Vab Min Int YearRead
Vab Min Int MonthRead
Vab Min Int DayRead
Vab Min Int HourRead
Vab Min Int MinuteRead
Vab Min Int SecondRead
Vbc Min IntVRead
Vbc Min Int YearRead
Vbc Min Int MonthRead
Vbc Min Int DayRead
Vbc Min Int HourRead
Vbc Min Int MinuteRead
Vbc Min Int SecondRead
Vca Min IntVRead
Vca Min Int YearRead
Vca Min Int MonthRead
Vca Min Int DayRead
Vca Min Int HourRead
Vca Min Int MinuteRead
Vca Min Int SecondRead
Ia Min IntARead
Ia Min Int YearRead
Ia Min Int MonthRead
Ia Min Int DayRead
Ia Min Int HourRead
Ia Min Int MinuteRead
Ia Min Int SecondRead
Ib Min IntARead
Ib Min Int YearRead
Ib Min Int MonthRead
Ib Min Int DayRead
Ib Min Int HourRead
Ib Min Int MinuteRead
Ib Min Int SecondRead
Ic Min IntRead
Ic Min Int YearRead
Ic Min Int MonthRead
Ic Min Int DayRead
Ic Min Int HourRead
Ic Min Int MinuteRead
Ic Min Int SecondRead
Total Power Min IntkWRead
Total Power Min Int YearRead
Total Power Min Int MonthRead
Total Power Min Int DayRead
Total Power Min Int HourRead
Total Power Min Int MinuteRead
Total Power Min Int SecondRead
Total Reactive Power Min IntkvarRead
Total Reactive Power Min Int YearRead
Total Reactive Power Min Int MonthRead
Total Reactive Power Min Int DayRead
Total Reactive Power Min Int HourRead
Total Reactive Power Min Int MinuteRead
Total Reactive Power Min Int SecondRead
Total Apparent Power Min IntkVARead
Total Apparent Power Min Int YearRead
Total Apparent Power Min Int MonthRead
Total Apparent Power Min Int DayRead
Total Apparent Power Min Int HourRead
Total Apparent Power Min Int MinuteRead
Total Apparent Power Min Int SecondRead
Power Factor Min IntRead
Power Factor Min Int YearRead
Power Factor Min Int MonthRead
Power Factor Min Int DayRead
Power Factor Min Int HourRead
Power Factor Min Int MinuteRead
Power Factor Min Int SecondRead
Frequency Min IntHzRead
Frequency Min Int YearRead
Frequency Min Int MonthRead
Frequency Min Int DayRead
Frequency Min Int HourRead
Frequency Min Int MinuteRead
Frequency Min Int SecondRead
Power Demand Min IntkWRead
Power Demand Min Int YearRead
Power Demand Min Int MonthRead
Power Demand Min Int DayRead
Power Demand Min Int HourRead
Power Demand Min Int MinuteRead
Power Demand Min Int SecondRead
Reactive Power Demand Min IntkvarRead
Reactive Power Demand Min Int YearRead
Reactive Power Demand Min Int MonthRead
Reactive Power Demand Min Int DayRead
Reactive Power Demand Min Int HourRead
Reactive Power Demand Min Int MinuteRead
Reactive Power Demand Min Int SecondRead
Apparent Power Demand Min IntkVARead
Apparent Power Demand Min Int YearRead
Apparent Power Demand Min Int MonthRead
Apparent Power Demand Min Int DayRead
Apparent Power Demand Min Int HourRead
Apparent Power Demand Min Int MinuteRead
Apparent Power Demand Min Int SecondRead
Voltage Unbalance Min Int%Read
Voltage Unbalance Min Int YearRead
Voltage Unbalance Min Int MonthRead
Voltage Unbalance Min Int DayRead
Voltage Unbalance Min Int HourRead
Voltage Unbalance Min Int MinuteRead
Voltage Unbalance Min Int SecondRead
Current Unbalance Min Int%Read
Current Unbalance Min Int YearRead
Current Unbalance Min Int MonthRead
Current Unbalance Min Int DayRead
Current Unbalance Min Int HourRead
Current Unbalance Min Int MinuteRead
Current Unbalance Min Int SecondRead
THD_Va(Vab) Min Int%Read
THD_Va(Vab) Min Int YearRead
THD_Va(Vab) Min Int MonthRead
THD_Va(Vab) Min Int DayRead
THD_Va(Vab) Min Int HourRead
THD_Va(Vab) Min Int MinuteRead
THD_Va(Vab) Min Int SecondRead
THD_Vb(Vca) Min Int%Read
THD_Vb(Vca) Min Int YearRead
THD_Vb(Vca) Min Int MonthRead
THD_Vb(Vca) Min Int DayRead
THD_Vb(Vca) Min Int HourRead
THD_Vb(Vca) Min Int MinuteRead
THD_Vb(Vca) Min Int SecondRead
THD_Vc(Vbc) Min Int%Read
THD_Vc(Vbc) Min Int YearRead
THD_Vc(Vbc) Min Int MonthRead
THD_Vc(Vbc) Min Int DayRead
THD_Vc(Vbc) Min Int HourRead
THD_Vc(Vbc) Min Int MinuteRead
THD_Vc(Vbc) Min Int SecondRead
THD_Ia Min Int%Read
THD_Ia Min Int YearRead
THD_Ia Min Int MonthRead
THD_Ia Min Int DayRead
THD_Ia Min Int HourRead
THD_Ia Min Int MinuteRead
THD_Ia Min Int SecondRead
THD_Ib Min Int%Read
THD_Ib Min Int YearRead
THD_Ib Min Int MonthRead
THD_Ib Min Int DayRead
THD_Ib Min Int HourRead
THD_Ib Min Int MinuteRead
THD_Ib Min Int SecondRead
THD_Ic Min Int%Read
THD_Ic Min Int YearRead
THD_Ic Min Int MonthRead
THD_Ic Min Int DayRead
THD_Ic Min Int HourRead
THD_Ic Min Int MinuteRead
