Fuji Electric Fuji Electric FRENIC-Mini C2 Modbus RTU template

Fuji Electric FRENIC-Mini C2

Compact inverter: frequency, current, alarms and every function code over RS-485.

The Fuji Electric FRENIC-Mini (C2) is a compact frequency inverter for small motors in pumps, fans and conveyors. This Modbus RTU template reads its monitor data and alarms, writes frequency reference and run commands, and gives access to the function codes, so you can follow and adjust the drive from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
317, read and write
Key readings
Output frequency · Output current · Output voltage · Input power · DC link voltage · Heat sink temperature · Run status · Alarm history
Available commands
Frequency reference · Run command · Alarm reset · Function codes
Compatible models
FRENIC-Mini C2 · Fuji Electric FRENIC-Mini (C2) series compact inverters with RS-485, all capacities
Last updated

Registers (317)

317 read, 225 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
F00 Data ProtectionRead and write0FC03 / FC06uint16
F01 Frequency Command 1Read and write1FC03 / FC06uint16
F02 Operation MethodRead and write2FC03 / FC06uint16
F03 Maximum Frequency 1HzRead and write3FC03 / FC06uint16
F04 Base Frequency 1HzRead and write4FC03 / FC06uint16
F05 Rated Voltage at Base Frequency 1VRead and write
F06 Maximum Output Voltage 1VRead and write
F07 Acceleration Time 1Read and write
F08 Deceleration Time 1Read and write
F09 Torque Boost 1%Read and write
F10 Thermal Overload, Motor (Select motor characteristics)Read and write
F11 Thermal Overload, Motor (Overload detection level)Read and write
F12 Thermal Overload, Motor (Thermal time constant)minRead and write
F14 Restart after Power Failure (Mode selection)Read and write
F15 Frequency Limiter (High)HzRead and write
F16 Frequency Limiter (Low)HzRead and write
F18 Bias (Frequency command 1)%Read and write
F20 DC Braking 1 (Braking starting frequency)HzRead and write
F21 DC Braking 1 (Braking level)%Read and write
F22 DC Braking 1 (Braking time)sRead and write
F23 Starting Frequency 1HzRead and write
F24 Starting Frequency 1 (Holding time)sRead and write
F25 Stop FrequencyHzRead and write
F26 Motor Sound (Carrier frequency)Read and write
F27 Motor Sound (Tone)Read and write
F30 Analog Output [FMA*1] (Voltage adjustment)%Read and write
F31 Analog Output [FMA*1] (Function)Read and write
F37 Load Selection/Auto Torque Boost/Auto Energy SavingRead and write
F39 Stop Frequency (Holding time)sRead and write
F42 Drive Control Selection 1Read and write
F43 Current Limiter (Mode selection)Read and write
F44 Current Limiter (Level)%Read and write
F50 Thermal Overload, BrakingRead and write
F51 Thermal Overload, Braking (Allowable average loss)kWRead and write
E01 Terminal [X1] FunctionRead and write
E02 Terminal [X2] FunctionRead and write
E03 Terminal [X3] FunctionRead and write
E10 Acceleration Time 2Read and write
E11 Deceleration Time 2Read and write
E20 Terminal [Y1] FunctionRead and write
E27 [30A/B/C] Function (Relay output)Read and write
E30 Frequency Arrival (Hysteresis width)HzRead and write
E31 Frequency Detection 1 (Level)HzRead and write
E32 Frequency Detection 1 (Hysteresis width)HzRead and write
E34 Overload Early Warning/Current Detection (Level)Read and write
E35 Overload Early Warning/Current Detection (Timer)sRead and write
E37 Current Detection 2 /Low Current Detection (Level)Read and write
E38 Current Detection 2 /Low Current Detection (Timer)sRead and write
E39 Coefficient for Constant Feeding Rate TimeRead and write
E40 PID Display Coefficient ARead and write
E41 PID Display Coefficient BRead and write
E42 LED Display FiltersRead and write
E43 LED Monitor (Item selection)Read and write
E45 LCD Monitor (Item selection)Read and write
E46 LCD Monitor (Language selection)Read and write
E47 LCD Monitor (Contrast control)Read and write
E48 LED Monitor (Speed monitor item)Read and write
E50 Coefficient for Speed IndicationRead and write
E51 Display Coefficient for Input Watt-hour DataRead and write
E52 Keypad (Menu display mode)Read and write
