Accuenergy Acuvim II
Three-phase multifunction power meter for voltage, current, power, energy and power quality.
The Accuenergy Acuvim II is a multifunction power meter that measures voltage, current, power, energy and power quality in switchboards and distribution panels. This Modbus RTU template reads all real-time values, energy counters and I/O states and lets you change the meter settings and relay outputs from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 768, read and write
- Brand
- Accuenergy
- Key readings
- Phase voltages · Phase currents · Active power · Reactive power · Power factor · Frequency · Imported energy · Voltage and current THD
- Available commands
- CT and PT ratio · Communication settings · Relay outputs · Clear energy and demand · Clock
- Compatible models
- Acuvim II · Acuvim IIR · Acuvim IIE · Acuvim IIW
- Last updated
Registers (768)
768 read, 253 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Frequency | Hz | Read | |||
| Phase A Line-Neutral Voltage | V | Read | |||
| Phase B Line-Neutral Voltage | V | Read | |||
| Phase C Line-Neutral Voltage | V | Read | |||
| Average Line-Neutral Voltage | V | Read | |||
| Line Voltage AB | V | Read | |||
| Line Voltage BC | V | Read | |||
| Line Voltage CA | V | Read | |||
| Average Line Voltage | V | Read | |||
| Phase A Current | A | Read | |||
| Phase B Current | A | Read | |||
| Phase C Current | A | Read | |||
| Average Phase Current | A | Read | |||
| Neutral Current | A | Read | |||
| Phase A Power | kW | Read | |||
| Phase B Power | kW | Read | |||
| Phase C Power | kW | Read | |||
| Total System Power | kW | Read | |||
| Phase A Reactive Power | kvar | Read | |||
| Phase B Reactive Power | kvar | Read | |||
| Phase C Reactive Power | kvar | Read | |||
| Total Reactive Power | kvar | Read | |||
| Phase A Apparent Power | kVA | Read | |||
| Phase B Apparent Power | kVA | Read | |||
| Phase C Apparent Power | kVA | Read | |||
| Total Apparent Power | kVA | Read | |||
| Phase A Power Factor | Read | ||||
| Phase B Power Factor | Read | ||||
| Phase C Power Factor | Read | ||||
| Total Power Factor | Read | ||||
| Voltage Unbalance | % | Read | |||
| Current Unbalance | % | Read | |||
| Load Characteristic | Read | ||||
| Active Power Demand | kW | Read | |||
| Reactive Power Demand | kvar | Read | |||
| Apparent Power Demand | kVA | Read | |||
| Phase A Current Demand | A | Read | |||
| Phase B Current Demand | A | Read | |||
| Phase C Current Demand | A | Read | |||
| Predictive Demand P | kW | Read | |||
| Predictive Demand Q | kvar | Read | |||
| Predictive Demand S | kVA | Read | |||
| Residual Current | A | Read | |||
| Phase A Displacement Power Factor | Read | ||||
| Phase B Displacement Power Factor | Read | ||||
| Phase C Displacement Power Factor | Read | ||||
| System Displacement Power Factor | Read | ||||
| Import Energy | kWh | Read and write | |||
| Export Energy | kWh | Read and write | |||
| Import Reactive Energy | kvarh | Read and write | |||
| Export Reactive Energy | kvarh | Read and write | |||
| Total Energy | kWh | Read and write | |||
| Net Energy | kWh | Read and write | |||
| Total Reactive Energy | kvarh | Read and write | |||
| Net Reactive Energy | kvarh | Read and write | |||
| Apparent Energy | kVAh | Read and write | |||
| Phase A Import Energy | kWh | Read and write | |||
| Phase A Export Energy | kWh | Read and write | |||
| Phase B Import Energy | kWh | Read and write | |||
| Phase B Export Energy | kWh | Read and write | |||
| Phase C Import Energy | kWh | Read and write | |||
| Phase C Export Energy | kWh | Read and write | |||
| Phase A Import Reactive Energy | kvarh | Read and write | |||
| Phase A Export Reactive Energy | kvarh | Read and write | |||
| Phase B Import Reactive Energy | kvarh | Read and write | |||
| Phase B Export Reactive Energy | kvarh | Read and write | |||
| Phase C Import Reactive Energy | kvarh | Read and write | |||
| Phase C Export Reactive Energy | kvarh | Read and write | |||
| Phase A Apparent Energy | kVAh | Read and write | |||
| Phase B Apparent Energy | kVAh | Read and write | |||
| Phase C Apparent Energy | kVAh | Read and write | |||
| Import Apparent Energy | kVAh | Read and write | |||
| Phase A Import Apparent Energy | kVAh | Read and write | |||
| Phase B Import Apparent Energy | kVAh | Read and write | |||
| Phase C Import Apparent Energy | kVAh | Read and write | |||
| Export Apparent Energy | kVAh | Read and write | |||
| Phase A Export Apparent Energy | kVAh | Read and write | |||
| Phase B Export Apparent Energy | kVAh | Read and write | |||
| Phase C Export Apparent Energy | kVAh | Read and write | |||
| Q1 Reactive Energy | Read and write | ||||
| Q1 Phase A Reactive Energy | Read and write | ||||
| Q1 Phase B Reactive Energy | Read and write | ||||
| Q1 Phase C Reactive Energy | Read and write | ||||
| Q2 Reactive Energy | Read and write | ||||