THD_Ic Min Int SecondRead
Va MaxVRead
Va Max YearRead
Va Max MonthRead
Va Max DayRead
Va Max HourRead
Va Max MinuteRead
Va Max SecondRead
Vb MaxVRead
Vb Max YearRead
Vb Max MonthRead
Vb Max DayRead
Vb Max HourRead
Vb Max MinuteRead
Vb Max SecondRead
Vc MaxVRead
Vc Max YearRead
Vc Max MonthRead
Vc Max DayRead
Vc Max HourRead
Vc Max MinuteRead
Vc Max SecondRead
Vab MaxVRead
Vab Max YearRead
Vab Max MonthRead
Vab Max DayRead
Vab Max HourRead
Vab Max MinuteRead
Vab Max SecondRead
Vbc MaxVRead
Vbc Max YearRead
Vbc Max MonthRead
Vbc Max DayRead
Vbc Max HourRead
Vbc Max MinuteRead
Vbc Max SecondRead
Vca MaxVRead
Vca Max YearRead
Vca Max MonthRead
Vca Max DayRead
Vca Max HourRead
Vca Max MinuteRead
Vca Max SecondRead
Ia MaxARead
Ia Max YearRead
Ia Max MonthRead
Ia Max DayRead
Ia Max HourRead
Ia Max MinuteRead
Ia Max SecondRead
Ib MaxARead
Ib Max YearRead
Ib Max MonthRead
Ib Max DayRead
Ib Max HourRead
Ib Max MinuteRead
Ib Max SecondRead
Ic MaxARead
Ic Max YearRead
Ic Max MonthRead
Ic Max DayRead
Ic Max HourRead
Ic Max MinuteRead
Ic Max SecondRead
Total Power MaxkWRead
Total Power Max YearRead
Total Power Max MonthRead
Total Power Max DayRead
Total Power Max HourRead
Total Power Max MinuteRead
Total Power Max SecondRead
Total Reactive Power MaxkvarRead
Total Reactive Power Max YearRead
Total Reactive Power Max MonthRead
Total Reactive Power Max DayRead
Total Reactive Power Max HourRead
Total Reactive Power Max MinuteRead
Total Reactive Power Max SecondRead
Total Apparent Power MaxkVARead
Total Apparent Power Max YearRead
Total Apparent Power Max MonthRead
Total Apparent Power Max DayRead
Total Apparent Power Max HourRead
Total Apparent Power Max MinuteRead
Total Apparent Power Max SecondRead
Power Factor MaxRead
Power Factor Max YearRead
Power Factor Max MonthRead
Power Factor Max DayRead
Power Factor Max HourRead
Power Factor Max MinuteRead
Power Factor Max SecondRead
Frequency MaxHzRead
Frequency Max YearRead
Frequency Max MonthRead
Frequency Max DayRead
Frequency Max HourRead
Frequency Max MinuteRead
Frequency Max SecondRead
Power Demand MaxkWRead
Power Demand Max YearRead
Power Demand Max MonthRead
Power Demand Max DayRead
Power Demand Max HourRead
Power Demand Max MinuteRead
Power Demand Max SecondRead
Reactive Power Demand MaxkvarRead
Reactive Power Demand Max YearRead
Reactive Power Demand Max MonthRead
Reactive Power Demand Max DayRead
Reactive Power Demand Max HourRead
Reactive Power Demand Max MinuteRead
Reactive Power Demand Max SecondRead
Apparent Demand MaxkVARead
Apparent Demand Max YearRead
Apparent Demand Max MonthRead
Apparent Demand Max DayRead
Apparent Demand Max HourRead
Apparent Demand Max MinuteRead
Apparent Demand Max SecondRead
Voltage Unbalance Max%Read
Voltage Unbalance Max YearRead
Voltage Unbalance Max MonthRead
Voltage Unbalance Max DayRead
Voltage Unbalance Max HourRead
Voltage Unbalance Max MinuteRead
Voltage Unbalance Max SecondRead
Current Unbalance Max%Read
Current Unbalance Max YearRead
Current Unbalance Max MonthRead
Current Unbalance Max DayRead
Current Unbalance Max HourRead
Current Unbalance Max MinuteRead
Current Unbalance Max SecondRead
THD_Va(Vab) Max%Read
THD_Va(Vab) Max YearRead
THD_Va(Vab) Max MonthRead
THD_Va(Vab) Max DayRead
THD_Va(Vab) Max HourRead
THD_Va(Vab) Max MinuteRead
THD_Va(Vab) Max SecondRead
THD_Vb(Vca) Max%Read
THD_Vb(Vca) Max YearRead
THD_Vb(Vca) Max MonthRead
THD_Vb(Vca) Max DayRead
THD_Vb(Vca) Max HourRead
THD_Vb(Vca) Max MinuteRead
THD_Vb(Vca) Max SecondRead
THD_Vc(Vbc) Max%Read
THD_Vc(Vbc) Max YearRead
THD_Vc(Vbc) Max MonthRead
THD_Vc(Vbc) Max DayRead
THD_Vc(Vbc) Max HourRead
THD_Vc(Vbc) Max MinuteRead
THD_Vc(Vbc) Max SecondRead
THD_Ia Max%Read
THD_Ia Max YearRead
THD_Ia Max MonthRead
THD_Ia Max DayRead
THD_Ia Max HourRead
THD_Ia Max MinuteRead
THD_Ia Max SecondRead
THD_Ib Max%Read
THD_Ib Max YearRead
THD_Ib Max MonthRead
THD_Ib Max DayRead
THD_Ib Max HourRead
THD_Ib Max MinuteRead
THD_Ib Max SecondRead
THD_Ic Max%Read
THD_Ic Max YearRead
THD_Ic Max MonthRead
THD_Ic Max DayRead
THD_Ic Max HourRead
THD_Ic Max MinuteRead
THD_Ic Max SecondRead
Ia Current Demand MaxARead
Ia Current Demand Max YearRead
Ia Current Demand Max MonthRead
Ia Current Demand Max DayRead
Ia Current Demand Max HourRead
Ia Current Demand Max MinuteRead
Ia Current Demand Max SecondRead
