Bender ISOMETER iso685
Insulation monitoring device for unearthed IT AC and DC systems with alarm relays and fault location.
The Bender ISOMETER iso685 is an insulation monitoring device that measures the insulation resistance of unearthed IT AC and DC systems in hospitals, data centres, ships and PV plants. This Modbus TCP template reads insulation resistance, voltages, alarm states and fault location values, and lets you set response values, profile and relays from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 343, read and write
- Brand
- Bender
- Key readings
- Insulation resistance · Minimum insulation resistance · Leakage capacitance · System voltage · System frequency · DC offset · Alarm status · Measurement quality
- Available commands
- Response value 1 and 2 · Measuring profile · Relay functions · Test and reset · Device on or off
- Compatible models
- iso685-D · iso685-S · iso685W-D · isoRW685W-D · iso685-D-B · iso685-D-P · isoHR685-D-I-B
- Last updated
Registers (343)
330 read, 108 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Insulation Resistance | Ω | Read | |||
| Minimum Insulation Resistance | Ω | Read | |||
| System Leakage Capacitance | Read | ||||
| Voltage L1 L2 | V | Read | |||
| Voltage L1 L3 | V | Read | |||
| Voltage L2 L3 | V | Read | |||
| Voltage L1 PE | V | Read | |||
| Voltage L2 PE | V | Read | |||
| Voltage L3 PE | V | Read | |||
| System Frequency | Hz | Read | |||
| Coupling To System | Read | ||||
| Coupling To Earth | Read | ||||
| Device Error | Read | ||||
| Device Inactive | Read | ||||
| DC Offset | % | Read | |||
| Measurement Quality | % | Read | |||
| Symmetrical Alarm | % | Read | |||
| DC Minus Alarm | % | Read | |||
| DC Plus Alarm | % | Read | |||
| Measuring Pulse Duration | % | Read | |||
| Voltage DC PE | V | Read | |||
| Locating Current Positive | A | Read | |||
| Locating Current Negative | A | Read | |||
| PGH Start Condition | Read | ||||
| Alarm Status | Read | ||||
| IO State | Read | ||||
| Measured Value Counter | Read and write | ||||
| Channel 1 Number | Read | ||||
| Channel 1 Insulation Resistance | Ω | Read | |||
| Channel 1 Test And Alarm Status | Read | ||||
| Channel 1 Range And Unit | Read | ||||
| Channel 2 Number | Read | ||||
| Channel 2 Insulation Resistance 2 | Ω | Read | |||
| Channel 2 Test And Alarm Status | Read | ||||
| Channel 2 Range And Unit | Read | ||||
| Channel 3 Number | Read | ||||
| Channel 3 System Leakage Capacitance | Read | ||||
| Channel 3 Test And Alarm Status | Read | ||||
| Channel 3 Range And Unit | Read | ||||
| Channel 4 Number | Read | ||||
| Channel 4 Voltage L1 L2 | V | Read | |||
| Channel 4 Test And Alarm Status | Read | ||||
| Channel 4 Range And Unit | Read | ||||
| Channel 5 Number | Read | ||||
| Channel 5 Voltage L1 L3 | V | Read | |||
| Channel 5 Test And Alarm Status | Read | ||||
| Channel 5 Range And Unit | Read | ||||
| Channel 6 Number | Read | ||||
| Channel 6 Voltage L2 L3 | V | Read | |||
| Channel 6 Test And Alarm Status | Read | ||||
| Channel 6 Range And Unit | Read | ||||
| Channel 7 Number | Read | ||||
| Channel 7 Voltage L1 PE | V | Read | |||
| Channel 7 Test And Alarm Status | Read | ||||
| Channel 7 Range And Unit | Read | ||||
| Channel 8 Number | Read | ||||
| Channel 8 Voltage L2 PE | V | Read | |||
| Channel 8 Test And Alarm Status | Read | ||||
| Channel 8 Range And Unit | Read | ||||
| Channel 9 Number | Read | ||||
| Channel 9 Voltage L3 PE | V | Read | |||