| Q2 Phase A Reactive Energy | Read and write | ||||
| Q2 Phase B Reactive Energy | Read and write | ||||
| Q2 Phase C Reactive Energy | Read and write | ||||
| Q3 Reactive Energy | Read and write | ||||
| Q3 Phase A Reactive Energy | Read and write | ||||
| Q3 Phase B Reactive Energy | Read and write | ||||
| Q3 Phase C Reactive Energy | Read and write | ||||
| Q4 Reactive Energy | Read and write | ||||
| Q4 Phase A Reactive Energy | Read and write | ||||
| Q4 Phase B Reactive Energy | Read and write | ||||
| Q4 Phase C Reactive Energy | Read and write | ||||
| Energy Accumulated Start Time Year | Read | ||||
| Energy Accumulated Start Time Month | Read | ||||
| Energy Accumulated Start Time Day | Read | ||||
| Energy Accumulated Start Time Hour | Read | ||||
| Energy Accumulated Start Time Minute | Read | ||||
| Energy Accumulated Start Time Second | Read | ||||
| Energy Accumulated End Time Year | Read | ||||
| Energy Accumulated End Time Month | Read | ||||
| Energy Accumulated End Time Day | Read | ||||
| Energy Accumulated End Time Hour | Read | ||||
| Energy Accumulated End Time Minute | Read | ||||
| Energy Accumulated End Time Second | Read | ||||
| Import Active Energy | Read and write | ||||
| Export Active Energy | Read and write | ||||
| Import Reactive Energy 18832 | Read and write | ||||
| Export Reactive Energy 18834 | Read and write | ||||
| Total Active Energy | Read and write | ||||
| Net Active Energy | Read and write | ||||
| Total Reactive Energy 18840 | Read and write | ||||
| Net Reactive Energy 18842 | Read and write | ||||
| Apparent Energy 18844 | kVAh | Read and write | |||
| Frequency Int | Hz | Read | |||
| Phase 1 Voltage Int | V | Read | |||
| Phase 2 Voltage Int | V | Read | |||
| Phase 3 Voltage Int | V | Read | |||
| Average Phase Voltage Int | V | Read | |||
| Line Voltage 1-2 Int | V | Read | |||
| Line Voltage 2-3 Int | V | Read | |||
| Line Voltage 3-1 Int | V | Read | |||
| Average Line Voltage Int | V | Read | |||
| Total Phase A Current Int | A | Read | |||
| Total Phase B Current Int | A | Read | |||
| Total Phase C Current Int | A | Read | |||
| Average Phase Current Int | A | Read | |||
| Neutral Current Int | A | Read | |||
| Phase A Power Int | W | Read | |||
| Phase B Power Int | W | Read | |||
| Phase C Power Int | W | Read | |||
| Total System Power Int | W | Read | |||
| Phase A Reactive Power Int | var | Read | |||
| Phase B Reactive Power Int | var | Read | |||
| Phase C Reactive Power Int | var | Read | |||
| Total Reactive Power Int | var | Read | |||
| Phase A Apparent Power Int | VA | Read | |||
| Phase B Apparent Power Int | VA | Read | |||
| Phase C Apparent Power Int | VA | Read | |||
| Total Apparent Power Int | VA | Read | |||
| Phase A Power Factor Int | Read | ||||
| Phase B Power Factor Int | Read | ||||
| Phase C Power Factor Int | Read | ||||
| Total Power Factor Int | Read | ||||
| Voltage Unbalance Int | % | Read | |||
| Current Unbalance Int | % | Read | |||
| Load Characteristic Int | Read | ||||
| Power Demand Int | W | Read | |||
| Reactive Power Demand Int | var | Read | |||
| Apparent Power Demand Int | VA | Read | |||
| Phase A Current Demand Int | A | Read | |||
| Phase B Current Demand Int | A | Read | |||
| Phase C Current Demand Int | A | Read | |||
| THD_Va(Vab) | % | Read | |||
| THD_Vb(Vca) | % | Read | |||
| THD_Vc(Vbc) | % | Read | |||
| THD_avg | % | Read | |||
| THD_Ia | % | Read | |||
| THD_Ib | % | Read | |||
| THD_Ic | % | Read | |||
| THD_Iavg | % | Read | |||
| TDD_I1 | % | Read | |||
| TDD_I2 | % | Read | |||
| TDD_I3 | % | Read | |||
| TDD_Iavg | % | Read | |||
| Crest Factor_I1 | % | Read | |||
| Crest Factor_I2 | % | Read | |||
| Crest Factor_I3 | % | Read | |||
| Crest Factor_In | % | Read | |||
| Phase Angle of V2 to V1 | ° | Read | |||
| Phase Angle of V3 to V1 | ° | Read | |||
| Phase Angle of I1 to V1 | ° | Read | |||
| Phase Angle of I2 to V1 | ° | Read | |||
| Phase Angle of I3 to V1 | ° | Read | |||
| Phase Angle of V1 to V1 | ° | Read | |||
| Positive Sequence Real Part of V1 | % | Read | |||
| Positive Sequence Complex Part of V1 | % | Read | |||
| Negative Sequence Real Part of V1 | % | Read | |||
| Negative Sequence Complex Part of V1 | % | Read | |||
| Zero Sequence Real Part of V1 | % | Read | |||
| Zero Sequence Complex Part of V1 | % | Read | |||
| Positive Sequence Real Part of I1 | % | Read | |||
| Positive Sequence Complex Part of I1 | % | Read | |||
| Negative Sequence Real Part of I1 | % | Read | |||
| Negative Sequence Complex Part of I1 | % | Read | |||
| Zero Sequence Real Part of I1 | % | Read | |||
| Zero Sequence Complex Part of I1 | % | Read | |||
| P Max, Phase A - Last Interval | kW | Read | |||
| P Max, Phase B - Last Interval | kW | Read | |||
| P Max, Phase C - Last Interval | kW | Read | |||
| P Max, Total - Last Interval | kW | Read | |||
