Atmoce Atmoce AC Battery and Module-Inverter Modbus RTU template

Atmoce AC Battery and Module-Inverter

Controls and monitors Atmoce module-inverters and AC coupled batteries via Modbus RTU.

This template provides full read and write access to Atmoce module-inverters and AC coupled batteries over Modbus RTU. It covers PV output, grid power, battery state of charge, energy counters, and active control of charging and discharging modes.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
38, read and write
Brand
Atmoce
Key readings
PV Power Output · Energy Storage Charging/Discharging Power · Grid Active Power · Energy Storage SOC · Grid Phase A-C Voltage and Current · Cumulative PV Generation
Available commands
Energy Storage Communication Control Mode · Active Power Fixed/Percentage Regulation · Forced Charging/Discharging Mode and Target SOC · Forced Charging/Discharging Duration
Last updated

Registers (38)

38 read, 7 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Rated Photovoltaic PowerkWRead
Energy Storage CapacitykWhRead
Rated Energy Storage PowerkWRead
Power Station StatusRead
Energy Storage StatusRead
Energy Storage Operating modeRead
Photovoltaic Power OutputkWRead
Energy Storage Charging/Discharging PowerkWRead
Grid Active PowerkWRead
PV Reactive PowerkVARead
Energy Storage Reactive PowerkVARead
Grid Phase C CurrentARead
Grid Phase A VoltageVRead
Grid Phase A CurrentARead
Grid Phase B VoltageVRead
Grid Phase C VoltageVRead
Grid Phase B CurrentARead
Energy Storage SOC%Read
Cumulative Storage Charging CapacitykWhRead
Cumulative PV Power GenerationkWhRead
Daily Energy Storage Charging CapacitykWhRead
Cumulative Storage Discharging CapacitykWhRead
Daily Energy Storage Discharging CapacitykWhRead
Cumulative Electricity Sales VolumekWhRead
Daily Electricity Sales VolumekWhRead
Cumulative Electricity Purchase VolumekWhRead
Daily Electricity Purchase VolumekWhRead
Energy Storage Maximum Charging Power LimitkWRead
Energy Storage Maximum Discharging Power LimitkWRead
Energy Storage Communication Control ModeRead and write
Active Power Fixed Value RegulationkWRead and write
Energy Storage Forced Charging/Discharging%Read and write
Active Power Percentage Regulation%Read and write
Energy Storage Forced Charged/Discharging Mode%Read and write
Energy Storage Forced Charged/Discharging Target SOC%Read and write
Energy Storage Forced Charged/Discharging DurationminRead and write
Energy Storage Forced Charged/Discharging PowerkWRead
Energy Storage Dispatch Charged/Discharging PowerkWRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor real-time PV power output and battery state of charge on a cloud dashboard for each customer site.
  • Create alerts when energy storage SOC drops below a defined threshold during peak tariff hours.
  • Remotely configure forced charging schedules to take advantage of low electricity rates overnight.
  • Track cumulative PV generation over time to verify system performance against design expectations.
  • Regulate active power output remotely to comply with grid feed-in limitations set by the utility.
  • Manage multiple Atmoce inverter and battery systems across different sites from a single platform.

Installation

  1. Connect the Modbus RTU wiring (A and B terminals) from the Atmoce module-inverter to the RS485 port on your ModbusCloud Gateway.

  2. Configure the Modbus RTU settings on the gateway to 19200 baud rate with odd parity (parity 1) and set the correct slave address matching the inverter configuration.

  3. Verify that Modbus RTU communication is enabled on the Atmoce inverter, checking the device manual for the relevant setting menu.

  4. Import the Atmoce AC Battery and Module-Inverter template from the ModbusCloud template library into your project.

  5. Confirm that register data is arriving correctly by checking live values in the ModbusCloud dashboard, paying attention to uint32 and int32 register alignment starting at address 60027.

  6. Test write functionality by sending a minor control command, such as adjusting the active power percentage, and verifying the inverter responds as expected.

Things to watch for

Why am I reading incorrect or zero values for PV power and grid power?

Registers use uint32 and int32 data types spanning two consecutive addresses starting at 60027. Ensure your gateway is configured for 32-bit register reads with the correct byte and word order. A mismatch will produce zero or nonsensical values.

The gateway cannot establish communication with the Atmoce inverter. What should I check?

Verify that the baud rate is set to 19200 and parity is set to odd (1 stop bit). Also confirm the RS485 A and B wiring is not swapped and that the correct Modbus slave address is configured on both the inverter and the gateway.

Can I read and write the forced charge and discharge registers at the same time?

Yes, several registers including forced charge/discharge mode, target SOC, and duration are both readable and writable. You can read current settings and update them remotely through the ModbusCloud platform.

Do I need a specific firmware version on the Atmoce inverter for Modbus RTU support?

Consult the Atmoce product documentation or contact their support to confirm that your inverter firmware supports the Modbus RTU register map used by this template. Older firmware versions may not expose all registers.