Ib Current Demand MaxARead
Ib Current Demand Max YearRead
Ib Current Demand Max MonthRead
Ib Current Demand Max DayRead
Ib Current Demand Max HourRead
Ib Current Demand Max MinuteRead
Ib Current Demand Max SecondRead
Ic Current Demand MaxARead
Ic Current Demand Max YearRead
Ic Current Demand Max MonthRead
Ic Current Demand Max DayRead
Ic Current Demand Max HourRead
Ic Current Demand Max MinuteRead
Ic Current Demand Max SecondRead
Va MinVRead
Va Min YearRead
Va Min MonthRead
Va Min DayRead
Va Min HourRead
Va Min MinuteRead
Va Min SecondRead
Vb MinVRead
Vb Min YearRead
Vb Min MonthRead
Vb Min DayRead
Vb Min HourRead
Vb Min MinuteRead
Vb Min SecondRead
Vc MinVRead
Vc Min YearRead
Vc Min MonthRead
Vc Min DayRead
Vc Min HourRead
Vc Min MinuteRead
Vc Min SecondRead
Vab MinVRead
Vab Min YearRead
Vab Min MonthRead
Vab Min DayRead
Vab Min HourRead
Vab Min MinuteRead
Vab Min SecondRead
Vbc MinVRead
Vbc Min YearRead
Vbc Min MonthRead
Vbc Min DayRead
Vbc Min HourRead
Vbc Min MinuteRead
Vbc Min SecondRead
Vca MinVRead
Vca Min YearRead
Vca Min MonthRead
Vca Min DayRead
Vca Min HourRead
Vca Min MinuteRead
Vca Min SecondRead
Ia MinARead
Ia Min YearRead
Ia Min MonthRead
Ia Min DayRead
Ia Min HourRead
Ia Min MinuteRead
Ia Min SecondRead
Ib MinARead
Ib Min YearRead
Ib Min MonthRead
Ib Min DayRead
Ib Min HourRead
Ib Min MinuteRead
Ib Min SecondRead
Ic MinARead
Ic Min YearRead
Ic Min MonthRead
Ic Min DayRead
Ic Min HourRead
Ic Min MinuteRead
Ic Min SecondRead
Total Power MinkWRead
Total Power Min YearRead
Total Power Min MonthRead
Total Power Min DayRead
Total Power Min HourRead
Total Power Min MinuteRead
Total Power Min SecondRead
Total Reactive Power MinkvarRead
Total Reactive Power Min YearRead
Total Reactive Power Min MonthRead
Total Reactive Power Min DayRead
Total Reactive Power Min HourRead
Total Reactive Power Min MinuteRead
Total Reactive Power Min SecondRead
Total Apparent Power MinkVARead
Total Apparent Power Min YearRead
Total Apparent Power Min MonthRead
Total Apparent Power Min DayRead
Total Apparent Power Min HourRead
Total Apparent Power Min MinuteRead
Total Apparent Power Min SecondRead
Power Factor MinRead
Power Factor Min YearRead
Power Factor Min MonthRead
Power Factor Min DayRead
Power Factor Min HourRead
Power Factor Min MinuteRead
Power Factor Min SecondRead
Frequency MinHzRead
Frequency Min YearRead
Frequency Min MonthRead
Frequency Min DayRead
Frequency Min HourRead
Frequency Min MinuteRead
Frequency Min SecondRead
Power Demand MinkWRead
Power Demand Min YearRead
Power Demand Min MonthRead
Power Demand Min DayRead
Power Demand Min HourRead
Power Demand Min MinuteRead
Power Demand Min SecondRead
Reactive Power Demand MinkvarRead
Reactive Power Demand Min YearRead
Reactive Power Demand Min MonthRead
Reactive Power Demand Min DayRead
Reactive Power Demand Min HourRead
Reactive Power Demand Min MinuteRead
Reactive Power Demand Min SecondRead
Apparent Demand MinkVARead
Apparent Demand Min YearRead
Apparent Demand Min MonthRead
Apparent Demand Min DayRead
Apparent Demand Min HourRead
Apparent Demand Min MinuteRead
Apparent Demand Min SecondRead
Voltage Unbalance Min%Read
Voltage Unbalance Min YearRead
Voltage Unbalance Min MonthRead
Voltage Unbalance Min DayRead
Voltage Unbalance Min HourRead
Voltage Unbalance Min MinuteRead
Voltage Unbalance Min SecondRead
Current Unbalance Min%Read
Current Unbalance Min YearRead
Current Unbalance Min MonthRead
Current Unbalance Min DayRead
Current Unbalance Min HourRead
Current Unbalance Min MinuteRead
Current Unbalance Min SecondRead
THD_Va(Vab) Min%Read
THD_Va(Vab) Min YearRead
THD_Va(Vab) Min MonthRead
THD_Va(Vab) Min DayRead
THD_Va(Vab) Min HourRead
THD_Va(Vab) Min MinuteRead
THD_Va(Vab) Min SecondRead
THD_Vb(Vca) Min%Read
THD_Vb(Vca) Min YearRead
THD_Vb(Vca) Min MonthRead
THD_Vb(Vca) Min DayRead
THD_Vb(Vca) Min HourRead
THD_Vb(Vca) Min MinuteRead
THD_Vb(Vca) Min SecondRead
THD_Vc(Vbc) Min%Read
THD_Vc(Vbc) Min YearRead
THD_Vc(Vbc) Min MonthRead
THD_Vc(Vbc) Min DayRead
THD_Vc(Vbc) Min HourRead
THD_Vc(Vbc) Min MinuteRead
THD_Vc(Vbc) Min SecondRead
THD_Ia Min%Read
THD_Ia Min YearRead
THD_Ia Min MonthRead
THD_Ia Min DayRead
THD_Ia Min HourRead
THD_Ia Min MinuteRead
THD_Ia Min SecondRead
THD_Ib Min%Read
THD_Ib Min YearRead
THD_Ib Min MonthRead
THD_Ib Min DayRead
THD_Ib Min HourRead
THD_Ib Min MinuteRead
