Alnor Systemy Wentylacji Sp. z o. o. Alnor HRU-P Modbus RTU template

Alnor HRU-P

Controls Alnor HRU-P heat recovery ventilation units via Modbus RTU.

This template monitors and controls Alnor HRU-P heat recovery ventilation units via Modbus RTU at 115200 baud. It reads temperatures, fan speeds, airflow, humidity, CO2, filter status, and bypass position. It also provides write access for work mode selection, fan speed and airflow settings, bypass control, and GHE configuration.

Protocol
Modbus RTU
Connection
RS485, 115200 baud
Registers
49, read and write
Key readings
Supply/Extract/Inlet/Exhaust temperatures · Supply and exhaust fan speed (%) · Supply and exhaust airflow (m3/h) · Indoor humidity and CO2 · Filter depletion and days left · Bypass position and status
Available commands
Work mode and turn on/off · Fan speed settings (Speed 1-3) · Fan flow settings (Speed 1-3) · Bypass and GHE control
Compatible models
HRU-SlimAIR-250-H-P · HRU-SlimAIR-250-H-CF-P · HRU-SlimAIR-250E-H-P · HRU-SlimAIR-250E-H-CF-P · HRU-SlimAIR-L-250-H-P · HRU-SlimAIR-L-250-H-CF-P · HRU-SlimAIR-L-250E-H-P · HRU-SlimAIR-L-250E-H-CF-P · HRU-SlimAIR-350-H-P · HRU-SlimAIR-350-H-CF-P · HRU-SlimAIR-350E-H-P · HRU-SlimAIR-350E-H-CF-P · HRU-SlimAIR-400-H-P · HRU-SlimAIR-400-H-CF-P · HRU-SlimAIR-400E-H-P · HRU-SlimAIR-400E-H-CF-P · HRU-SlimAIR-300-H-P · HRU-SlimAIR-300-H-CF-P · HRU-SlimAIR-300E-H-P · HRU-SlimAIR-300E-H-CF-P · HRU-SlimAIR-500-H-P · HRU-SlimAIR-500-H-CF-P · HRU-SlimAIR-500E-H-P · HRU-SlimAIR-500E-H-CF-P · HRU-SlimAIR-800-H-P · HRU-SlimAIR-800-H-CF-P · HRU-SlimAIR-800E-H-P · HRU-SlimAIR-800E-H-CF-P · HRU-SlimAIR-1000-P · HRU-SlimAIR-1000E-P · HRU-SlimAIR-1000E-CF-P · HRU-SlimAIR-1000-CF-P · HRU-PremAIR-350-P · HRU-PremAIR-350-CF-P · HRU-PremAIR-350E-CF-P · HRU-PremAIR-350E-P · HRU-PremAIR-450-P · HRU-PremAIR-450-CF-P · HRU-PremAIR-450E-P · HRU-PremAIR-450E-CF-P · HRU-PremAIR-500-P · HRU-PremAIR-500-CF-P · HRU-MinistAIR-L-250E-H-CF-P · HRU-MinistAIR-L-250E-H-P · HRU-MinistAIR-L-250-H-CF-P · HRU-MinistAIR-L-250-H-P · HRU-MinistAIR-L-325E-H-CF-P · HRU-MinistAIR-L-325E-H-P · HRU-MinistAIR-L-325-H-CF-P · HRU-MinistAIR-L-325-H-P · HRU-MinistAIR-L-350E-H-CF-P · HRU-MinistAIR-L-350E-H-P · HRU-MinistAIR-L-350-H-CF-P · HRU-MinistAIR-L-350-H-P · HRU-MinistAIR-LS-250E-H-CF-P · HRU-MinistAIR-LS-250E-H-P · HRU-MinistAIR-LS-250-H-CF-P · HRU-MinistAIR-LS-250-H-P · HRU-MinistAIR-LS-325E-H-CF-P · HRU-MinistAIR-LS-325E-H-P · HRU-MinistAIR-LS-325-H-CF-P · HRU-MinistAIR-LS-325-H-P · HRU-MinistAIR-LS-350E-H-CF-P · HRU-MinistAIR-LS-350E-H-P · HRU-MinistAIR-LS-350-H-CF-P · HRU-MinistAIR-LS-350-H-P · HRU-MinistAIR-R-250E-H-CF-P · HRU-MinistAIR-R-250E-H-P · HRU-MinistAIR-R-250-H-CF-P · HRU-MinistAIR-R-250-H-P · HRU-MinistAIR-R-325E-H-CF-P · HRU-MinistAIR-R-325E-H-P · HRU-MinistAIR-R-325-H-CF-P · HRU-MinistAIR-R-325-H-P · HRU-MinistAIR-R-350E-H-CF-P · HRU-MinistAIR-R-350E-H-P · HRU-MinistAIR-R-350-H-CF-P · HRU-MinistAIR-R-350-H-P · HRU-MinistAIR-RS-250E-H-CF-P · HRU-MinistAIR-RS-250E-H-P · HRU-MinistAIR-RS-250-H-CF-P · HRU-MinistAIR-RS-250-H-P · HRU-MinistAIR-RS-325E-H-CF-P · HRU-MinistAIR-RS-325E-H-P · HRU-MinistAIR-RS-325-H-CF-P · HRU-MinistAIR-RS-325-H-P · HRU-MinistAIR-RS-350E-H-CF-P · HRU-MinistAIR-RS-350E-H-P · HRU-MinistAIR-RS-350-H-CF-P · HRU-MinistAIR-RS-350-H-P · HRU-FlatAIR-80E-H-P · HRU-FlatAIR-80E-H-CF-P · HRU-FlatAIR-80-H-P · HRU-FlatAIR-80-H-CF-P · HRU-FlatAIR-100E-H-P · HRU-FlatAIR-100E-H-CF-P · HRU-FlatAIR-100-H-P · HRU-FlatAIR-100-H-CF-P · HRU-FlatAIR-120E-H-P · HRU-FlatAIR-120E-H-CF-P · HRU-FlatAIR-120-H-P · HRU-FlatAIR-120-H-CF-P · HRU-FlatAIR-125E-H-P · HRU-FlatAIR-125E-H-CF-P · HRU-FlatAIR-125-H-P · HRU-FlatAIR-125-H-CF-P · HRU-FlatAIR-150E-H-P · HRU-FlatAIR-150E-H-CF-P · HRU-FlatAIR-150-H-P · HRU-FlatAIR-150-H-CF-P · HRU-FlatAIR-200E-H-P · HRU-FlatAIR-200E-H-CF-P · HRU-FlatAIR-200-H-P · HRU-FlatAIR-200-H-CF-P · HRU-FlatAIR-225E-H-P · HRU-FlatAIR-225E-H-CF-P · HRU-FlatAIR-225-H-P · HRU-FlatAIR-225-H-CF-P · HRU-FlatAIR-250E-H-P · HRU-FlatAIR-250E-H-CF-P · HRU-FlatAIR-250-H-P · HRU-FlatAIR-250-H-CF-P
Last updated