| P Min, Phase A - Last Interval | kW | Read | |||
| P Min, Phase B - Last Interval | kW | Read | |||
| P Min, Phase C - Last Interval | kW | Read | |||
| P Min, Total - Last Interval | kW | Read | |||
| P Avg, Phase A - Last Interval | kW | Read | |||
| P Avg, Phase B - Last Interval | kW | Read | |||
| P Avg, Phase C - Last Interval | kW | Read | |||
| P Avg, Total - Last Interval | kW | Read | |||
| Q Max, Phase A - Last Interval | kvar | Read | |||
| Q Max, Phase B - Last Interval | kvar | Read | |||
| Q Max, Phase C - Last Interval | kvar | Read | |||
| Q Max, Total - Last Interval | kvar | Read | |||
| Q Min, Phase A - Last Interval | kvar | Read | |||
| Q Min, Phase B - Last Interval | kvar | Read | |||
| Q Min, Phase C - Last Interval | kvar | Read | |||
| Q Min, Total - Last Interval | kvar | Read | |||
| Q Avg, Phase A - Last Interval | kvar | Read | |||
| Q Avg, Phase B - Last Interval | kvar | Read | |||
| Q Avg, Phase C - Last Interval | kvar | Read | |||
| Q Avg, Total - Last Interval | kvar | Read | |||
| S Max, Phase A - Last Interval | kVA | Read | |||
| S Max, Phase B - Last Interval | kVA | Read | |||
| S Max, Phase C - Last Interval | kVA | Read | |||
| S Max, Total - Last Interval | kVA | Read | |||
| S Min, Phase A - Last Interval | kVA | Read | |||
| S Min, Phase B - Last Interval | kVA | Read | |||
| S Min, Phase C - Last Interval | kVA | Read | |||
| S Min, Total - Last Interval | kVA | Read | |||
| S Avg, Phase A - Last Interval | kVA | Read | |||
| S Avg, Phase B - Last Interval | kVA | Read | |||
| S Avg, Phase C - Last Interval | kVA | Read | |||
| S Avg, Total - Last Interval | kVA | Read | |||
| I Max, Phase A - Last Interval | A | Read | |||
| I Max, Phase B - Last Interval | A | Read | |||
| I Max, Phase C - Last Interval | A | Read | |||
| I Max, Phase N - Last Interval | A | Read | |||
| I Max, Average - Last Interval | A | Read | |||
| I Min, Phase A - Last Interval | A | Read | |||
| I Min, Phase B - Last Interval | A | Read | |||
| I Min, Phase C - Last Interval | A | Read | |||
| I Min, Phase N - Last Interval | A | Read | |||
| I Min, Average - Last Interval | A | Read | |||
| I Avg, Phase A - Last Interval | A | Read | |||
| I Avg, Phase B - Last Interval | A | Read | |||
| I Avg, Phase C - Last Interval | A | Read | |||
| I Avg, Phase N - Last Interval | A | Read | |||
| I Avg, Average - Last Interval | A | Read | |||
| Voltage LN Max - Phase A - Last Interval | V | Read | |||
| Voltage LN Max - Phase B - Last Interval | V | Read | |||
| Voltage LN Max - Phase C - Last Interval | V | Read | |||
| Voltage LL Max - Phase AB - Last Interval | V | Read | |||
| Voltage LL Max - Phase BC - Last Interval | V | Read | |||
| Voltage LL Max- Phase CA - Last Interval | V | Read | |||
| Voltage LN Min - Phase A - Last Interval | V | Read | |||
| Voltage LN Min - Phase B - Last Interval | V | Read | |||
| Voltage LN Min - Phase C - Last Interval | V | Read | |||
| Voltage LL Min - Phase AB - Last Interval | V | Read | |||
| Voltage LL Min - Phase BC - Last Interval | V | Read | |||
| Voltage LL Min- Phase CA - Last Interval | V | Read | |||
| Voltage LN Avg - Phase A - Last Interval | V | Read | |||
| Voltage LN Avg - Phase B - Last Interval | V | Read | |||
| Voltage LN Avg - Phase C - Last Interval | V | Read | |||
| Voltage LL Avg - Phase AB - Last Interval | V | Read | |||
| Voltage LL Avg - Phase BC - Last Interval | V | Read | |||
| Voltage LL Avg- Phase CA - Last Interval | V | Read | |||
| Frequency 100ms | Hz | Read | |||
| Phase A Line-Neutral Voltage 100ms | V | Read | |||
| Phase B Line-Neutral Voltage 100ms | V | Read | |||
| Phase C Line-Neutral Voltage 100ms | V | Read | |||
| Average Line-Neutral Voltage 100ms | V | Read | |||
| Line Voltage AB 100ms | V | Read | |||
| Line Voltage BC 100ms | V | Read | |||
| Line Voltage CA 100ms | V | Read | |||
| Average Line-Line Voltage 100ms | V | Read | |||
| Phase A Current 100ms | A | Read | |||
| Phase B Current 100ms | A | Read | |||
| Phase C Current 100ms | A | Read | |||
| Average Phase Current 100ms | A | Read | |||
| Neutral Current 100ms | A | Read | |||
| Phase A Power 100ms | kW | Read | |||
| Phase B Power 100ms | kW | Read | |||
| Phase C Power 100ms | kW | Read | |||
| Total System Power 100ms | kW | Read | |||
| Phase A Reactive Power 100ms | kvar | Read | |||
| Phase B Reactive Power 100ms | kvar | Read | |||
| Phase C Reactive Power 100ms | kvar | Read | |||
| Total Reactive Power 100ms | kvar | Read | |||
| Phase A Apparent Power 100ms | kVA | Read | |||
| Phase B Apparent Power 100ms | kVA | Read | |||
| Phase C Apparent Power 100ms | kVA | Read | |||
| Total Apparent Power 100ms | kVA | Read | |||
| Phase A Power Factor 100ms | Read | ||||
| Phase B Power Factor 100ms | Read | ||||
| Phase C Power Factor 100ms | Read | ||||
| Total Power Factor 100ms | Read | ||||
| Phase A Line-Neutral Voltage 20ms | V | Read | |||
