Eliwell IDPlus 974
Refrigeration controller for compressor, defrost and evaporator fans with three probes and HACCP alarms.
The Eliwell IDPlus 974 is a refrigeration controller that switches the compressor, defrost and evaporator fans of cold rooms and display cabinets. This Modbus RTU template reads the probe temperatures, alarms and relay status and lets you start a defrost, switch to economy or standby and change setpoints from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 583, read and write
- Brand
- Eliwell
- Key readings
- Cabinet temperature · Evaporator temperature · Probe 3 temperature · Compressor status · Defrost status · Active alarms
- Available commands
- Setpoint · Manual defrost · Economy mode · Standby · Alarm limits
- Compatible models
- IDPlus 974 · IDPlus 971 · IDPlus 961 · IDPlus 902 · IDPlus 978
- Last updated
Registers (583)
582 read, 570 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Probe 1 Temperature | °C | Read | |||
| Probe 2 Temperature | °C | Read | |||
| Probe 3 Temperature | °C | Read | |||
| Alarm Word 1 | Read | ||||
| Alarm Word 2 | Read | ||||
| Alarm Word 3 | Read | ||||
| Mode Status Word | Read | ||||
| Compressor Defrost Status Word | Read | ||||
| Fan Status Word | Read | ||||
| Alarm Present Word | Read | ||||
| Door Status Word | Read | ||||
| Digital Input Word | Read | ||||
| Command Word | Read and write | ||||
| Command Window Timer | s | Write | |||
| Setpoint | °C | Read and write | |||
| Compressor Differential | °C | Read and write | |||
| Setpoint Maximum | °C | Read and write | |||
| Setpoint Minimum | °C | Read and write | |||
| Economy Setpoint Offset | °C | Read and write | |||
| Control Mode | Read and write | ||||
| Compressor On Time Probe Fault | min | Read and write | |||
| Compressor Off Time Probe Fault | min | Read and write | |||
| Compressor Start Delay | s | Read and write | |||
| Compressor Minimum Off Time | min | Read and write | |||
| Delay Between Compressor Starts | min | Read and write | |||
| Output Delay At Power On | min | Read and write | |||
| Deep Cooling Setpoint | °C | Read and write | |||
| Deep Cooling Duration | min | Read and write | |||
| Defrost Delay After Deep Cooling | Read and write | ||||
| Defrost Type | Read and write | ||||
| Defrost Interval | h | Read and write | |||
| Defrost Interval Count Mode | Read and write | ||||
| First Defrost Delay | min | Read and write | |||
| Defrost Timeout | min | Read and write | |||
| Defrost End Temperature | °C | Read and write | |||
| Defrost At Start Up | Read and write | ||||
| Fan Stop Temperature | °C | Read and write | |||
| Fan Differential | °C | Read and write | |||
| Fan Delay After Defrost | min | Read and write | |||
| Drip Time | min | Read and write | |||
| Fans Off During Defrost | Read and write | ||||
| Fans At Compressor Off | Read and write | ||||
| Fan On Time Day Cycle | min | Read and write | |||
| Fan Off Time Day Cycle | min | Read and write | |||
| Fan On Time Night Cycle | Read and write | ||||
| Fan Off Time Night Cycle | Read and write | ||||
| Night Mode Fans | Read and write | ||||
| Alarm Threshold Mode | Read and write | ||||
| Alarm Differential | °C | Read and write | |||
| High Temperature Alarm | °C | Read and write | |||
| Low Temperature Alarm | °C | Read and write | |||
| Alarm Delay After Power On | h | Read and write | |||
| Alarm Delay After Defrost | min | Read and write | |||
| Alarm Delay After Door Closed | h | Read and write | |||
| Door Open Alarm Delay | min | Read and write | |||
| Temperature Alarm Delay | min | Read and write | |||
| Defrost Timeout Alarm | Read and write | ||||
| External Alarm Locks Controller | Read and write | ||||
| Probe 3 Alarm Setpoint | °C | Read and write | |||
| Probe 3 Alarm Differential | °C | Read and write | |||
| Door Input Disables Loads | Read and write | ||||
| Digital Input Delay | min | Read and write | |||
| Compressor Off Delay Door Open | min | Read and write | |||
| Aux Output On Door Open | Read and write | ||||
| Pressure Switch Error Count | Read and write | ||||
| Pressure Switch Count Interval | min | Read and write | |||
| Compressor Delay After Pressure Switch | min | Read and write | |||
