Bio Instruments Bio Instruments SF-xT-485M Modbus RTU template

Bio Instruments SF-xT-485M

Phyto-Sensor sap flow sensor for leaf petioles and small shoots, read over RS485.

The Bio Instruments SF-xT-485M is a Phyto-Sensor sap flow sensor that tracks relative changes in sap flow in a leaf petiole or small shoot, used for crop monitoring in greenhouses. This Modbus RTU template reads the relative sap flow and the communication settings, and lets you change the address, baud rate and parity from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
5, read and write
Key readings
Relative sap flow · Modbus address · Baud rate · Parity
Available commands
Modbus address · Baud rate · Parity
Compatible models
SF-4T-485M · SF-5T-485M
Last updated

Registers (5)

5 read, 3 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Sap FlowRead
Sap Flow FloatRead
Device AddressRead and write
Baud Rate CodeRead and write
Parity CodeRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Plot relative sap flow next to irrigation and greenhouse climate data on one dashboard to see how the crop responds during the day.
  • Get an email or webhook when sap flow drops below a threshold you choose, for example after an irrigation fault.
  • Keep 365 days of sap flow history to compare days, crop stages and irrigation strategies.
  • Let automatic monitoring flag a sap flow value that stays exactly the same for hours.
  • Give each sensor its own address from ModbusCloud before you add more sensors to the same RS485 line.

Installation

  1. Mount the probe on a petiole or small shoot with the red mark pointing in the direction of the upward sap flow, and wrap it completely in two or three layers of aluminium foil.

  2. Connect black to ground, yellow to RS485 B and white to RS485 A of the ModbusCloud Gateway, and red to a 5 to 24 Vdc supply. Terminate both ends of the bus with 120 Ω.

  3. Give every sensor on the bus its own address with the Bio Instruments address tool or by writing Device Address. All sensors leave the factory with address 247.

  4. In ModbusCloud, add a Modbus device with protocol RTU, the sensor address, 9600 baud and 8E1, and import this template.

  5. Allow 15 minutes of warm-up, then check that Sap Flow shows a value between 0 and 2.

Things to watch for

The sensor does not answer. What should I check?

Check 9600 baud, even parity, 1 stop bit and address 247 in ModbusCloud; many tools default to no parity. Swap A and B if nothing comes back, connect the black ground wire to the bus ground, and terminate both ends of the bus, because the sensor has no termination resistor inside.

Sap flow reads about 0.4 and hardly changes. Is that normal?

The output has a zero offset of about 0.4 relative units, so read changes against the course of the day rather than the absolute number. If it stays flat, check that the red mark points upward with the sap flow, that the foil covers the whole sensor and that the probe has had 15 minutes to warm up.

Why do I see every measured value twice?

The sensor gives each measurement as a scaled whole number and as a floating-point value. Both carry the same reading. Keep the one you want on your dashboards and remove the other from the Modbus device in ModbusCloud if you do not need it.

Can I change the address, baud rate or parity from ModbusCloud?

Yes, these three registers are writable. Writing is off per gateway by default; request it for the gateway in the portal. After a new address the sensor only answers on that address. Change baud rate or parity only when every device on the bus gets the same setting, and update the Modbus device in ModbusCloud right away.

Want to see how it works?

Electrician working in an open distribution board