| Phase B Line-Neutral Voltage 20ms | V | Read | |||
| Phase C Line-Neutral Voltage 20ms | V | Read | |||
| Phase A Current 20ms | A | Read | |||
| Phase B Current 20ms | A | Read | |||
| Phase C Current 20ms | A | Read | |||
| Phase A Power 20ms | kW | Read | |||
| Phase B Power 20ms | kW | Read | |||
| Phase C Power 20ms | kW | Read | |||
| Average Line-Neutral Voltage 20ms | V | Read | |||
| Average Phase Current 20ms | A | Read | |||
| Average Line-Line Voltage 20ms | V | Read | |||
| Total Power 20ms | kW | Read | |||
| Total Reactive Power 20ms | kvar | Read | |||
| Frequency 20ms | Hz | Read | |||
| Phase A Line-Neutral Voltage Moving Avg | V | Read | |||
| Phase B Line-Neutral Voltage Moving Avg | V | Read | |||
| Phase C Line-Neutral Voltage Moving Avg | V | Read | |||
| Line Voltage AB Moving Avg | V | Read | |||
| Line Voltage BC Moving Avg | V | Read | |||
| Line Voltage CA Moving Avg | V | Read | |||
| Phase A Current Moving Avg | A | Read | |||
| Phase B Current Moving Avg | A | Read | |||
| Phase C Current Moving Avg | A | Read | |||
| Neutral Current Moving Avg | A | Read | |||
| Phase A Active Power Moving Avg | kW | Read | |||
| Phase B Active Power Moving Avg | kW | Read | |||
| Phase C Active Power Moving Avg | kW | Read | |||
| Phase A Apparent Power Moving Avg | kVA | Read | |||
| Phase B Apparent Power Moving Avg | kVA | Read | |||
| Phase C Apparent Power Moving Avg | kVA | Read | |||
| Total System Active Power Moving Avg | kW | Read | |||
| Channel 4 Current Int | A | Read | |||
| Channel 4 Angle Int | ° | Read | |||
| Channel 4 Active Power Int | kW | Read | |||
| Channel 4 Reactive Power Int | kvar | Read | |||
| Channel 4 Apparent Power Int | kVA | Read | |||
| Channel 4 PF Int | Read | ||||
| Channel 4 LN (L/C/R) Int | Read | ||||
| Channel 4 Current Demand Int | A | Read | |||
| Summation 2 Iavg Int | A | Read | |||
| Summation 2 P Int | kW | Read | |||
| Summation 2 Q Int | kvar | Read | |||
| Summation 2 S Int | kVA | Read | |||
| Summation 2 PF Int | Read | ||||
| Summation 2 LN (L/C/R) Int | Read | ||||
| Channel 1 LN (L/C/R) Int | Read | ||||
| Channel 2 LN (L/C/R) Int | Read | ||||
| Channel 3 LN (L/C/R) Int | Read | ||||
| Channel 1 P Demand Int | kW | Read | |||
| Channel 2 P Demand Int | kW | Read | |||
| Channel 3 P Demand Int | kW | Read | |||
| Channel 4 P Demand Int | kW | Read | |||
| Summation 2 P Demand Int | kW | Read | |||
| Channel 1 Q Demand Int | kvar | Read | |||
| Channel 2 Q Demand Int | kvar | Read | |||
| Channel 3 Q Demand Int | kvar | Read | |||
| Channel 4 Q Demand Int | kvar | Read | |||
| Summation 2 Q Demand Int | kvar | Read | |||
| Channel 1 S Demand Int | kVA | Read | |||
| Channel 2 S Demand Int | kVA | Read | |||
| Channel 3 S Demand Int | kVA | Read | |||
| Channel 4 S Demand Int | kVA | Read | |||
| Summation 2 S Demand Int | kVA | Read | |||
| Channel 4 Current | A | Read | |||
| Channel 4 Angle | ° | Read | |||
| Channel 4 Active Power | kW | Read | |||
| Channel 4 Reactive Power | kvar | Read | |||
| Channel 4 Apparent Power | kVA | Read | |||
| Channel 4 PF | Read | ||||
| Channel 4 LN (L/C/R) | Read | ||||
| Channel 4 Current Demand | A | Read | |||
| Summation 2 Iavg | A | Read | |||
| Summation 2 P | kW | Read | |||
| Summation 2 Q | kvar | Read | |||
| Summation 2 S | kVA | Read | |||
| Summation 2 PF | Read | ||||
| Summation 2 LN (L/C/R) | Read | ||||
| Channel 1 LN (L/C/R) | Read | ||||
| Channel 2 LN (L/C/R) | Read | ||||
| Channel 3 LN (L/C/R) | Read | ||||
| Channel 1 P Demand | kW | Read | |||
| Channel 2 P Demand | kW | Read | |||
| Channel 3 P Demand | kW | Read | |||
| Channel 4 P Demand | kW | Read | |||
| Summation 2 P Demand | kW | Read | |||
| Channel 1 Q Demand | kvar | Read | |||
| Channel 2 Q Demand | kvar | Read | |||
| Channel 3 Q Demand | kvar | Read | |||
| Channel 4 Q Demand | kvar | Read | |||
| Summation 2 Q Demand | kvar | Read | |||
| Channel 1 S Demand | kVA | Read | |||
| Channel 2 S Demand | kVA | Read | |||
| Channel 3 S Demand | kVA | Read | |||
| Channel 4 S Demand | kVA | Read | |||
| Summation 2 S Demand | kVA | Read | |||
| Channel 4 Ep_imp | kWh | Read and write | |||
| Channel 4 Ep_exp | kWh | Read and write | |||
| Channel 4 Eq_imp | kvarh | Read and write | |||
| Channel 4 Eq_exp | kvarh | Read and write | |||
| Channel 4 Es_imp | kVAh | Read and write | |||
| Channel 4 Es_exp | kVAh | Read and write | |||
| Channel 4 Es_total | kVAh | Read and write | |||
| Channel 4 Eq_q1 | kvarh | Read and write | |||
| Channel 4 Eq_q2 | kvarh | Read and write | |||
| Channel 4 Eq_q3 | kvarh | Read and write | |||
| Channel 4 Eq_q4 | Read and write | ||||
| Summation 2 Ep_imp | kWh | Read and write | |||
| Summation 2 Ep_exp | kWh | Read and write | |||
| Summation 2 Ep_total | kWh | Read and write | |||
| Summation 2 Ep_net | kWh | Read and write | |||