THD_Ib Min SecondRead
THD_Ic Min%Read
THD_Ic Min YearRead
THD_Ic Min MonthRead
THD_Ic Min DayRead
THD_Ic Min HourRead
THD_Ic Min MinuteRead
THD_Ic Min SecondRead
Ia Current Demand MinARead
Ia Current Demand Min YearRead
Ia Current Demand Min MonthRead
Ia Current Demand Min DayRead
Ia Current Demand Min HourRead
Ia Current Demand Min MinuteRead
Ia Current Demand Min SecondRead
Ib Current Demand MinARead
Ib Current Demand Min YearRead
Ib Current Demand Min MonthRead
Ib Current Demand Min DayRead
Ib Current Demand Min HourRead
Ib Current Demand Min MinuteRead
Ib Current Demand Min SecondRead
Ic Current Demand MinARead
Ic Current Demand Min YearRead
Ic Current Demand Min MonthRead
Ic Current Demand Min DayRead
Ic Current Demand Min HourRead
Ic Current Demand Min MinuteRead
Ic Current Demand Min SecondRead
Max of Phase A PRead
Max of Phase A P YearRead
Max of Phase A P MonthRead
Max of Phase A P DayRead
Max of Phase A P HourRead
Max of Phase A P MinuteRead
Max of Phase A P SecondRead
Max of Phase B PRead
Max of Phase B P YearRead
Max of Phase B P MonthRead
Max of Phase B P DayRead
Max of Phase B P HourRead
Max of Phase B P MinuteRead
Max of Phase B P SecondRead
Max of Phase C PRead
Max of Phase C P YearRead
Max of Phase C P MonthRead
Max of Phase C P DayRead
Max of Phase C P HourRead
Max of Phase C P MinuteRead
Max of Phase C P SecondRead
Max of Phase N PRead
Max of Phase N P YearRead
Max of Phase N P MonthRead
Max of Phase N P DayRead
Max of Phase N P HourRead
Max of Phase N P MinuteRead
Max of Phase N P SecondRead
Max of Phase A QRead
Max of Phase A Q YearRead
Max of Phase A Q MonthRead
Max of Phase A Q DayRead
Max of Phase A Q HourRead
Max of Phase A Q MinuteRead
Max of Phase A Q SecondRead
Max of Phase B QRead
Max of Phase B Q YearRead
Max of Phase B Q MonthRead
Max of Phase B Q DayRead
Max of Phase B Q HourRead
Max of Phase B Q MinuteRead
Max of Phase B Q SecondRead
Max of Phase C QRead
Max of Phase C Q YearRead
Max of Phase C Q MonthRead
Max of Phase C Q DayRead
Max of Phase C Q HourRead
Max of Phase C Q MinuteRead
Max of Phase C Q SecondRead
Max of Phase N QRead
Max of Phase N Q YearRead
Max of Phase N Q MonthRead
Max of Phase N Q DayRead
Max of Phase N Q HourRead
Max of Phase N Q MinuteRead
Max of Phase N Q SecondRead
Max of Phase A SRead
Max of Phase A S YearRead
Max of Phase A S MonthRead
Max of Phase A S DayRead
Max of Phase A S HourRead
Max of Phase A S MinuteRead
Max of Phase A S SecondRead
Max of Phase B SRead
Max of Phase B S YearRead
Max of Phase B S MonthRead
Max of Phase B S DayRead
Max of Phase B S HourRead
Max of Phase B S MinuteRead
Max of Phase B S SecondRead
Max of Phase C SRead
Max of Phase C S YearRead
Max of Phase C S MonthRead
Max of Phase C S DayRead
Max of Phase C S HourRead
Max of Phase C S MinuteRead
Max of Phase C S SecondRead
Max of Phase N SRead
Max of Phase N S YearRead
Max of Phase N S MonthRead
Max of Phase N S DayRead
Max of Phase N S HourRead
Max of Phase N S MinuteRead
Max of Phase N S SecondRead
Max of Phase A PFRead
Max of Phase A PF YearRead
Max of Phase A PF MonthRead
Max of Phase A PF DayRead
Max of Phase A PF HourRead
Max of Phase A PF MinuteRead
Max of Phase A PF SecondRead
Max of Phase B PFRead
Max of Phase B PF YearRead
Max of Phase B PF MonthRead
Max of Phase B PF DayRead
Max of Phase B PF HourRead
Max of Phase B PF MinuteRead
Max of Phase B PF SecondRead
Max of Phase C PFRead
Max of Phase C PF YearRead
Max of Phase C PF MonthRead
Max of Phase C PF DayRead
Max of Phase C PF HourRead
Max of Phase C PF MinuteRead
Max of Phase C PF SecondRead
Max of Phase N PFRead
Max of Phase N PF YearRead
Max of Phase N PF MonthRead
Max of Phase N PF DayRead
Max of Phase N PF HourRead
Max of Phase N PF MinuteRead
Max of Phase N PF SecondRead
Max of Phase A P DemandRead
Max of Phase A P Demand YearRead
Max of Phase A P Demand MonthRead
Max of Phase A P Demand DayRead
Max of Phase A P Demand HourRead
Max of Phase A P Demand MinuteRead
Max of Phase A P Demand SecondRead
Max of Phase B P DemandRead
Max of Phase B P Demand YearRead
Max of Phase B P Demand MonthRead
Max of Phase B P Demand DayRead
Max of Phase B P Demand HourRead
Max of Phase B P Demand MinuteRead
Max of Phase B P Demand SecondRead
Max of Phase C P DemandRead
Max of Phase C P Demand YearRead
Max of Phase C P Demand MonthRead
Max of Phase C P Demand DayRead