E60 Built-in Potentiometer (Function selection)Read and write
E61 Terminal [12] Extended FunctionRead and write
E62 Terminal [C1] Extended FunctionRead and write
E98 Terminal [FWD] FunctionRead and write
E99 Terminal [REV] FunctionRead and write
C01 Jump Frequency 1HzRead and write
C02 Jump Frequency 2HzRead and write
C03 Jump Frequency 3HzRead and write
C04 Jump Frequency (Hysteresis width)HzRead and write
C05 Multi-Frequency 1HzRead and write
C06 Multi-Frequency 2HzRead and write
C07 Multi-Frequency 3HzRead and write
C08 Multi-Frequency 4HzRead and write
C09 Multi-Frequency 5HzRead and write
C10 Multi-Frequency 6HzRead and write
C11 Multi-Frequency 7HzRead and write
C12 Multi-Frequency 8HzRead and write
C13 Multi-Frequency 9HzRead and write
C14 Multi-Frequency 10HzRead and write
C15 Multi-Frequency 11HzRead and write
C16 Multi-Frequency 12HzRead and write
C17 Multi-Frequency 13HzRead and write
C18 Multi-Frequency 14HzRead and write
C19 Multi-Frequency 15HzRead and write
C20 Jogging FrequencyHzRead and write
C21 Timer Operation/Pattern Operation SelectionRead and write
C30 Frequency Command 2Read and write
C32 Analog Input Adjustment for [12] (Gain)%Read and write
C33 Analog Input Adjustment for [12] (Filter time constant)sRead and write
C34 Analog Input Adjustment for [12] (Gain base point)%Read and write
C37 Analog Input Adjustment for [C1] (Gain)%Read and write
C38 Analog Input Adjustment for [C1] (Filter time constant)sRead and write
C39 Analog Input Adjustment for [C1] (Gain base point)%Read and write
C40 Analog Input [C1] (Range selection)Read and write
C50 Bias (Frequency command 1) (Bias base point)%Read and write
C51 Bias (PID command 1) (Bias value)%Read and write
C52 Bias (PID command 1) (Bias base point)%Read and write
C94 Jump Frequency 4HzRead and write
C95 Jump Frequency 5HzRead and write
C96 Jump Frequency 6HzRead and write
C99 Multi-frequency 1 (0.01 Hz resolution)HzRead and write
P02 Motor 1 (Rated Capacity)kWRead and write
P03 Motor 1 (Rated current)Read and write
P06 Motor 1 (No-load current)Read and write
P07 Motor 1 (%R1)%Read and write
P08 Motor 1 (%X)%Read and write
P09 Motor 1 (Slip compensation gain for driving)%Read and write
P10 Motor 1 (Slip compensation response time)sRead and write
P11 Motor 1 (Slip compensation gain for braking)%Read and write
P12 Motor 1 (Rated slip frequency)HzRead and write
P60 Motor 1 (PMSM Armature resistance)Read and write
P61 Motor 1 (PMSM d-axis inductance)Read and write
P62 Motor 1 (PMSM q-axis inductance)Read and write
P63 Motor 1 (PMSM Induced voltage)VRead and write
P74 Motor 1 (PMSM Reference current at starting)%Read and write
P89 Motor 1 (PMSM Reserved)%Read and write
P90 Motor 1 (PMSM Overcurrent protection level)Read and write
P91 Motor 1 (V/f Dumping Control Compensation gain of d-axis)Read and write
P92 Motor 1 (V/f Dumping Control Compensation gain of q-axis)Read and write
P93 Motor 1 (Control Change Level)%Read and write
P99 Motor 1 SelectionRead and write
H03 Data InitializationRead and write
H04 Auto-reset (Times)Read and write
H05 Auto-reset (Reset interval)sRead and write
H06 Cooling Fan ON/OFF ControlRead and write
H07 Acceleration/Deceleration PatternRead and write
H08 Rotational Direction LimitationRead and write
H11 Deceleration ModeRead and write
H12 Instantaneous Overcurrent Limiting (Mode selection)Read and write
H13 Restart after Power Failure (Restart time)sRead and write
H14 Restart after Power Failure (Frequency fall rate)Read and write
H15 Restart after Power Failure (Continuous running level)VRead and write
H26 Thermistor (for motor) (Mode selection)Read and write
H27 Thermistor (Level)VRead and write
H30 Communications Link Function (Mode selection)Read and write
H42 Capacitance of DC Link Bus CapacitorRead and write
H43 Cumulative Run Time of Cooling FanhRead and write
H44 Startup Counter for Motor 1Read and write
H45 Mock AlarmRead and write
H47 Initial Capacitance of DC Link Bus CapacitorRead and write
H48 Cumulative Run Time of Capacitors on Printed CircuithRead and write
H50 Non-linear V/f Pattern 1 (Frequency)HzRead and write
H51 Non-linear V/f Pattern 1 (Voltage)VRead and write