| Summation 2 Eq_imp | kvarh | Read and write | |||
| Summation 2 Eq_exp | kvarh | Read and write | |||
| Summation 2 Eq_total | kvarh | Read and write | |||
| Summation 2 Eq_net | kvarh | Read and write | |||
| Summation 2 Es_imp | kVAh | Read and write | |||
| Summation 2 ES_exp | kVAh | Read and write | |||
| Summation 2 Es_total | kVAh | Read and write | |||
| Summation 2 Es_net | kVAh | Read and write | |||
| Summation 2 Ep_q1 | kvarh | Read and write | |||
| Summation 2 Ep_q2 | kvarh | Read and write | |||
| Summation 2 Ep_q3 | kvarh | Read and write | |||
| Summation 2 Ep_q4 | kvarh | Read and write | |||
| Summation 2 Eq_q1 | kvarh | Read and write | |||
| Summation 2 Eq_q2 | kvarh | Read and write | |||
| Summation 2 Eq_q3 | kvarh | Read and write | |||
| Summation 2 Eq_q4 | kvarh | Read and write | |||
| Summation 2 Es_q1 | kvarh | Read and write | |||
| Summation 2 Es_q2 | kvarh | Read and write | |||
| Summation 2 Es_q3 | kvarh | Read and write | |||
| Summation 2 Es_q4 | kvarh | Read and write | |||
| Alarm Channel 1 Status | Read | ||||
| Alarm Channel 2 Status | Read | ||||
| Alarm Channel 3 Status | Read | ||||
| Alarm Channel 4 Status | Read | ||||
| Alarm Channel 5 Status | Read | ||||
| Alarm Channel 6 Status | Read | ||||
| Alarm Channel 7 Status | Read | ||||
| Alarm Channel 8 Status | Read | ||||
| Alarm Channel 9 Status | Read | ||||
| Alarm Channel 10 Status | Read | ||||
| Alarm Channel 11 Status | Read | ||||
| Alarm Channel 12 Status | Read | ||||
| Alarm Channel 13 Status | Read | ||||
| Alarm Channel 14 Status | Read | ||||
| Alarm Channel 15 Status | Read | ||||
| Alarm Channel 16 Status | Read | ||||
| AXM-IO11 DI Status | Read | ||||
| AXM-IO21 DI Status | Read | ||||
| AXM-IO31 DI Status | Read | ||||
| AXM-IO12 DI Status | Read | ||||
| AXM-IO22 DI Status | Read | ||||
| AXM-IO32 DI Status | Read | ||||
| AXM-IO1-1 DI1 Status | Read | ||||
| AXM-IO1-1 DI2 Status | Read | ||||
| AXM-IO1-1 DI3 Status | Read | ||||
| AXM-IO1-1 DI4 Status | Read | ||||
| AXM-IO1-1 DI5 Status | Read | ||||
| AXM-IO1-1 DI6 Status | Read | ||||
| AXM-IO2-1 DI7 Status | Read | ||||
| AXM-IO2-1 DI8 Status | Read | ||||
| AXM-IO2-1 DI9 Status | Read | ||||
| AXM-IO2-1 DI10 Status | Read | ||||
| AXM-IO3-1 DI11 Status | Read | ||||
| AXM-IO3-1 DI12 Status | Read | ||||
| AXM-IO3-1 DI13 Status | Read | ||||
| AXM-IO3-1 DI14 Status | Read | ||||
| AXM-IO1-2 DI15 Status | Read | ||||
| AXM-IO1-2 DI16 Status | Read | ||||
| AXM-IO1-2 DI17 Status | Read | ||||
| AXM-IO1-2 DI18 Status | Read | ||||
| AXM-IO1-2 DI19 Status | Read | ||||
| AXM-IO1-2 DI20 Status | Read | ||||
| AXM-IO2-2 DI21 Status | Read | ||||
| AXM-IO2-2 DI22 Status | Read | ||||
| AXM-IO2-2 DI23 Status | Read | ||||
| AXM-IO2-2 DI24 Status | Read | ||||
| AXM-IO3-2 DI25 Status | Read | ||||
| AXM-IO3-2 DI26 Status | Read | ||||
| AXM-IO3-2 DI27 Status | Read | ||||
| AXM-IO3-2 DI28 Status | Read | ||||
| AXM-IO1-1 DI1 Pulse Count | Read | ||||
| AXM-IO1-1 DI2 Pulse Count | Read | ||||
| AXM-IO1-1 DI3 Pulse Count | Read | ||||
| AXM-IO1-1 DI4 Pulse Count | Read | ||||
| AXM-IO1-1 DI5 Pulse Count | Read | ||||
| AXM-IO1-1 DI6 Pulse Count | Read | ||||
| AXM-IO2-1 DI1 Pulse Count | Read | ||||
| AXM-IO2-1 DI2 Pulse Count | Read | ||||
| AXM-IO2-1 DI3 Pulse Count | Read | ||||
| AXM-IO2-1 DI4 Pulse Count | Read | ||||
| AXM-IO3-1 DI1 Pulse Count | Read | ||||
| AXM-IO3-1 DI2 Pulse Count | Read | ||||
| AXM-IO3-1 DI3 Pulse Count | Read | ||||
| AXM-IO3-1 DI4 Pulse Count | Read | ||||
| AXM-IO1-2 DI1 Pulse Count | Read | ||||
| AXM-IO1-2 DI2 Pulse Count | Read | ||||
| AXM-IO1-2 DI3 Pulse Count | Read | ||||
| AXM-IO1-2 DI4 Pulse Count | Read | ||||
| AXM-IO1-2 DI5 Pulse Count | Read | ||||
| AXM-IO1-2 DI6 Pulse Count | Read | ||||
| AXM-IO2-2 DI1 Pulse Count | Read | ||||
| AXM-IO2-2 DI2 Pulse Count | Read | ||||
| AXM-IO2-2 DI3 Pulse Count | Read | ||||
| AXM-IO2-2 DI4 Pulse Count | Read | ||||
| AXM-IO3-2 DI1 Pulse Count | Read | ||||
| AXM-IO3-2 DI2 Pulse Count | Read | ||||
| AXM-IO3-2 DI3 Pulse Count | Read | ||||
| AXM-IO3-2 DI4 Pulse Count | Read | ||||
| Value of AO1 | Read | ||||
| Value of AO2 | Read | ||||
| Value of AO3 | Read | ||||
| Value of AO4 | Read | ||||
| AXM-IO3-1 AI1 Sampling Value | Read | ||||
| AXM-IO3-1 AI2 Sampling Value | Read | ||||
| AXM-IO3-2 AI3 Sampling Value | Read | ||||
| AXM-IO3-2 AI4 Sampling Value | Read | ||||
| AXM-IO11 Relay Output 1 | Read and write | ||||
| AXM-IO11 Relay Output 2 | Read and write | ||||
| AXM-IO31 Relay Output 1 | Read and write | ||||
| AXM-IO31 Relay Output 2 | Read and write | ||||
| AXM-IO12 Relay Output 1 | Read and write | ||||
| AXM-IO12 Relay Output 2 | Read and write | ||||
| AXM-IO32 Relay Output 1 | Read and write | ||||
| AXM-IO32 Relay Output 2 | Read and write | ||||
| Frequency Setting | Read and write | ||||
| Protocol 1 | Read and write | ||||
| Parity 1 | Read and write | ||||