Max of Phase C P Demand HourRead
Max of Phase C P Demand MinuteRead
Max of Phase C P Demand SecondRead
Max of Phase N P DemandRead
Max of Phase N P Demand YearRead
Max of Phase N P Demand MonthRead
Max of Phase N P Demand DayRead
Max of Phase N P Demand HourRead
Max of Phase N P Demand MinuteRead
Max of Phase N P Demand SecondRead
Max of Phase A Q DemandRead
Max of Phase A Q Demand YearRead
Max of Phase A Q Demand MonthRead
Max of Phase A Q Demand DayRead
Max of Phase A Q Demand HourRead
Max of Phase A Q Demand MinuteRead
Max of Phase A Q Demand SecondRead
Max of Phase B Q DemandRead
Max of Phase B Q Demand YearRead
Max of Phase B Q Demand MonthRead
Max of Phase B Q Demand DayRead
Max of Phase B Q Demand HourRead
Max of Phase B Q Demand MinuteRead
Max of Phase B Q Demand SecondRead
Max of Phase C Q DemandRead
Max of Phase C Q Demand YearRead
Max of Phase C Q Demand MonthRead
Max of Phase C Q Demand DayRead
Max of Phase C Q Demand HourRead
Max of Phase C Q Demand MinuteRead
Max of Phase C Q Demand SecondRead
Max of Phase N Q DemandRead
Max of Phase N Q Demand YearRead
Max of Phase N Q Demand MonthRead
Max of Phase N Q Demand DayRead
Max of Phase N Q Demand HourRead
Max of Phase N Q Demand MinuteRead
Max of Phase N Q Demand SecondRead
Max of Phase A S DemandRead
Max of Phase A S Demand YearRead
Max of Phase A S Demand MonthRead
Max of Phase A S Demand DayRead
Max of Phase A S Demand HourRead
Max of Phase A S Demand MinuteRead
Max of Phase A S Demand SecondRead
Max of Phase B S DemandRead
Max of Phase B S Demand YearRead
Max of Phase B S Demand MonthRead
Max of Phase B S Demand DayRead
Max of Phase B S Demand HourRead
Max of Phase B S Demand MinuteRead
Max of Phase B S Demand SecondRead
Max of Phase C S DemandRead
Max of Phase C S Demand YearRead
Max of Phase C S Demand MonthRead
Max of Phase C S Demand DayRead
Max of Phase C S Demand HourRead
Max of Phase C S Demand MinuteRead
Max of Phase C S Demand SecondRead
Max of Phase N S DemandRead
Max of Phase N S Demand YearRead
Max of Phase N S Demand MonthRead
Max of Phase N S Demand DayRead
Max of Phase N S Demand HourRead
Max of Phase N S Demand MinuteRead
Max of Phase N S Demand SecondRead
Max of Phase N I DemandRead
Max of Phase N I Demand YearRead
Max of Phase N I Demand MonthRead
Max of Phase N I Demand DayRead
Max of Phase N I Demand HourRead
Max of Phase N I Demand MinuteRead
Max of Phase N I Demand SecondRead
Max of Phase N IRead
Max of Phase N I YearRead
Max of Phase N I MonthRead
Max of Phase N I DayRead
Max of Phase N I HourRead
Max of Phase N I MinuteRead
Max of Phase N I SecondRead
Max of Summation 2 PRead
Max of Summation 2 P YearRead
Max of Summation 2 P MonthRead
Max of Summation 2 P DayRead
Max of Summation 2 P HourRead
Max of Summation 2 P MinuteRead
Max of Summation 2 P SecondRead
Max of Summation 2 QRead
Max of Summation 2 Q YearRead
Max of Summation 2 Q MonthRead
Max of Summation 2 Q DayRead
Max of Summation 2 Q HourRead
Max of Summation 2 Q MinuteRead
Max of Summation 2 Q SecondRead
Max of Summation 2 SRead
Max of Summation 2 S YearRead
Max of Summation 2 S MonthRead
Max of Summation 2 S DayRead
Max of Summation 2 S HourRead
Max of Summation 2 S MinuteRead
Max of Summation 2 S SecondRead
Max of Summation 2 PFRead
Max of Summation 2 PF YearRead
Max of Summation 2 PF MonthRead
Max of Summation 2 PF DayRead
Max of Summation 2 PF HourRead
Max of Summation 2 PF MinuteRead
Max of Summation 2 PF SecondRead
Max of Summation 2 P DemandRead
Max of Summation 2 P Demand YearRead
Max of Summation 2 P Demand MonthRead
Max of Summation 2 P Demand DayRead
Max of Summation 2 P Demand HourRead
Max of Summation 2 P Demand MinuteRead
Max of Summation 2 P Demand SecondRead
Max of Summation 2 Q DemandRead
Max of Summation 2 Q Demand YearRead
Max of Summation 2 Q Demand MonthRead
Max of Summation 2 Q Demand DayRead
Max of Summation 2 Q Demand HourRead
Max of Summation 2 Q Demand MinuteRead
Max of Summation 2 Q Demand SecondRead
Max of Summation 2 S DemandRead
Max of Summation 2 S Demand YearRead
Max of Summation 2 S Demand MonthRead
Max of Summation 2 S Demand DayRead
Max of Summation 2 S Demand HourRead
Max of Summation 2 S Demand MinuteRead
Max of Summation 2 S Demand SecondRead
Max of Summation 2 IRead
Max of Summation 2 I YearRead
Max of Summation 2 I MonthRead