| Protocol Selection | Read and write | ||||
| Address Index In Family | Read and write | ||||
| Address Family | Read and write | ||||
| Modbus Parity | Read and write | ||||
| Modbus Stop Bits | Read and write | ||||
| Keypad Lock | Read and write | ||||
| Password User Level | Read and write | ||||
| Password Installer Level | Read and write | ||||
| Decimal Point Display | Read and write | ||||
| Probe 1 Calibration | °C | Read and write | |||
| Probe 2 Calibration | °C | Read and write | |||
| Probe 3 Calibration | °C | Read and write | |||
| Display During Defrost | Read and write | ||||
| Display Lock Timeout | min | Read and write | |||
| Temperature Unit | Read and write | ||||
| Main Display Value | Read and write | ||||
| HACCP High Threshold | °C | Read and write | |||
| HACCP Low Threshold | °C | Read and write | |||
| HACCP Alarm Delay | min | Read and write | |||
| HACCP Alarm Reset Time | h | Read and write | |||
| HACCP Enable | Read and write | ||||
| HACCP Alarm Exclusion Time | min | Read and write | |||
| Probe Type | Read and write | ||||
| Digital Input 1 Function | Read and write | ||||
| Digital Input 2 Function | Read and write | ||||
| Digital Output 1 Function | Read and write | ||||
| Digital Output 2 Function | Read and write | ||||
| Digital Output 3 Function | Read and write | ||||
| Digital Output 4 Function | Read and write | ||||
| Buzzer | Read and write | ||||
| Up Key Function | Read and write | ||||
| Down Key Function | Read and write | ||||
| Evaporator Probe Present | Read and write | ||||
| Probe 3 Present | Read and write | ||||
| AP1 Setpoint | °C | Read and write | |||
| AP1 Compressor Differential | °C | Read and write | |||
| AP1 Setpoint Maximum | °C | Read and write | |||
| AP1 Setpoint Minimum | °C | Read and write | |||
| AP1 Economy Setpoint Offset | °C | Read and write | |||
| AP1 Control Mode | Read and write | ||||
| AP1 Compressor On Time Probe Fault | min | Read and write | |||
| AP1 Compressor Off Time Probe Fault | min | Read and write | |||
| AP1 Compressor Start Delay | s | Read and write | |||
| AP1 Compressor Minimum Off Time | min | Read and write | |||
| AP1 Delay Between Compressor Starts | min | Read and write | |||
| AP1 Output Delay At Power On | min | Read and write | |||
| AP1 Deep Cooling Setpoint | °C | Read and write | |||
| AP1 Deep Cooling Duration | min | Read and write | |||
| AP1 Defrost Delay After Deep Cooling | Read and write | ||||
| AP1 Defrost Type | Read and write | ||||
| AP1 Defrost Interval | h | Read and write | |||
| AP1 Defrost Interval Count Mode | Read and write | ||||
| AP1 First Defrost Delay | min | Read and write | |||
| AP1 Defrost Timeout | min | Read and write | |||
| AP1 Defrost End Temperature | °C | Read and write | |||
| AP1 Defrost At Start Up | Read and write | ||||
| AP1 Fan Stop Temperature | °C | Read and write | |||
| AP1 Fan Differential | °C | Read and write | |||
| AP1 Fan Delay After Defrost | min | Read and write | |||
| AP1 Drip Time | min | Read and write | |||
| AP1 Fans Off During Defrost | Read and write | ||||
| AP1 Fans At Compressor Off | Read and write | ||||
| AP1 Fan On Time Day Cycle | min | Read and write | |||
| AP1 Fan Off Time Day Cycle | min | Read and write | |||
| AP1 Fan On Time Night Cycle | Read and write | ||||
| AP1 Fan Off Time Night Cycle | Read and write | ||||
| AP1 Night Mode Fans | Read and write | ||||
| AP1 Alarm Threshold Mode | Read and write | ||||
| AP1 Alarm Differential | °C | Read and write | |||
| AP1 High Temperature Alarm | °C | Read and write | |||
| AP1 Low Temperature Alarm | °C | Read and write | |||
| AP1 Alarm Delay After Power On | h | Read and write | |||
| AP1 Alarm Delay After Defrost | min | Read and write | |||
| AP1 Alarm Delay After Door Closed | h | Read and write | |||
| AP1 Door Open Alarm Delay | min | Read and write | |||
| AP1 Temperature Alarm Delay | min | Read and write | |||
| AP1 Defrost Timeout Alarm | Read and write | ||||
| AP1 External Alarm Locks Controller | Read and write | ||||
| AP1 Probe 3 Alarm Setpoint | °C | Read and write | |||
| AP1 Probe 3 Alarm Differential | °C | Read and write | |||