| Password | Read and write | ||||
| Communication Address 1 | Read and write | ||||
| Baud Rate | Read and write | ||||
| Voltage Input Wiring Type | Read and write | ||||
| Current Input Wiring Type | Read and write | ||||
| PT1(High 16 Bit) | Read and write | ||||
| PT1(Low 16 Bit) | Read and write | ||||
| PT2 | Read and write | ||||
| CT1 | Read and write | ||||
| CT2 | Read and write | ||||
| KWh Pulse Constant | Read and write | ||||
| Kvarh Pulse Constant | Read and write | ||||
| LCD Backlight Time | Read and write | ||||
| Demand Sliding Window Time | Read and write | ||||
| Demand Calculation Mode | Read and write | ||||
| Clear Demand | Read and write | ||||
| Max/Min Clear | Read and write | ||||
| Run Time Clear | Read and write | ||||
| Current I1 Direction | Read and write | ||||
| Current I2 Direction | Read and write | ||||
| Current I3 Direction | Read and write | ||||
| VAR/PF Convention | Read and write | ||||
| Clear Energy | Read and write | ||||
| Energy Calculation Mode | Read and write | ||||
| Reactive Power Measurement Mode | Read and write | ||||
| Energy Display Mode | Read and write | ||||
| Reset Ethernet Module | Read and write | ||||
| Enable SOE | Read and write | ||||
| Clear Pulse Counter | Read and write | ||||
| Basic Parameter Mode | Read and write | ||||
| Non Standard Seal Options | Read and write | ||||
| Sealed State | Read | ||||
| Demand Calculation Slip Time | Read and write | ||||
| Clear Alarm Records | Read and write | ||||
| CT41 | Read and write | ||||
| CT42 | Read and write | ||||
| Restore Factory Settings | Read and write | ||||
| Neutral Current Mode | Read and write | ||||
| Load Percentage Power Rating | Read and write | ||||
| Load Percentage Property | Read and write | ||||
| System Status | Read | ||||
| Baud Rate 2 | Read and write | ||||
| Parity 2 | Read and write | ||||
| Address 2 | Read and write | ||||
| Alarm Record Number | Read | ||||
| SOE Record Number | Read | ||||
| Run Time (High) | Read and write | ||||
| Run Time (Low) | Read | ||||
| IO Module Connection Status | Read | ||||
| Protocol 2 | Read | ||||
| 10 Year Holiday Setting Enable | Read and write | ||||
| Clear Sharp Tariff | Read and write | ||||
| Clear Peak Tariff | Read and write | ||||
| Clear Valley Tariff | Read and write | ||||
| Clear Normal Tariff | Read and write | ||||
| Clear Total TOU Energy | Read and write | ||||
| Phase A Current Phase Selection | Read and write | ||||
| Phase B Current Phase Selection | Read and write | ||||
| Phase C Current Phase Selection | Read and write | ||||
| Neutral Current Phase Selection | Read and write | ||||
| Frequency Average Filter: Update Rate | Read and write | ||||
| Frequency Average Filter: Window Size | Read and write | ||||
| Load Run Time High Byte | Read and write | ||||
| Load Run Time Low Byte | Read | ||||
| Last Interval | Read and write | ||||
| Dual Source Enable/Disable | Read and write | ||||
| Energy Selection 1 | Read and write | ||||
| Energy Selection 2 | Read and write | ||||
| Energy Selection 3 | Read and write | ||||
| Control Mode | Read and write | ||||
| Direction | Read and write | ||||
| Clear Dual Source Energy | Read and write | ||||
| Clear Dual Source Swithching Record | Read and write | ||||
| Energy 1 - Grid Direction | Read | ||||
| Energy 1 - Generator Direction | Read | ||||
| Energy 2 - Grid Direction | Read | ||||
| Energy 2 - Generator Direction | Read | ||||
| Energy 3 - Grid Direction | Read | ||||
| Energy 3 - Generator Direction | Read | ||||
| Number of Records to Read | Read | ||||
| ID of Current Switching Record | Read | ||||
| The Length of Bytes That Can Be Read By the Current Window | Read | ||||
| 1st Switch Record - Timestamp Year & Month | Read | ||||
| 1st Switch Record - Timestamp Day & Hour | Read | ||||
| 1st Switch Record - Timestamp Minute & Second | Read | ||||
| 1st Switch Record - Switch Command Source | Read | ||||
| 1st Switch Record - Swith Command | Read | ||||
| 1st Switch Record - Energy 1 - Grid Direction Word 1 | Read | ||||
| 1st Switch Record - Energy 1 - Grid Direction Word 2 | Read | ||||
| 1st Switch Record - Energy 1 - Generator Direction Word 1 | Read | ||||
| 1st Switch Record - Energy 1 - Generator Direction Word 2 | Read | ||||
| 1st Switch Record - Energy 2 - Grid Direction Word 1 | Read | ||||
| 1st Switch Record - Energy 2 - Grid Direction Word 2 | Read | ||||
| 1st Switch Record - Energy 2 - Generator Direction Word 1 | Read | ||||
| 1st Switch Record - Energy 2 - Generator Direction Word 2 | Read | ||||
| 1st Switch Record - Energy 3 - Grid Direction Word 1 | Read | ||||
| 1st Switch Record - Energy 3 - Grid Direction Word 2 | Read | ||||
| 1st Switch Record - Energy 3 - Generator Direction Word 1 | Read | ||||
| 1st Switch Record - Energy 3 - Generator Direction Word 2 | Read | ||||
| 2nd Switch Record Data Word 1 | Read | ||||