Max of Summation 2 I DayRead
Max of Summation 2 I HourRead
Max of Summation 2 I MinuteRead
Max of Summation 2 I SecondRead
Max of In THDRead
Max of In THD YearRead
Max of In THD MonthRead
Max of In THD DayRead
Max of In THD HourRead
Max of In THD MinuteRead
Max of In THD SecondRead
Min of Phase A PRead
Min of Phase A P YearRead
Min of Phase A P MonthRead
Min of Phase A P DayRead
Min of Phase A P HourRead
Min of Phase A P MinuteRead
Min of Phase A P SecondRead
Min of Phase B PRead
Min of Phase B P YearRead
Min of Phase B P MonthRead
Min of Phase B P DayRead
Min of Phase B P HourRead
Min of Phase B P MinuteRead
Min of Phase B P SecondRead
Min of Phase C PRead
Min of Phase C P YearRead
Min of Phase C P MonthRead
Min of Phase C P DayRead
Min of Phase C P HourRead
Min of Phase C P MinuteRead
Min of Phase C P SecondRead
Min of Phase N PRead
Min of Phase N P YearRead
Min of Phase N P MonthRead
Min of Phase N P DayRead
Min of Phase N P HourRead
Min of Phase N P MinuteRead
Min of Phase N P SecondRead
Min of Phase A QRead
Min of Phase A Q YearRead
Min of Phase A Q MonthRead
Min of Phase A Q DayRead
Min of Phase A Q HourRead
Min of Phase A Q MinuteRead
Min of Phase A Q SecondRead
Min of Phase B QRead
Min of Phase B Q YearRead
Min of Phase B Q MonthRead
Min of Phase B Q DayRead
Min of Phase B Q HourRead
Min of Phase B Q MinuteRead
Min of Phase B Q SecondRead
Min of Phase C QRead
Min of Phase C Q YearRead
Min of Phase C Q MonthRead
Min of Phase C Q DayRead
Min of Phase C Q HourRead
Min of Phase C Q MinuteRead
Min of Phase C Q SecondRead
Min of Phase N QRead
Min of Phase N Q YearRead
Min of Phase N Q MonthRead
Min of Phase N Q DayRead
Min of Phase N Q HourRead
Min of Phase N Q MinuteRead
Min of Phase N Q SecondRead
Min of Phase A SRead
Min of Phase A S YearRead
Min of Phase A S MonthRead
Min of Phase A S DayRead
Min of Phase A S HourRead
Min of Phase A S MinuteRead
Min of Phase A S SecondRead
Min of Phase B SRead
Min of Phase B S YearRead
Min of Phase B S MonthRead
Min of Phase B S DayRead
Min of Phase B S HourRead
Min of Phase B S MinuteRead
Min of Phase B S SecondRead
Min of Phase C SRead
Min of Phase C S YearRead
Min of Phase C S MonthRead
Min of Phase C S DayRead
Min of Phase C S HourRead
Min of Phase C S MinuteRead
Min of Phase C S SecondRead
Min of Phase N SRead
Min of Phase N S YearRead
Min of Phase N S MonthRead
Min of Phase N S DayRead
Min of Phase N S HourRead
Min of Phase N S MinuteRead
Min of Phase N S SecondRead
Min of Phase A PFRead
Min of Phase A PF YearRead
Min of Phase A PF MonthRead
Min of Phase A PF DayRead
Min of Phase A PF HourRead
Min of Phase A PF MinuteRead
Min of Phase A PF SecondRead
Min of Phase B PFRead
Min of Phase B PF YearRead
Min of Phase B PF MonthRead
Min of Phase B PF DayRead
Min of Phase B PF HourRead
Min of Phase B PF MinuteRead
Min of Phase B PF SecondRead
Min of Phase C PFRead
Min of Phase C PF YearRead
Min of Phase C PF MonthRead
Min of Phase C PF DayRead
Min of Phase C PF HourRead
Min of Phase C PF MinuteRead
Min of Phase C PF SecondRead
Min of Phase N PFRead
Min of Phase N PF YearRead
Min of Phase N PF MonthRead
Min of Phase N PF DayRead
Min of Phase N PF HourRead
Min of Phase N PF MinuteRead
Min of Phase N PF SecondRead
Min of Phase A P DemandRead
Min of Phase A P Demand YearRead
Min of Phase A P Demand MonthRead
Min of Phase A P Demand DayRead
Min of Phase A P Demand HourRead
Min of Phase A P Demand MinuteRead
Min of Phase A P Demand SecondRead
Min of Phase B P DemandRead
Min of Phase B P Demand YearRead
Min of Phase B P Demand MonthRead
Min of Phase B P Demand DayRead
Min of Phase B P Demand HourRead
Min of Phase B P Demand MinuteRead
Min of Phase B P Demand SecondRead
Min of Phase C P DemandRead
Min of Phase C P Demand YearRead
Min of Phase C P Demand MonthRead
Min of Phase C P Demand DayRead
Min of Phase C P Demand HourRead
Min of Phase C P Demand MinuteRead
Min of Phase C P Demand SecondRead
Min of Phase N P DemandRead
Min of Phase N P Demand YearRead
Min of Phase N P Demand MonthRead
Min of Phase N P Demand DayRead
Min of Phase N P Demand HourRead
Min of Phase N P Demand MinuteRead
Min of Phase N P Demand SecondRead
Min of Phase A Q DemandRead
Min of Phase A Q Demand YearRead
Min of Phase A Q Demand MonthRead
Min of Phase A Q Demand DayRead
Min of Phase A Q Demand HourRead
Min of Phase A Q Demand MinuteRead