| AP1 Door Input Disables Loads | Read and write | ||||
| AP1 Digital Input Delay | min | Read and write | |||
| AP1 Compressor Off Delay Door Open | min | Read and write | |||
| AP1 Aux Output On Door Open | Read and write | ||||
| AP1 Pressure Switch Error Count | Read and write | ||||
| AP1 Pressure Switch Count Interval | min | Read and write | |||
| AP1 Compressor Delay After Pressure Switch | min | Read and write | |||
| AP1 Keypad Lock | Read and write | ||||
| AP1 Password User Level | Read and write | ||||
| AP1 Password Installer Level | Read and write | ||||
| AP1 Decimal Point Display | Read and write | ||||
| AP1 Probe 1 Calibration | °C | Read and write | |||
| AP1 Probe 2 Calibration | °C | Read and write | |||
| AP1 Probe 3 Calibration | °C | Read and write | |||
| AP1 Display During Defrost | Read and write | ||||
| AP1 Display Lock Timeout | min | Read and write | |||
| AP1 Temperature Unit | Read and write | ||||
| AP1 Main Display Value | Read and write | ||||
| AP1 HACCP High Threshold | °C | Read and write | |||
| AP1 HACCP Low Threshold | °C | Read and write | |||
| AP1 HACCP Alarm Delay | min | Read and write | |||
| AP1 HACCP Alarm Reset Time | h | Read and write | |||
| AP1 HACCP Enable | Read and write | ||||
| AP1 HACCP Alarm Exclusion Time | min | Read and write | |||
| AP1 Probe Type | Read and write | ||||
| AP1 Digital Input 1 Function | Read and write | ||||
| AP1 Digital Input 2 Function | Read and write | ||||
| AP1 Digital Output 1 Function | Read and write | ||||
| AP1 Digital Output 2 Function | Read and write | ||||
| AP1 Digital Output 3 Function | Read and write | ||||
| AP1 Digital Output 4 Function | Read and write | ||||
| AP1 Buzzer | Read and write | ||||
| AP1 Up Key Function | Read and write | ||||
| AP1 Down Key Function | Read and write | ||||
| AP1 Evaporator Probe Present | Read and write | ||||
| AP1 Probe 3 Present | Read and write | ||||
| AP2 Setpoint | °C | Read and write | |||
| AP2 Compressor Differential | °C | Read and write | |||
| AP2 Setpoint Maximum | °C | Read and write | |||
| AP2 Setpoint Minimum | °C | Read and write | |||
| AP2 Economy Setpoint Offset | °C | Read and write | |||
| AP2 Control Mode | Read and write | ||||
| AP2 Compressor On Time Probe Fault | min | Read and write | |||
| AP2 Compressor Off Time Probe Fault | min | Read and write | |||
| AP2 Compressor Start Delay | s | Read and write | |||
| AP2 Compressor Minimum Off Time | min | Read and write | |||
| AP2 Delay Between Compressor Starts | min | Read and write | |||
| AP2 Output Delay At Power On | min | Read and write | |||
| AP2 Deep Cooling Setpoint | °C | Read and write | |||
| AP2 Deep Cooling Duration | min | Read and write | |||
| AP2 Defrost Delay After Deep Cooling | Read and write | ||||
| AP2 Defrost Type | Read and write | ||||
| AP2 Defrost Interval | h | Read and write | |||
| AP2 Defrost Interval Count Mode | Read and write | ||||
| AP2 First Defrost Delay | min | Read and write | |||
| AP2 Defrost Timeout | min | Read and write | |||
| AP2 Defrost End Temperature | °C | Read and write | |||
| AP2 Defrost At Start Up | Read and write | ||||
| AP2 Fan Stop Temperature | °C | Read and write | |||
| AP2 Fan Differential | °C | Read and write | |||
| AP2 Fan Delay After Defrost | min | Read and write | |||
| AP2 Drip Time | min | Read and write | |||
| AP2 Fans Off During Defrost | Read and write | ||||
| AP2 Fans At Compressor Off | Read and write | ||||
| AP2 Fan On Time Day Cycle | min | Read and write | |||
| AP2 Fan Off Time Day Cycle | min | Read and write | |||
| AP2 Fan On Time Night Cycle | Read and write | ||||
| AP2 Fan Off Time Night Cycle | Read and write | ||||
| AP2 Night Mode Fans | Read and write | ||||
| AP2 Alarm Threshold Mode | Read and write | ||||
| AP2 Alarm Differential | °C | Read and write | |||
| AP2 High Temperature Alarm | °C | Read and write | |||
| AP2 Low Temperature Alarm | °C | Read and write | |||
| AP2 Alarm Delay After Power On | h | Read and write | |||
| AP2 Alarm Delay After Defrost | min | Read and write | |||
| AP2 Alarm Delay After Door Closed | h | Read and write | |||
| AP2 Door Open Alarm Delay | min | Read and write | |||