| Channel 9 Test And Alarm Status | Read | ||||
| Channel 9 Range And Unit | Read | ||||
| Channel 10 Number | Read | ||||
| Channel 10 System Frequency | Hz | Read | |||
| Channel 10 Test And Alarm Status | Read | ||||
| Channel 10 Range And Unit | Read | ||||
| Channel 11 Number | Read | ||||
| Channel 11 Coupling To System | Read | ||||
| Channel 11 Test And Alarm Status | Read | ||||
| Channel 11 Range And Unit | Read | ||||
| Channel 12 Number | Read | ||||
| Channel 12 Coupling To Earth | Read | ||||
| Channel 12 Test And Alarm Status | Read | ||||
| Channel 12 Range And Unit | Read | ||||
| Channel 13 Number | Read | ||||
| Channel 13 Device Error | Read | ||||
| Channel 13 Test And Alarm Status | Read | ||||
| Channel 13 Range And Unit | Read | ||||
| Channel 14 Number | Read | ||||
| Channel 14 Device Status | Read | ||||
| Channel 14 Test And Alarm Status | Read | ||||
| Channel 14 Range And Unit | Read | ||||
| Channel 15 Number | Read | ||||
| Channel 15 DC Offset | % | Read | |||
| Channel 15 Test And Alarm Status | Read | ||||
| Channel 15 Range And Unit | Read | ||||
| Channel 16 Number | Read | ||||
| Channel 16 Measurement Quality | % | Read | |||
| Channel 16 Test And Alarm Status | Read | ||||
| Channel 16 Range And Unit | Read | ||||
| Channel 17 Number | Read | ||||
| Channel 17 Minimum Insulation Resistance | Ω | Read | |||
| Channel 17 Test And Alarm Status | Read | ||||
| Channel 17 Range And Unit | Read | ||||
| Channel 18 Number | Read | ||||
| Channel 18 Symmetrical Alarm | % | Read | |||
| Channel 18 Test And Alarm Status | Read | ||||
| Channel 18 Range And Unit | Read | ||||
| Channel 19 Number | Read | ||||
| Channel 19 DC Minus Alarm | % | Read | |||
| Channel 19 Test And Alarm Status | Read | ||||
| Channel 19 Range And Unit | Read | ||||
| Channel 20 Number | Read | ||||
| Channel 20 DC Plus Alarm | % | Read | |||
| Channel 20 Test And Alarm Status | Read | ||||
| Channel 20 Range And Unit | Read | ||||
| Channel 21 Number | Read | ||||
| Channel 21 ISOnet Device Timeout | Read | ||||
| Channel 21 Test And Alarm Status | Read | ||||
| Channel 21 Range And Unit | Read | ||||
| Channel 22 Number | Read | ||||
| Channel 22 ISOnet Devices Incomplete | Read | ||||
| Channel 22 Test And Alarm Status | Read | ||||
| Channel 22 Range And Unit | Read | ||||
| Channel 23 Number | Read | ||||
| Channel 23 General ISOnet Fault | Read | ||||
| Channel 23 Test And Alarm Status | Read | ||||
| Channel 23 Range And Unit | Read | ||||
| Channel 24 Number | Read | ||||
| Channel 24 DC Offset Voltage To Earth | V | Read | |||
| Channel 24 Test And Alarm Status | Read | ||||
| Channel 24 Range And Unit | Read | ||||
| Channel 25 Number | Read | ||||
| Channel 25 Active EDS Channels | Read | ||||
| Channel 25 Test And Alarm Status | Read | ||||
| Channel 25 Range And Unit | Read | ||||
| Channel 26 Number | Read | ||||
| Channel 26 EDS Alarms | Read | ||||
| Channel 26 Test And Alarm Status | Read | ||||
| Channel 26 Range And Unit | Read | ||||
| Channel 27 Number | Read | ||||
| Channel 27 RCM Alarms | Read | ||||
| Channel 27 Test And Alarm Status | Read | ||||
| Channel 27 Range And Unit | Read | ||||
| Channel 28 Number | Read | ||||
| Channel 28 First Offline Device | Read | ||||
| Channel 28 Error Status | Read | ||||
| Channel 28 Value Validity | Read | ||||
| Channel 28 Text Number | Read | ||||
| Channel 28 Index To Text Number | Read | ||||
| Channel 28 Position Text Number | Read | ||||
| Channel 28 Index To Position Text | Read | ||||