Min of Phase A Q Demand SecondRead
Min of Phase B Q DemandRead
Min of Phase B Q Demand YearRead
Min of Phase B Q Demand MonthRead
Min of Phase B Q Demand DayRead
Min of Phase B Q Demand HourRead
Min of Phase B Q Demand MinuteRead
Min of Phase B Q Demand SecondRead
Min of Phase C Q DemandRead
Min of Phase C Q Demand YearRead
Min of Phase C Q Demand MonthRead
Min of Phase C Q Demand DayRead
Min of Phase C Q Demand HourRead
Min of Phase C Q Demand MinuteRead
Min of Phase C Q Demand SecondRead
Min of Phase N Q DemandRead
Min of Phase N Q Demand YearRead
Min of Phase N Q Demand MonthRead
Min of Phase N Q Demand DayRead
Min of Phase N Q Demand HourRead
Min of Phase N Q Demand MinuteRead
Min of Phase N Q Demand SecondRead
Min of Phase A S DemandRead
Min of Phase A S Demand YearRead
Min of Phase A S Demand MonthRead
Min of Phase A S Demand DayRead
Min of Phase A S Demand HourRead
Min of Phase A S Demand MinuteRead
Min of Phase A S Demand SecondRead
Min of Phase B S DemandRead
Min of Phase B S Demand YearRead
Min of Phase B S Demand MonthRead
Min of Phase B S Demand DayRead
Min of Phase B S Demand HourRead
Min of Phase B S Demand MinuteRead
Min of Phase B S Demand SecondRead
Min of Phase C S DemandRead
Min of Phase C S Demand YearRead
Min of Phase C S Demand MonthRead
Min of Phase C S Demand DayRead
Min of Phase C S Demand HourRead
Min of Phase C S Demand MinuteRead
Min of Phase C S Demand SecondRead
Min of Phase N S DemandRead
Min of Phase N S Demand YearRead
Min of Phase N S Demand MonthRead
Min of Phase N S Demand DayRead
Min of Phase N S Demand HourRead
Min of Phase N S Demand MinuteRead
Min of Phase N S Demand SecondRead
Min of Phase N IRead
Min of Phase N I YearRead
Min of Phase N I MonthRead
Min of Phase N I DayRead
Min of Phase N I HourRead
Min of Phase N I MinuteRead
Min of Phase N I SecondRead
Min of Summation 2 PRead
Min of Summation 2 P YearRead
Min of Summation 2 P MonthRead
Min of Summation 2 P DayRead
Min of Summation 2 P HourRead
Min of Summation 2 P MinuteRead
Min of Summation 2 P SecondRead
Min of Summation 2 QRead
Min of Summation 2 Q YearRead
Min of Summation 2 Q MonthRead
Min of Summation 2 Q DayRead
Min of Summation 2 Q HourRead
Min of Summation 2 Q MinuteRead
Min of Summation 2 Q SecondRead
Min of Summation 2 SRead
Min of Summation 2 S YearRead
Min of Summation 2 S MonthRead
Min of Summation 2 S DayRead
Min of Summation 2 S HourRead
Min of Summation 2 S MinuteRead
Min of Summation 2 S SecondRead
Min of Summation 2 PFRead
Min of Summation 2 PF YearRead
Min of Summation 2 PF MonthRead
Min of Summation 2 PF DayRead
Min of Summation 2 PF HourRead
Min of Summation 2 PF MinuteRead
Min of Summation 2 PF SecondRead
Min of Summation 2 P DemandRead
Min of Summation 2 P Demand YearRead
Min of Summation 2 P Demand MonthRead
Min of Summation 2 P Demand DayRead
Min of Summation 2 P Demand HourRead
Min of Summation 2 P Demand MinuteRead
Min of Summation 2 P Demand SecondRead
Min of Summation 2 Q DemandRead
Min of Summation 2 Q Demand YearRead
Min of Summation 2 Q Demand MonthRead
Min of Summation 2 Q Demand DayRead
Min of Summation 2 Q Demand HourRead
Min of Summation 2 Q Demand MinuteRead
Min of Summation 2 Q Demand SecondRead
Min of Summation 2 S DemandRead
Min of Summation 2 S Demand YearRead
Min of Summation 2 S Demand MonthRead
Min of Summation 2 S Demand DayRead
Min of Summation 2 S Demand HourRead
Min of Summation 2 S Demand MinuteRead
Min of Summation 2 S Demand SecondRead
Min of Summation 2 IRead
Min of Summation 2 I YearRead
Min of Summation 2 I MonthRead
Min of Summation 2 I DayRead
Min of Summation 2 I HourRead
Min of Summation 2 I MinuteRead
Min of Summation 2 I SecondRead
Min of In THDRead
Min of In THD YearRead
Min of In THD MonthRead
Min of In THD DayRead
Min of In THD HourRead
Min of In THD MinuteRead
Min of In THD SecondRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show peak power demand and the moment it occurred on a dashboard for capacity planning.
  • Set an alarm when the recorded maximum phase current passes a threshold you choose.
  • Check after a complaint how low each phase voltage dropped and when it happened.
  • Track the highest THD per phase over time to see whether power quality gets worse.
  • Compare peak demand per month in the history to discuss the grid connection with the customer.