| 2nd Switch Record Data Word 2 | Read | ||||
| 2nd Switch Record Data Word 3 | Read | ||||
| 2nd Switch Record Data Word 4 | Read | ||||
| 2nd Switch Record Data Word 5 | Read | ||||
| 2nd Switch Record Data Word 6 | Read | ||||
| 2nd Switch Record Data Word 7 | Read | ||||
| 2nd Switch Record Data Word 8 | Read | ||||
| 2nd Switch Record Data Word 9 | Read | ||||
| 2nd Switch Record Data Word 10 | Read | ||||
| 2nd Switch Record Data Word 11 | Read | ||||
| 2nd Switch Record Data Word 12 | Read | ||||
| 2nd Switch Record Data Word 13 | Read | ||||
| 2nd Switch Record Data Word 14 | Read | ||||
| 2nd Switch Record Data Word 15 | Read | ||||
| 2nd Switch Record Data Word 16 | Read | ||||
| 2nd Switch Record Data Word 17 | Read | ||||
| 3rd Switch Record Data Word 1 | Read | ||||
| 3rd Switch Record Data Word 2 | Read | ||||
| 3rd Switch Record Data Word 3 | Read | ||||
| 3rd Switch Record Data Word 4 | Read | ||||
| 3rd Switch Record Data Word 5 | Read | ||||
| 3rd Switch Record Data Word 6 | Read | ||||
| 3rd Switch Record Data Word 7 | Read | ||||
| 3rd Switch Record Data Word 8 | Read | ||||
| 3rd Switch Record Data Word 9 | Read | ||||
| 3rd Switch Record Data Word 10 | Read | ||||
| 3rd Switch Record Data Word 11 | Read | ||||
| 3rd Switch Record Data Word 12 | Read | ||||
| 3rd Switch Record Data Word 13 | Read | ||||
| 3rd Switch Record Data Word 14 | Read | ||||
| 3rd Switch Record Data Word 15 | Read | ||||
| 3rd Switch Record Data Word 16 | Read | ||||
| 3rd Switch Record Data Word 17 | Read | ||||
| 4th Switch Record Data Word 1 | Read | ||||
| 4th Switch Record Data Word 2 | Read | ||||
| 4th Switch Record Data Word 3 | Read | ||||
| 4th Switch Record Data Word 4 | Read | ||||
| 4th Switch Record Data Word 5 | Read | ||||
| 4th Switch Record Data Word 6 | Read | ||||
| 4th Switch Record Data Word 7 | Read | ||||
| 4th Switch Record Data Word 8 | Read | ||||
| 4th Switch Record Data Word 9 | Read | ||||
| 4th Switch Record Data Word 10 | Read | ||||
| 4th Switch Record Data Word 11 | Read | ||||
| 4th Switch Record Data Word 12 | Read | ||||
| 4th Switch Record Data Word 13 | Read | ||||
| 4th Switch Record Data Word 14 | Read | ||||
| 4th Switch Record Data Word 15 | Read | ||||
| 4th Switch Record Data Word 16 | Read | ||||
| 4th Switch Record Data Word 17 | Read | ||||
| 5th Switch Record Data Word 1 | Read | ||||
| 5th Switch Record Data Word 2 | Read | ||||
| 5th Switch Record Data Word 3 | Read | ||||
| 5th Switch Record Data Word 4 | Read | ||||
| 5th Switch Record Data Word 5 | Read | ||||
| 5th Switch Record Data Word 6 | Read | ||||
| 5th Switch Record Data Word 7 | Read | ||||
| 5th Switch Record Data Word 8 | Read | ||||
| 5th Switch Record Data Word 9 | Read | ||||
| 5th Switch Record Data Word 10 | Read | ||||
| 5th Switch Record Data Word 11 | Read | ||||
| 5th Switch Record Data Word 12 | Read | ||||
| 5th Switch Record Data Word 13 | Read | ||||
| 5th Switch Record Data Word 14 | Read | ||||
| 5th Switch Record Data Word 15 | Read | ||||
| 5th Switch Record Data Word 16 | Read | ||||
| 5th Switch Record Data Word 17 | Read | ||||
| Week | Read and write | ||||
| Year | Read and write | ||||
| Month | Read and write | ||||
| Day | Read and write | ||||
| Hour | Read and write | ||||
| Minute | Read and write | ||||
| Second | Read and write | ||||
| AXM-IO1-1 DI1-DI6 Type | Read and write | ||||
| AXM-IO1-1 DI Pulse Constant | Read and write | ||||
| AXM-IO1-1 RO Type Mode | Read and write | ||||
| AXM-IO1-1 RO Control Mode | Read and write | ||||
| AXM-IO1-1 Pulse Width | Read and write | ||||
| AXM-IO2-1 DI1-DI4 Type | Read and write | ||||
| AXM-IO2-1 DI Pulse Constant | Read and write | ||||
| AXM-IO2-1 DO Mode | Read and write | ||||
| AXM-IO2-1 DO Pulse Width | Read and write | ||||
| AXM-IO2-1 DO1 Output | Read and write | ||||
| AXM-IO2-1 DO1 Output Hex Address | Read and write | ||||
| AXM-IO2-1 DO2 Output | Read and write | ||||
| AXM-IO2-1 DO2 Output Hex Address | Read and write | ||||
| AXM-IO2-1 AO Type | Read and write | ||||
| AXM-IO3-1 DI11~DI14 Type | Read and write | ||||
| AXM-IO3-1 DI Pulse Constant | Read and write | ||||
| AXM-IO3-1 RO Type Mode | Read and write | ||||
| AXM-IO3-1 RO Control Mode | Read and write | ||||
| AXM-IO3-1 Pulse Width | Read and write | ||||
| AXM-IO3-1 AI Type | Read and write | ||||
| AXM-IO1-2 DI15~20 Type | Read and write | ||||
| AXM-IO1-2 DI Pulse Constant | Read and write | ||||
| AXM-IO1-2 RO Type Mode | Read and write | ||||
| AXM-IO1-2 RO Control Mode | Read and write | ||||
| AXM-IO1-2 Pulse Width | Read and write | ||||
| AXM-IO2-2 DI21~DI24 Type | Read and write | ||||
| AXM-IO2-2 DI Pulse Constant | Read and write | ||||
| AXM-IO2-2 DO Mode | Read and write | ||||
| AXM-IO2-2 DO Pulse Width | Read and write | ||||
| AXM-IO2-2 DO1 Output | Read and write | ||||
| AXM-IO2-2 DO2 Output | Read and write | ||||