| Channel 29 Number | Read | ||||
| Channel 29 First Offline Device | Read | ||||
| Channel 29 Error Status | Read | ||||
| Channel 29 Value Validity | Read | ||||
| Channel 29 Text Number | Read | ||||
| Channel 29 Index To Text Number | Read | ||||
| Channel 29 Position Text Number | Read | ||||
| Channel 29 Index To Position Text | Read | ||||
| PGH Current Set | A | Read | |||
| IdN Percentage 1 | % | Read | |||
| IdN Percentage 1 Channel | Read | ||||
| IdN Percentage 2 | % | Read | |||
| IdN Percentage 2 Channel | Read | ||||
| IdN Percentage 3 | % | Read | |||
| IdN Percentage 3 Channel | Read | ||||
| IdN Percentage 4 | % | Read | |||
| IdN Percentage 4 Channel | Read | ||||
| IdN Percentage 5 | % | Read | |||
| IdN Percentage 5 Channel | Read | ||||
| IdN Percentage 6 | % | Read | |||
| IdN Percentage 6 Channel | Read | ||||
| IdN Percentage 7 | % | Read | |||
| IdN Percentage 7 Channel | Read | ||||
| IdN Percentage 8 | % | Read | |||
| IdN Percentage 8 Channel | Read | ||||
| IdN Absolute 1 | A | Read | |||
| IdN Absolute 1 Response Value | Read | ||||
| IdN Absolute 1 Maximum | A | Read | |||
| IdN Absolute 1 Channel | Read | ||||
| IdN Absolute 2 | A | Read | |||
| IdN Absolute 2 Response Value | Read | ||||
| IdN Absolute 2 Maximum | A | Read | |||
| IdN Absolute 2 Channel | Read | ||||
| IdN Absolute 3 | A | Read | |||
| IdN Absolute 3 Response Value | Read | ||||
| IdN Absolute 3 Maximum | A | Read | |||
| IdN Absolute 3 Channel | Read | ||||
| IdN Absolute 4 | A | Read | |||
| IdN Absolute 4 Response Value | Read | ||||
| IdN Absolute 4 Maximum | A | Read | |||
| IdN Absolute 4 Channel | Read | ||||
| IdN Absolute 5 | A | Read | |||
| IdN Absolute 5 Response Value | Read | ||||
| IdN Absolute 5 Maximum | A | Read | |||
| IdN Absolute 5 Channel | Read | ||||
| IdN Absolute 6 | A | Read | |||
| IdN Absolute 6 Response Value | Read | ||||
| IdN Absolute 6 Maximum | A | Read | |||
| IdN Absolute 6 Channel | Read | ||||
| IdN Absolute 7 | A | Read | |||
| IdN Absolute 7 Response Value | Read | ||||
| IdN Absolute 7 Maximum | A | Read | |||
| IdN Absolute 7 Channel | Read | ||||
| IdN Absolute 8 | A | Read | |||
| IdN Absolute 8 Response Value | Read | ||||
| IdN Absolute 8 Maximum | A | Read | |||
| IdN Absolute 8 Channel | Read | ||||
| IdL Value 1 | A | Read | |||
| IdL Value 1 Response Value | A | Read | |||
| IdL Value 1 Channel | Read | ||||
| IdL Value 2 | A | Read | |||
| IdL Value 2 Response Value | A | Read | |||
| IdL Value 2 Channel | Read | ||||
| IdL Value 3 | A | Read | |||
| IdL Value 3 Response Value | A | Read | |||
| IdL Value 3 Channel | Read | ||||
| IdL Value 4 | A | Read | |||
| IdL Value 4 Response Value | A | Read | |||
| IdL Value 4 Channel | Read | ||||
| IdL Value 5 | A | Read | |||
| IdL Value 5 Response Value | A | Read | |||
| IdL Value 5 Channel | Read | ||||
| IdL Value 6 | A | Read | |||
| IdL Value 6 Response Value | A | Read | |||
| IdL Value 6 Channel | Read | ||||
| IdL Value 7 | A | Read | |||
| IdL Value 7 Response Value | A | Read | |||
| IdL Value 7 Channel | Read | ||||
| IdL Value 8 | A | Read | |||
| IdL Value 8 Response Value | A | Read | |||
| IdL Value 8 Channel | Read | ||||
| MAC Address | Read | ||||
| Current IP Address | Read | ||||
| DHCP | Read and write | ||||
| IP Address | Read and write | ||||
| Standard Gateway | Read and write | ||||
| Subnet Mask | Read and write | ||||
| Modbus TCP | Read and write | ||||
| Register Write Access | Read and write | ||||