Installation

  1. Connect RS485 A and B of the Acuvim II to the RS485 port of the ModbusCloud Gateway, with a 120 ohm terminator at both ends of the bus.

  2. Check on the meter that the address is 1 and the link is 19200 baud, 8 data bits, no parity, 1 stop bit, or note the values you use.

  3. In ModbusCloud, add a Modbus device with the same address and settings and import this template, next to the main Acuvim II template if you use it.

  4. Check that the maximum and minimum values and their time stamps come in and match the meter display.

Things to watch for

The meter does not answer. What should I check?

Compare address, baud rate and parity on the meter with the settings in ModbusCloud; the default is address 1 at 19200 baud, 8N1. Swap A and B if nothing answers, and make sure the bus has a terminator at both ends.

Why do the integer values differ from the float values?

The integer maxima and minima are on the secondary side of the voltage and current transformers. The float values follow the primary or secondary mode set on the meter. With transformers, multiply the integer values by the PT or CT ratio.

The time stamp shows zeros. Is that a fault?

A time stamp of zeros usually means the value has not been recorded since the last reset of the max/min log, or the meter clock is not set. Set the date and time on the meter and wait until a new extreme occurs.

Can I read several Acuvim II meters on one bus?

Yes. Give every meter its own address and the same baud rate and parity, and add each one as a separate Modbus device in ModbusCloud with this template.

Want to see how it works?

Electrician working in an open distribution board