| AXM-IO2-2 AO Type | Read and write | ||||
| AXM-IO3-2 DI25~DI28 Type | Read and write | ||||
| AXM-IO3-2 DI Pulse Constant | Read and write | ||||
| AXM-IO3-2 RO Type Mode | Read and write | ||||
| AXM-IO3-2 RO Control Mode | Read and write | ||||
| AXM-IO3-2 Pulse Width | Read and write | ||||
| AXM-IO3-2 AI Type | Read and write | ||||
| AXM-IO2-1 AO1 Parameter Selection | Read and write | ||||
| AXM-IO2-1 AO2 Parameter Selection | Read and write | ||||
| AXM-IO2-2 AO3 Parameter Selection | Read and write | ||||
| AXM-IO2-2 AO4 Parameter Selection | Read and write | ||||
| AXM-IO2-1 AO1 Slope Selection | Read and write | ||||
| AXM-IO2-1 AO1 Starting Point Value | Read and write | ||||
| AXM-IO2-1 AO1 Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO1 Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO1 End Point Value | Read and write | ||||
| AXM-IO2-1 AO1 Output Starting Point Value | Read and write | ||||
| AXM-IO2-1 AO1 Output Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO1 Output Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO1 Output End Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Slope Selection | Read and write | ||||
| AXM-IO2-1 AO2 Starting Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO2 End Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Output Starting Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Output Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Output Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-1 AO2 Output End Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Slope Selection | Read and write | ||||
| AXM-IO2-2 AO1 Starting Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO1 End Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Output Starting Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Output Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Output Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO1 Output End Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Slope Selection | Read and write | ||||
| AXM-IO2-2 AO2 Starting Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO2 End Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Output Starting Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Output Slope 1 End/Slope 2 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Output Slope 2 End/Slope 3 Start Point Value | Read and write | ||||
| AXM-IO2-2 AO2 Output End Point Value | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show voltage, current, power and power factor per phase on a dashboard for each switchboard.
- Log imported and exported energy per phase to compare tenants or production lines month by month.
- Get an alert when the current unbalance or voltage THD passes a limit you set.
- Watch the demand values to see when a connection gets close to its contracted capacity.
- Switch a relay output of an AXM module from ModbusCloud, for example to shed a load.
Installation
Connect the RS485 terminals A and B of the meter to the RS485 port of the ModbusCloud Gateway, with a 120 ohm terminator at both ends of the bus.
On the meter, set the address, baud rate and parity in the communication menu, for example address 1, 19200 baud, no parity.
Set Basic Parameter Mode to Primary if you want readings that match the display, independent of the CT and PT ratio.
In ModbusCloud, add a Modbus device with the same address and settings and import this template.
Check that frequency reads about 50 Hz and the phase voltages match the display of the meter.
Things to watch for
The meter does not answer on the bus. What should I check?
Compare address, baud rate and parity with the communication menu of the meter. Parity setting Non1 means no parity with one stop bit, Non2 means no parity with two. Then swap A and B and make sure the bus has a terminator at both ends.
Why are currents and power much lower than on the display?
The meter is in Secondary mode, so values are on the secondary side of the CT and PT. Set Basic Parameter Mode to Primary, or multiply by CT1/CT2 and PT1/PT2. The integer registers always need that ratio.
The energy counter is ten or a thousand times off. Why?
The energy registers follow Energy Display Mode. In Primary mode the counter has one decimal, in Secondary mode three. Check the setting on the meter and keep it the same as when you set up the template.
Can I write the settings and relays from ModbusCloud?
Yes. Settings, clock and energy presets are holding registers written with function code 16, relay outputs are coils. A write to the clear and restore registers resets counters or the whole meter, so check the value before you send it. Writing must be enabled for the gateway first.
Can I connect several meters to one RS485 line?
Yes. Give each meter its own address and the same baud rate and parity. Wire them as a line, not a star, and terminate both ends.