| ISOnet | Read and write | ||||
| ISOnet Devices | Read and write | ||||
| BCOM System Name | Read and write | ||||
| BCOM Subsystem Address | Read and write | ||||
| BCOM Device Address | Read and write | ||||
| BCOM Messages Timeout | s | Read and write | |||
| BCOM Repetition Interval | s | Read and write | |||
| BCOM Percentage Change | % | Read and write | |||
| DNS Server IP | Read and write | ||||
| DNS Domain | Read and write | ||||
| Time | Read and write | ||||
| Time Zone | h | Read and write | |||
| NTP | Read and write | ||||
| NTP Server IP | Read and write | ||||
| Date Format | Read and write | ||||
| Summertime | Read and write | ||||
| Time Format | Read and write | ||||
| BS Bus Address | Read and write | ||||
| Digital Input 1 Function | Read and write | ||||
| Digital Input 1 Mode | Read and write | ||||
| Digital Input 1 T On | s | Read and write | |||
| Digital Input 1 T Off | s | Read and write | |||
| Digital Input 2 Function | Read and write | ||||
| Digital Input 2 Mode | Read and write | ||||
| Digital Input 2 T On | s | Read and write | |||
| Digital Input 2 T Off | s | Read and write | |||
| Digital Input 3 Function | Read and write | ||||
| Digital Input 3 Mode | Read and write | ||||
| Digital Input 3 T On | s | Read and write | |||
| Digital Input 3 T Off | s | Read and write | |||
| Digital Output 1 Function 1 | Read and write | ||||
| Digital Output 1 Function 2 | Read and write | ||||
| Digital Output 1 Function 3 | Read and write | ||||
| Digital Output 1 Mode | Read and write | ||||
| Digital Output 1 Test | Read and write | ||||
| Digital Output 2 Function 1 | Read and write | ||||
| Digital Output 2 Function 2 | Read and write | ||||
| Digital Output 2 Function 3 | Read and write | ||||
| Digital Output 2 Mode | Read and write | ||||
| Digital Output 2 Test | Read and write | ||||
| Analogue Output Function | Read and write | ||||
| Analogue Output Mode | Read and write | ||||
| Analogue Output Midscale | Read and write | ||||
| Analogue Output Test | Read and write | ||||
| Buzzer Function 1 | Read and write | ||||
| Buzzer Function 2 | Read and write | ||||
| Buzzer Function 3 | Read and write | ||||
| Buzzer Test | Read and write | ||||
| Relay 1 Test | Read and write | ||||
| Relay 1 Operating Mode | Read and write | ||||
| Relay 1 Function 1 | Read and write | ||||
| Relay 1 Function 2 | Read and write | ||||
| Relay 1 Function 3 | Read and write | ||||
| Relay 2 Test | Read and write | ||||
| Relay 2 Operating Mode | Read and write | ||||
| Relay 2 Function 1 | Read and write | ||||
| Relay 2 Function 2 | Read and write | ||||
| Relay 2 Function 3 | Read and write | ||||
| Response Value 1 | Ω | Read and write | |||
| Response Value 2 | Ω | Read and write | |||
| System Type | Read and write | ||||
| Profile | Read and write | ||||
| Coupling Monitoring | Read and write | ||||
| Coupling Device | Read and write | ||||
| Fault Memory | Read and write | ||||
| Start Up Delay | s | Read and write | |||
| Activate Device | Read and write | ||||
| DC Alarm Value | V | Read and write | |||
| DC Alarm | Read and write | ||||
| EDS Current | Read and write | ||||
| EDS Mode | Read and write | ||||
| Portable EDS | Read and write | ||||
| RS485 Protocol | Read and write | ||||
| IsoData Mode | Read and write | ||||
| ISOsync | Read and write | ||||
| EDSsync | Read and write | ||||
| ISOloop | Read and write | ||||
| Share ISOloop Measured Value | Read and write | ||||