H52 Non-linear V/f Pattern 2 (Frequency)HzRead and write
H53 Non-linear V/f Pattern 2 (Voltage)VRead and write
H54 ACC/DEC Time (Jogging)Read and write
H61 UP/DOWN Control (Initial frequency setting)Read and write
H63 Low Limiter (Mode selection)Read and write
H64 Low Limiter (Lower limiting frequency)HzRead and write
H69 Automatic Deceleration (Mode selection)Read and write
H70 Overload Prevention ControlRead and write
H71 Deceleration CharacteristicsRead and write
H76 Torque Limiter (Frequency increment limit for braking)HzRead and write
H78 Maintenance Interval (M1)Read and write
H79 Preset Startup Count for Maintenance (M1)Read and write
H80 Output Current Fluctuation Damping Gain for Motor 1Read and write
H89 Reserved.Read and write
H91 PID Feedback Wire Break DetectionsRead and write
H92 Continuity of Running (P)Read and write
H93 Continuity of Running (I)Read and write
H94 Cumulative Motor Run Time 1Read and write
H95 DC Braking (Braking response mode)Read and write
H96 STOP Key Priority / Start Check FunctionRead and write
H97 Clear Alarm DataRead and write
H98 Protection / Maintenance Function (Mode selection)Read and write
A01 Maximum Frequency 2HzRead and write
A02 Base Frequency 2HzRead and write
A03 Rated Voltage at Base Frequency 2VRead and write
A04 Maximum Output Voltage 2VRead and write
A05 Torque Boost 2%Read and write
A06 Thermal Overload, Motor 2 (Select motor characteristics)Read and write
A07 Thermal Overload, Motor 2 (Overload detection level)Read and write
A08 Thermal Overload, Motor 2 (Thermal time constant)minRead and write
A09 DC Braking 2 (Braking starting frequency)HzRead and write
A10 DC Braking 2 (Braking level)%Read and write
A11 DC Braking 2 (Braking time)sRead and write
A12 Starting Frequency 2HzRead and write
A13 Load Selection/Auto Torque Boost/Auto Energy SavingRead and write
A14 Drive Control Selection 2Read and write
A16 Motor 2 (Rated Capacity)kWRead and write
A17 Motor 2 (Rated current)Read and write
A20 Motor 2 (No-load current)Read and write
A21 Motor 2 (%R1)%Read and write
A22 Motor 2 (%X)%Read and write
A23 Motor 2 (Slip compensation gain for driving)%Read and write
A24 Motor 2 (Slip compensation response time)sRead and write
A25 Motor 2 (Slip compensation gain for braking)%Read and write
A26 Motor 2 (Rated slip frequency)HzRead and write
A39 Motor 2 SelectionRead and write
A41 Output Current Fluctuation Damping Gain for Motor 2Read and write
A51 Cumulative Motor Run Time 2Read and write
A52 Startup Counter for Motor 2Read and write
S01 Frequency Reference (p.u.)Read and write
S05 Frequency ReferenceHzRead and write
S06 Operation CommandRead and write
S08 Acceleration Time F07Read and write
S09 Deceleration Time F08Read and write
S13 PID CommandRead and write
S14 Alarm Reset CommandRead and write
M01 Frequency Reference (p.u.) (Final command)Read
M05 Frequency Reference (Final command)HzRead
M06 Output Frequency 1(p.u.)Read
M09 Output FrequencyHzRead
M10 Input Power%Read
M11 Output Current Effective Value%Read
M12 Output Voltage Effective ValueVRead
M13 Operation Command (Final command)Read
M14 Operation StatusRead
M15 General-purpose Output Terminal InformationRead
M16 Alarm Contents (Latest)Read
M17 Alarm Contents (Last)Read
M18 Alarm Contents (2nd last)Read
M19 Alarm Contents (3rd last)Read
M20 Cumulative Operation TimehRead
M21 DC link Circuit VoltageVRead
M23 Model CodeRead
M24 Capacity CodeRead
M25 ROM VersionRead
M26 Transmission Error Transaction CodeRead
M27 Frequency Reference on Alarm (p.u.) (Final Command)Read
M31 Frequency Reference on Alarm (Final Command)HzRead
M32 Output Frequency 1 on Alarm (p.u.)Read
M33 Torque Value on Alarm%Read
M35 Output Frequency on AlarmHzRead
M36 Input Power on Alarm%Read
M37 Output Current Effective Value on Alarm%Read
M38 Output Voltage Effective Value on AlarmVRead
M39 Operation Command on AlarmRead
M40 Operation Status on AlarmRead
M41 Output terminal Information on AlarmRead
M42 Cumulative Operation Time on AlarmhRead
M43 DC Link Circuit Voltage on AlarmVRead
M45 Heat Sink Temperature on Alarm°CRead