| AP2 Temperature Alarm Delay | min | Read and write | |||
| AP2 Defrost Timeout Alarm | Read and write | ||||
| AP2 External Alarm Locks Controller | Read and write | ||||
| AP2 Probe 3 Alarm Setpoint | °C | Read and write | |||
| AP2 Probe 3 Alarm Differential | °C | Read and write | |||
| AP2 Door Input Disables Loads | Read and write | ||||
| AP2 Digital Input Delay | min | Read and write | |||
| AP2 Compressor Off Delay Door Open | min | Read and write | |||
| AP2 Aux Output On Door Open | Read and write | ||||
| AP2 Pressure Switch Error Count | Read and write | ||||
| AP2 Pressure Switch Count Interval | min | Read and write | |||
| AP2 Compressor Delay After Pressure Switch | min | Read and write | |||
| AP2 Keypad Lock | Read and write | ||||
| AP2 Password User Level | Read and write | ||||
| AP2 Password Installer Level | Read and write | ||||
| AP2 Decimal Point Display | Read and write | ||||
| AP2 Probe 1 Calibration | °C | Read and write | |||
| AP2 Probe 2 Calibration | °C | Read and write | |||
| AP2 Probe 3 Calibration | °C | Read and write | |||
| AP2 Display During Defrost | Read and write | ||||
| AP2 Display Lock Timeout | min | Read and write | |||
| AP2 Temperature Unit | Read and write | ||||
| AP2 Main Display Value | Read and write | ||||
| AP2 HACCP High Threshold | °C | Read and write | |||
| AP2 HACCP Low Threshold | °C | Read and write | |||
| AP2 HACCP Alarm Delay | min | Read and write | |||
| AP2 HACCP Alarm Reset Time | h | Read and write | |||
| AP2 HACCP Enable | Read and write | ||||
| AP2 HACCP Alarm Exclusion Time | min | Read and write | |||
| AP2 Probe Type | Read and write | ||||
| AP2 Digital Input 1 Function | Read and write | ||||
| AP2 Digital Input 2 Function | Read and write | ||||
| AP2 Digital Output 1 Function | Read and write | ||||
| AP2 Digital Output 2 Function | Read and write | ||||
| AP2 Digital Output 3 Function | Read and write | ||||
| AP2 Digital Output 4 Function | Read and write | ||||
| AP2 Buzzer | Read and write | ||||
| AP2 Up Key Function | Read and write | ||||
| AP2 Down Key Function | Read and write | ||||
| AP2 Evaporator Probe Present | Read and write | ||||
| AP2 Probe 3 Present | Read and write | ||||
| AP3 Setpoint | °C | Read and write | |||
| AP3 Compressor Differential | °C | Read and write | |||
| AP3 Setpoint Maximum | °C | Read and write | |||
| AP3 Setpoint Minimum | °C | Read and write | |||
| AP3 Economy Setpoint Offset | °C | Read and write | |||
| AP3 Control Mode | Read and write | ||||
| AP3 Compressor On Time Probe Fault | min | Read and write | |||
| AP3 Compressor Off Time Probe Fault | min | Read and write | |||
| AP3 Compressor Start Delay | s | Read and write | |||
| AP3 Compressor Minimum Off Time | min | Read and write | |||
| AP3 Delay Between Compressor Starts | min | Read and write | |||
| AP3 Output Delay At Power On | min | Read and write | |||
| AP3 Deep Cooling Setpoint | °C | Read and write | |||
| AP3 Deep Cooling Duration | min | Read and write | |||
| AP3 Defrost Delay After Deep Cooling | Read and write | ||||
| AP3 Defrost Type | Read and write | ||||
| AP3 Defrost Interval | h | Read and write | |||
| AP3 Defrost Interval Count Mode | Read and write | ||||
| AP3 First Defrost Delay | min | Read and write | |||
| AP3 Defrost Timeout | min | Read and write | |||
| AP3 Defrost End Temperature | °C | Read and write | |||
| AP3 Defrost At Start Up | Read and write | ||||
| AP3 Fan Stop Temperature | °C | Read and write | |||
| AP3 Fan Differential | °C | Read and write | |||
| AP3 Fan Delay After Defrost | min | Read and write | |||
| AP3 Drip Time | min | Read and write | |||
| AP3 Fans Off During Defrost | Read and write | ||||
| AP3 Fans At Compressor Off | Read and write | ||||
| AP3 Fan On Time Day Cycle | min | Read and write | |||
| AP3 Fan Off Time Day Cycle | min | Read and write | |||
| AP3 Fan On Time Night Cycle | Read and write | ||||
| AP3 Fan Off Time Night Cycle | Read and write | ||||
| AP3 Night Mode Fans | Read and write | ||||
| AP3 Alarm Threshold Mode | Read and write | ||||
| AP3 Alarm Differential | °C | Read and write | |||
| AP3 High Temperature Alarm | °C | Read and write | |||