Registers (49)

49 read, 23 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Error Status (R)Read
Work Mode (RW)Read and write
Exhaust temperature sensor (R)°CRead
Extract temperature sensor (R)°CRead
Inlet temperature sensor (R)°CRead
Supply temperature sensor (R)°CRead
Pre-heater thermostat (R)Read
Afterheater thermostat (R)Read
Bypass status (R)Read
SAP signal (R)Read
Pre-heater status (R)Read
Afterhater status (R)Read
Bypass position (R)%Read
Time Mode OUT (RW)Read and write
Time Mode PARTY (RW)Read and write
Fireplace Mode (RW)Read and write
Supply fan speed (R)%Read
Exhaust fan speed (R)%Read
Supply fan speed - Speed 1 (RW)%Read and write
Supply fan speed - Speed 2 (RW)%Read and write
Supply fan speed - Speed 3 (RW)%Read and write
Exhaust fan speed - Speed 2 (RW)%Read and write
Exhaust fan speed - Speed 3 (RW)%Read and write
Exhaust fan speed - Speed 1 (RW)%Read and write
Flow setpoint supply (R)m³/hRead
Supply fan flow - Speed 2 (RW)m³/hRead and write
Flow setpoint exhaust (R)m³/hRead
Flow reading supply (R)m³/hRead
Flow reading exhaust (R)m³/hRead
Supply fan flow - Speed 1 (RW)m³/hRead and write
Supply fan flow - Speed 3 (RW)m³/hRead and write
Exhaust fan flow - Speed 1 (RW)m³/hRead and write
Exhaust fan flow - Speed 2 (RW)m³/hRead and write
Exhaust fan flow - Speed 3 (RW)m³/hRead and write
GHE status (R)Read
GHE mode (RW)Read and write
GHE winter temperature (RW)°CRead and write
GHE summer temperature (RW)°CRead and write
Filter alarm (R)Read
Turn ON/OFF (RW)Read and write
Supply filter days left (R)daysRead
Exhaust filter days left (R)daysRead
Supply air filter - depletion (R)%Read
Exhaust air filter - depletion (R)%Read
Reset filter counting (RW)Read and write
Bypass control (RW)Read and write
Airing time mode (RW)Read and write
Humidity indoor (R)%Read
CO2 indoor (R)ppmRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor supply and exhaust temperatures on a live dashboard to verify heat recovery efficiency.
  • Create an alert when filter depletion reaches a critical level or remaining days drop below a threshold.
  • Remotely switch the ventilation work mode or turn the unit on and off without an on-site visit.
  • Track indoor CO2 and humidity trends over time to ensure healthy indoor air quality for occupants.
  • Adjust fan speed and airflow setpoints for Speed 1 through Speed 3 from the cloud during commissioning.
  • Log bypass position and GHE status to verify seasonal free-cooling operation.

Installation

  1. Connect the ModbusCloud Gateway to the HRU-P unit's PCB using the RS-485 A, B, and GND terminals, following the correct wiring structure for your model family (SlimAIR/PremAIR/MinistAIR or FlatAIR).

  2. Set the Modbus RTU baud rate on the gateway to 115200 to match the Alnor HRU-P default communication speed.

  3. Configure the Modbus slave address on the HRU-P unit and ensure it matches the address set in the ModbusCloud template.

  4. Import the Alnor HRU-P template from the ModbusCloud template library and assign it to the correct gateway and slave address.

  5. Verify communication by checking that live temperature, fan speed, and airflow readings appear on the ModbusCloud dashboard.

  6. Test write functionality by toggling the work mode or adjusting a fan speed setpoint and confirming the unit responds.

Things to watch for

Communication fails after wiring. What should I check first?

Verify the baud rate is set to 115200 on both the gateway and the HRU-P unit. Also confirm that the RS-485 A and B lines are not swapped and that a common GND connection is present.

Which wiring diagram should I use for my model?

HRU-SlimAIR-P, HRU-PremAIR-P, and HRU-MinistAIR-P models share one PCB connection structure. HRU-FlatAIR-P models use a different layout. Check the Alnor installation documentation for the correct pinout before connecting.

Can I connect multiple HRU-P units on the same RS-485 bus?

Yes, as long as each unit has a unique Modbus slave address. Make sure the total cable length and number of devices stay within RS-485 bus limits, and add a termination resistor at the end of the bus if needed.

Some sensor readings show zero or are missing. Why?

Not all HRU-P models include internal humidity or CO2 sensors. If a sensor is not physically present in the unit, the corresponding register will return zero or a default value. Confirm the sensor configuration of your specific model.

More Alnor Systemy Wentylacji Sp. z o. o. templates

Want to see how it works?