M46 Life of Main Circuit Capacitor%Read
M47 Life of PC Board Electrolytic CapacitorhRead
M48 Life of Cooling FanhRead
M49 Input Terminal Voltage[12] (p.u.)Read
M50 Input Terminal Current[C1] (p.u.)Read
M62 Heat Sink Temperature°CRead
M68 PID Final CommandRead
M69 Inverter Rated CurrentRead
M70 Operation Status 2Read
M71 Input Terminal InformationRead
M72 PID Feedback ValueRead
M73 PID OutputRead
M74 Running Status 2Read
M81 Remaining Time Before The Next Motor 1 MaintenancehRead
M85 Remaining Startup Times Before The Next MaintenanceRead
J01 PID Control (Mode selection)Read and write
J02 PID Control (Remote command SV)Read and write
J03 PID Control P (Gain)Read and write
J04 PID Control I (Integral time)sRead and write
J05 PID Control D (Differential time)sRead and write
J06 PID Control (Feedback filter)sRead and write
J15 PID Control (Stop frequency for slow flowrate)HzRead and write
J16 PID Control (Slow flowrate level stop latency)sRead and write
J17 PID Control (Starting frequency)HzRead and write
J23 PID Control (Starting feedback deviation level)%Read and write
J24 PID Control (Starting latency from the flow rate stop)sRead and write
J68 Brake Signal (Brake OFF current)%Read and write
J69 Brake Signal (Brake OFF frequency/speed)HzRead and write
J70 Brake Signal (Brake OFF timer)sRead and write
J71 Brake Signal (Brake ON frequency/speed)HzRead and write
J72 Brake Signal (Brake ON timer)sRead and write
y01 RS-485 Communication (Station address)Read and write
y02 RS-485 Communication (Communications error processing)Read and write
y03 RS-485 Communication (Timer)sRead and write
y04 RS-485 Communication (Baud rate)Read and write
y05 RS-485 Communication (Data length)Read and write
y06 RS-485 Communication (Parity check)Read and write
y07 RS-485 Communication (Stop bits)Read and write
y08 RS-485 Communication (No-response error detection time)sRead and write
y09 RS-485 Communication (Response interval)sRead and write
y10 RS-485 Communication (Protocol selection)Read and write
W01 Running StatusRead
W02 Frequency ReferenceHzRead
W03 Output Frequency (Before slip compensation)HzRead
W04 Output Frequency (After slip compensation)HzRead
W05 Output CurrentRead
W06 Output VoltageVRead
W09 Load Shaft SpeedRead
W10 Line SpeedRead
W11 PID Process CommandRead
W12 PID Feedback ValueRead
W17 Load Shaft Set ValueRead
W18 Line Speed Set ValueRead
W19 Constant Feed Time Set ValueRead
W20 Constant Feed TimeRead
W21 Input PowerRead
W27 Timer Operation Remaining TimesRead
W28 Operation Command SourceRead
W29 Frequency and PID Command SourceRead
W32 PID Output%Read
W40 Control Circuit Terminal (Input)Read
W41 Control Circuit Terminal (Output)Read
W42 Communications Control Signal (Input)Read
W43 Communications Control Signal (Output)Read
W44 Terminal [12] Input VoltageVRead
W45 Terminal [C1] Input CurrentmARead
W46 Terminal [FMA*3] Output VoltageVRead
W67 Cumulative Run Time of Capacitors on Printed CircuithRead
W68 Cumulative Run Time of Cooling FanhRead
W70 Cumulative Operation TimehRead
W71 DC link Circuit VoltageVRead
W73 Heat Sink Maximum Temperature°CRead
W74 Maximum Effective Current ValueRead
W75 Main Circuit Capacitor's Capacitor%Read
W76 Cumulative Ope. Time of Capacitor on PC BoardhRead
W77 Cumulative Ope. Time of Cooling FanhRead
W78 Number of StartupsRead
W79 Cumulative Ope. Time of Motor DrivinghRead
W81 Integrating Electric PowerRead
W82 Data Used Integrating Electric PowerRead
W83 Number of RS-485 Ch1 ErrorsRead
W84 Contents of RS-485 Ch1 ErrorRead
W87 Inverter's ROM VersionRead
W89 Remote Keypad's ROM VersionRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show output frequency, current and DC link voltage of each drive on a ModbusCloud dashboard.
  • Send an email alert when a new alarm code appears in the latest alarm register.
  • Keep 365 days of history of current and heat sink temperature to spot a pump that works harder over time.
  • Write a new frequency reference from ModbusCloud when the drive runs under communication control.
  • Export the cumulative run time and capacitor life values as CSV for maintenance planning.