| AP3 Low Temperature Alarm | °C | Read and write | |||
| AP3 Alarm Delay After Power On | h | Read and write | |||
| AP3 Alarm Delay After Defrost | min | Read and write | |||
| AP3 Alarm Delay After Door Closed | h | Read and write | |||
| AP3 Door Open Alarm Delay | min | Read and write | |||
| AP3 Temperature Alarm Delay | min | Read and write | |||
| AP3 Defrost Timeout Alarm | Read and write | ||||
| AP3 External Alarm Locks Controller | Read and write | ||||
| AP3 Probe 3 Alarm Setpoint | °C | Read and write | |||
| AP3 Probe 3 Alarm Differential | °C | Read and write | |||
| AP3 Door Input Disables Loads | Read and write | ||||
| AP3 Digital Input Delay | min | Read and write | |||
| AP3 Compressor Off Delay Door Open | min | Read and write | |||
| AP3 Aux Output On Door Open | Read and write | ||||
| AP3 Pressure Switch Error Count | Read and write | ||||
| AP3 Pressure Switch Count Interval | min | Read and write | |||
| AP3 Compressor Delay After Pressure Switch | min | Read and write | |||
| AP3 Keypad Lock | Read and write | ||||
| AP3 Password User Level | Read and write | ||||
| AP3 Password Installer Level | Read and write | ||||
| AP3 Decimal Point Display | Read and write | ||||
| AP3 Probe 1 Calibration | °C | Read and write | |||
| AP3 Probe 2 Calibration | °C | Read and write | |||
| AP3 Probe 3 Calibration | °C | Read and write | |||
| AP3 Display During Defrost | Read and write | ||||
| AP3 Display Lock Timeout | min | Read and write | |||
| AP3 Temperature Unit | Read and write | ||||
| AP3 Main Display Value | Read and write | ||||
| AP3 HACCP High Threshold | °C | Read and write | |||
| AP3 HACCP Low Threshold | °C | Read and write | |||
| AP3 HACCP Alarm Delay | min | Read and write | |||
| AP3 HACCP Alarm Reset Time | h | Read and write | |||
| AP3 HACCP Enable | Read and write | ||||
| AP3 HACCP Alarm Exclusion Time | min | Read and write | |||
| AP3 Probe Type | Read and write | ||||
| AP3 Digital Input 1 Function | Read and write | ||||
| AP3 Digital Input 2 Function | Read and write | ||||
| AP3 Digital Output 1 Function | Read and write | ||||
| AP3 Digital Output 2 Function | Read and write | ||||
| AP3 Digital Output 3 Function | Read and write | ||||
| AP3 Digital Output 4 Function | Read and write | ||||
| AP3 Buzzer | Read and write | ||||
| AP3 Up Key Function | Read and write | ||||
| AP3 Down Key Function | Read and write | ||||
| AP3 Evaporator Probe Present | Read and write | ||||
| AP3 Probe 3 Present | Read and write | ||||
| AP4 Setpoint | °C | Read and write | |||
| AP4 Compressor Differential | °C | Read and write | |||
| AP4 Setpoint Maximum | °C | Read and write | |||
| AP4 Setpoint Minimum | °C | Read and write | |||
| AP4 Economy Setpoint Offset | °C | Read and write | |||
| AP4 Control Mode | Read and write | ||||
| AP4 Compressor On Time Probe Fault | min | Read and write | |||
| AP4 Compressor Off Time Probe Fault | min | Read and write | |||
| AP4 Compressor Start Delay | s | Read and write | |||
| AP4 Compressor Minimum Off Time | min | Read and write | |||
| AP4 Delay Between Compressor Starts | min | Read and write | |||
| AP4 Output Delay At Power On | min | Read and write | |||
| AP4 Deep Cooling Setpoint | °C | Read and write | |||
| AP4 Deep Cooling Duration | min | Read and write | |||
| AP4 Defrost Delay After Deep Cooling | Read and write | ||||
| AP4 Defrost Type | Read and write | ||||
| AP4 Defrost Interval | h | Read and write | |||
| AP4 Defrost Interval Count Mode | Read and write | ||||
| AP4 First Defrost Delay | min | Read and write | |||
| AP4 Defrost Timeout | min | Read and write | |||
| AP4 Defrost End Temperature | °C | Read and write | |||
| AP4 Defrost At Start Up | Read and write | ||||
| AP4 Fan Stop Temperature | °C | Read and write | |||
| AP4 Fan Differential | °C | Read and write | |||
| AP4 Fan Delay After Defrost | min | Read and write | |||
| AP4 Drip Time | min | Read and write | |||
| AP4 Fans Off During Defrost | Read and write | ||||
| AP4 Fans At Compressor Off | Read and write | ||||
| AP4 Fan On Time Day Cycle | min | Read and write | |||
| AP4 Fan Off Time Day Cycle | min | Read and write | |||