| Modbus RTU Address | Read and write | ||||
| Modbus RTU Baud Rate | Read and write | ||||
| Modbus RTU Parity | Read and write | ||||
| Modbus RTU Stop Bits | Read and write | ||||
| Scan Channels | Read and write | ||||
| Modbus RTU Master | Read and write | ||||
| EDSsync Failure Monitoring | Read and write | ||||
| EDSsync Configuration | Read and write | ||||
| EDSsync Reset | Read and write | ||||
| Behaviour When Inactive | Read and write | ||||
| Test Command | Write | ||||
| Reset Command | Write | ||||
| Factory Settings Command | Write | ||||
| Initial Measurement Start | Write | ||||
| EDS Start | Write | ||||
| EDS Stop | Write | ||||
| Request ISOnet Priority | Write | ||||
| Yield ISOnet Priority | Write | ||||
| Start EDS Scan | Write | ||||
| Acknowledge EDS Failure | Write | ||||
| Save Parameter | Write | ||||
| Restore Parameter | Write | ||||
| Reset EDSsync Participants | Write | ||||
| Device Model | Read | ||||
| Article Number | Read | ||||
| Serial Number | Read | ||||
| Manufacturer | Read | ||||
| Interface D Number | Read | ||||
| Interface Software Version | Read | ||||
| Measurement D Number | Read | ||||
| Measurement Software Version | Read | ||||
| FP200 D Number | Read | ||||
| FP200 Software Version | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show insulation resistance of every IT system on one dashboard and compare it over months.
- Get an email alert when the insulation resistance drops below a threshold you choose.
- Alert on the alarm status register so a pre-warning reaches the maintenance team before a second fault.
- Track leakage capacitance and DC offset to see where an insulation fault starts.
- Adjust response value 1 and 2 from ModbusCloud after a change in the installation.
Installation
Connect the Ethernet port of the iso685 to the same network as the ModbusCloud Gateway, or directly to its LAN port.
Note the IP address and the BCOM device address in the device menu or the COMTRAXX web interface, and check that Modbus TCP is on.
In ModbusCloud, add a Modbus TCP device with that IP address, port 502 and the BCOM device address as unit ID, and import this template.
Check that Insulation Resistance and the system voltages match the device display.
Things to watch for
The device does not answer on Modbus TCP. What should I check?
Check that Modbus TCP is switched on in the device, that the IP address is reachable from the ModbusCloud Gateway and that the unit ID matches the BCOM device address. The device handles a limited number of requests per second, so avoid reading it from several systems at the same time.
Why does insulation resistance show a very large number?
In a healthy IT system the insulation resistance can be many megaohm. Look at the range and unit register of the channel as well: it tells whether the value is exact, smaller than or larger than the shown value, or invalid.
Some registers return zero or an error. Is that normal?
Yes. Fault location, ISOnet, ISOloop and EDS values exist only in certain variants, such as the P version with EDS fault locators. On a standard iso685-D these registers stay empty.
What should I know before writing settings?
Register write access must be set to allow on the device, and the device only accepts writes with function 16. A wrong response value or profile changes when the device alarms, so agree changes with the owner. The test and reset commands only act on the documented values 64260 and 65025.
More Bender templates