Installation

  1. Wire the RS-485 port of the FRENIC-Mini to RS485 A and B of the ModbusCloud Gateway and terminate the bus at both ends.

  2. On the keypad, set y10 to 0 (Modbus RTU) and check y01 (station address), y04 (baud rate) and y06 (parity).

  3. To start and stop the drive over Modbus, set H30 so the run command and frequency come from communication.

  4. In ModbusCloud, add a Modbus device with 19200 baud, no parity, 8 data bits and 2 stop bits, or the values you set, and import this template.

  5. Check that output frequency and output current match the keypad display.

Things to watch for

The drive does not answer. What should I check?

The factory setting of y10 is 1, the FRENIC Loader protocol. Set y10 to 0 for Modbus RTU. Then check station address, baud rate and parity: with y06 = 0 Modbus RTU uses no parity and 2 stop bits.

Writing the frequency reference or run command has no effect. Why?

The drive only follows commands from the RS-485 link when H30 allows it. Check H30 and the frequency command source F01, and make sure the drive is not in local mode on the keypad. The setting codes F to y and the command codes S are writable; only change a setting when you know what it does and note the old value.

Acceleration time and some motor values look like odd numbers. Are they wrong?

These function codes use a Fuji floating point word with sign, exponent and mantissa. The template reads the raw word; the register comment explains how to turn it into seconds or another value.