| AP4 Fan On Time Night Cycle | Read and write | ||||
| AP4 Fan Off Time Night Cycle | Read and write | ||||
| AP4 Night Mode Fans | Read and write | ||||
| AP4 Alarm Threshold Mode | Read and write | ||||
| AP4 Alarm Differential | °C | Read and write | |||
| AP4 High Temperature Alarm | °C | Read and write | |||
| AP4 Low Temperature Alarm | °C | Read and write | |||
| AP4 Alarm Delay After Power On | h | Read and write | |||
| AP4 Alarm Delay After Defrost | min | Read and write | |||
| AP4 Alarm Delay After Door Closed | h | Read and write | |||
| AP4 Door Open Alarm Delay | min | Read and write | |||
| AP4 Temperature Alarm Delay | min | Read and write | |||
| AP4 Defrost Timeout Alarm | Read and write | ||||
| AP4 External Alarm Locks Controller | Read and write | ||||
| AP4 Probe 3 Alarm Setpoint | °C | Read and write | |||
| AP4 Probe 3 Alarm Differential | °C | Read and write | |||
| AP4 Door Input Disables Loads | Read and write | ||||
| AP4 Digital Input Delay | min | Read and write | |||
| AP4 Compressor Off Delay Door Open | min | Read and write | |||
| AP4 Aux Output On Door Open | Read and write | ||||
| AP4 Pressure Switch Error Count | Read and write | ||||
| AP4 Pressure Switch Count Interval | min | Read and write | |||
| AP4 Compressor Delay After Pressure Switch | min | Read and write | |||
| AP4 Keypad Lock | Read and write | ||||
| AP4 Password User Level | Read and write | ||||
| AP4 Password Installer Level | Read and write | ||||
| AP4 Decimal Point Display | Read and write | ||||
| AP4 Probe 1 Calibration | °C | Read and write | |||
| AP4 Probe 2 Calibration | °C | Read and write | |||
| AP4 Probe 3 Calibration | °C | Read and write | |||
| AP4 Display During Defrost | Read and write | ||||
| AP4 Display Lock Timeout | min | Read and write | |||
| AP4 Temperature Unit | Read and write | ||||
| AP4 Main Display Value | Read and write | ||||
| AP4 HACCP High Threshold | °C | Read and write | |||
| AP4 HACCP Low Threshold | °C | Read and write | |||
| AP4 HACCP Alarm Delay | min | Read and write | |||
| AP4 HACCP Alarm Reset Time | h | Read and write | |||
| AP4 HACCP Enable | Read and write | ||||
| AP4 HACCP Alarm Exclusion Time | min | Read and write | |||
| AP4 Probe Type | Read and write | ||||
| AP4 Digital Input 1 Function | Read and write | ||||
| AP4 Digital Input 2 Function | Read and write | ||||
| AP4 Digital Output 1 Function | Read and write | ||||
| AP4 Digital Output 2 Function | Read and write | ||||
| AP4 Digital Output 3 Function | Read and write | ||||
| AP4 Digital Output 4 Function | Read and write | ||||
| AP4 Buzzer | Read and write | ||||
| AP4 Up Key Function | Read and write | ||||
| AP4 Down Key Function | Read and write | ||||
| AP4 Evaporator Probe Present | Read and write | ||||
| AP4 Probe 3 Present | Read and write | ||||
| Parameter Table Version | Read | ||||
| Visibility Word 49312 | Read and write | ||||
| Visibility Word 49313 | Read and write | ||||
| Visibility Word 49316 | Read and write | ||||
| Visibility Word 49317 | Read and write | ||||
| Visibility Word 49318 | Read and write | ||||
| Visibility Word 49319 | Read and write | ||||
| Visibility Word 49320 | Read and write | ||||
| Visibility Word 49321 | Read and write | ||||
| Visibility Word 49322 | Read and write | ||||
| Visibility Word 49323 | Read and write | ||||
| Visibility Word 49324 | Read and write | ||||
| Visibility Word 49325 | Read and write | ||||
| Visibility Word 49326 | Read and write | ||||
| Visibility Word 49327 | Read and write | ||||
| Visibility Word 49328 | Read and write | ||||
| Visibility Word 49329 | Read and write | ||||
| Visibility Word 49330 | Read and write | ||||
| Visibility Word 49331 | Read and write | ||||
| Visibility Word 49332 | Read and write | ||||
| Visibility Word 49333 | Read and write | ||||
| Visibility Word 49334 | Read and write | ||||
| Visibility Word 49335 | Read and write | ||||
| Visibility Word 49336 | Read and write | ||||
| Visibility Word 49337 | Read and write | ||||
| Visibility Word 49338 | Read and write | ||||
| Visibility Word 49339 | Read and write | ||||
| Visibility Word 49340 | Read and write | ||||
| Visibility Word 49341 | Read and write | ||||
| Visibility Word 49342 | Read and write | ||||
| Visibility Word 49343 | Read and write | ||||
| Visibility Word 49344 | Read and write | ||||
| Visibility Word 49345 | Read and write | ||||
| Visibility Word 49364 | Read and write | ||||
| Visibility Word 49600 | Read and write | ||||
| Visibility Word 49601 | Read and write | ||||
| Visibility Word 49602 | Read and write | ||||
| Visibility Word 49604 | Read and write | ||||
| Visibility Word 49605 | Read and write | ||||
| Visibility Word 49606 | Read and write | ||||
| Visibility Word 49607 | Read and write | ||||
| Visibility Word 49608 | Read and write | ||||
| Visibility Word 49609 | Read and write | ||||
| Visibility Word 49610 | Read and write | ||||
| Visibility Word 49611 | Read and write | ||||
| Visibility Word 49612 | Read and write | ||||
| Visibility Word 49613 | Read and write | ||||
| Visibility Word 49614 | Read and write | ||||
| Visibility Word 49615 | Read and write | ||||
| Visibility Word 49616 | Read and write | ||||
| Visibility Word 49617 | Read and write | ||||
| Visibility Word 49618 | Read and write | ||||
| Visibility Word 49619 | Read and write | ||||
| Visibility Word 49620 | Read and write | ||||
| Visibility Word 49621 | Read and write | ||||
| Visibility Word 49622 | Read and write | ||||
| Visibility Word 49623 | Read and write | ||||
| Visibility Word 49624 | Read and write | ||||
| Visibility Word 49625 | Read and write | ||||
| Visibility Word 49626 | Read and write | ||||
| Visibility Word 49627 | Read and write | ||||
| Visibility Word 49628 | Read and write | ||||
| Visibility Word 49629 | Read and write | ||||
| Visibility Word 49634 | Read and write | ||||
| Visibility Word 49776 | Read and write | ||||
| Visibility Word 49777 | Read and write | ||||
| Visibility Word 49778 | Read and write | ||||
| Visibility Word 49780 | Read and write | ||||
| Visibility Word 49781 | Read and write | ||||
| Visibility Word 49782 | Read and write | ||||
| Visibility Word 49783 | Read and write | ||||
| Visibility Word 49784 | Read and write | ||||
| Visibility Word 49785 | Read and write | ||||
| Visibility Word 49786 | Read and write | ||||
| Visibility Word 49787 | Read and write | ||||
| Visibility Word 49788 | Read and write | ||||
| Visibility Word 49789 | Read and write | ||||
| Visibility Word 49790 | Read and write | ||||
| Visibility Word 49791 | Read and write | ||||
| Visibility Word 49792 | Read and write | ||||
| Visibility Word 49793 | Read and write | ||||
| Visibility Word 49794 | Read and write | ||||
| Visibility Word 49795 | Read and write | ||||
| Visibility Word 49796 | Read and write | ||||
| Visibility Word 49797 | Read and write | ||||
| Visibility Word 49798 | Read and write | ||||
| Visibility Word 49799 | Read and write | ||||
| Visibility Word 49800 | Read and write | ||||
| Visibility Word 49801 | Read and write | ||||
| Visibility Word 49802 | Read and write | ||||
| Visibility Word 49803 | Read and write | ||||
| Visibility Word 49804 | Read and write | ||||
| Visibility Word 49805 | Read and write | ||||
| Visibility Word 49810 | Read and write | ||||
| Visibility Word 49952 | Read and write | ||||
| Visibility Word 49953 | Read and write | ||||
| Visibility Word 49954 | Read and write | ||||
| Visibility Word 49956 | Read and write | ||||
| Visibility Word 49957 | Read and write | ||||
| Visibility Word 49958 | Read and write | ||||
| Visibility Word 49959 | Read and write | ||||
| Visibility Word 49960 | Read and write | ||||
| Visibility Word 49961 | Read and write | ||||
| Visibility Word 49962 | Read and write | ||||
| Visibility Word 49963 | Read and write | ||||
| Visibility Word 49964 | Read and write | ||||
| Visibility Word 49965 | Read and write | ||||
| Visibility Word 49966 | Read and write | ||||
| Visibility Word 49967 | Read and write | ||||
| Visibility Word 49968 | Read and write | ||||
| Visibility Word 49969 | Read and write | ||||
| Visibility Word 49970 | Read and write | ||||
| Visibility Word 49971 | Read and write | ||||
| Visibility Word 49972 | Read and write | ||||
| Visibility Word 49973 | Read and write | ||||
| Visibility Word 49974 | Read and write | ||||
| Visibility Word 49975 | Read and write | ||||
| Visibility Word 49976 | Read and write | ||||
| Visibility Word 49977 | Read and write | ||||
| Visibility Word 49978 | Read and write | ||||
| Visibility Word 49979 | Read and write | ||||
| Visibility Word 49980 | Read and write | ||||
| Visibility Word 49981 | Read and write | ||||
| Visibility Word 49986 | Read and write | ||||
| Visibility Word 50128 | Read and write | ||||
| Visibility Word 50129 | Read and write | ||||
| Visibility Word 50130 | Read and write | ||||
| Visibility Word 50132 | Read and write | ||||
| Visibility Word 50133 | Read and write | ||||
| Visibility Word 50134 | Read and write | ||||
| Visibility Word 50135 | Read and write | ||||
| Visibility Word 50136 | Read and write | ||||
| Visibility Word 50137 | Read and write | ||||
| Visibility Word 50138 | Read and write | ||||
| Visibility Word 50139 | Read and write | ||||
| Visibility Word 50140 | Read and write | ||||
| Visibility Word 50141 | Read and write | ||||
| Visibility Word 50142 | Read and write | ||||
| Visibility Word 50143 | Read and write | ||||
| Visibility Word 50144 | Read and write | ||||
| Visibility Word 50145 | Read and write | ||||
| Visibility Word 50146 | Read and write | ||||
| Visibility Word 50147 | Read and write | ||||
| Visibility Word 50148 | Read and write | ||||
| Visibility Word 50149 | Read and write | ||||
| Visibility Word 50150 | Read and write | ||||
| Visibility Word 50151 | Read and write | ||||
| Visibility Word 50152 | Read and write | ||||
| Visibility Word 50153 | Read and write | ||||
| Visibility Word 50154 | Read and write | ||||
| Visibility Word 50155 | Read and write | ||||
| Visibility Word 50156 | Read and write | ||||
| Visibility Word 50157 | Read and write | ||||
| Visibility Word 50162 | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show the cabinet and evaporator temperature of every cold room on one ModbusCloud dashboard.
- Get an email alert when the cabinet temperature rises above a set limit or the alarm word is not 0.
- Keep a temperature history per cold room to show the food safety inspector.
- Start a manual defrost from ModbusCloud when an evaporator ices up.
- Raise or lower the setpoint of a display cabinet remotely when the product range changes.
Installation
Connect the 5-pin TTL port of the controller to an Eliwell TTL to RS485 adapter and wire its A and B to the ModbusCloud Gateway, with termination at the bus end.
On the controller set PtS to d (Modbus), and set FAA and dEA so FAA x 16 + dEA gives a unique address of 1 or higher.
Leave parity at none and stop bits at 1, or match them in ModbusCloud; power cycle after changing the parity.
In ModbusCloud, add a Modbus RTU device at 9600 baud with that address and import this template.
Check that Probe 1 Temperature matches the value on the controller display.
Things to watch for
The controller does not answer. What should I check?
Check that PtS is set to d (Modbus) and not t (Televis), that the address FAA x 16 + dEA is not 0, and that baud rate, parity and stop bits match. Swap A and B on the adapter if needed and add termination at the end of a long bus.
Why do I get errors when reading many parameters at once?
The controller answers short messages only and reads parameters one register at a time. Poll only the parameters you need and keep the poll interval relaxed; the probe and status values are the ones to read often.
Why does writing a command have no effect?
Commands such as defrost, economy, AUX and standby are accepted only while a short timer runs. Write a number of seconds to Command Window Timer first, then write the command value within that time. Parameter writes change the cooling at once, so check the value before you write.
Why does the status word show a large number?
Status and alarm values are packed as bits in one word. The register comment says which bit means what, such as bit 3 of the compressor word for compressor on.
Can I connect several controllers to one bus?
Yes. Give each controller its own adapter on the RS485 bus and a unique address through FAA and dEA, then add each one in ModbusCloud as a separate device with this template.