Fuji Electric FRENIC-Mini C2
Compact inverter: frequency, current, alarms and every function code over RS-485.
The Fuji Electric FRENIC-Mini (C2) is a compact frequency inverter for small motors in pumps, fans and conveyors. This Modbus RTU template reads its monitor data and alarms, writes frequency reference and run commands, and gives access to the function codes, so you can follow and adjust the drive from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 317, read and write
- Brand
- Fuji Electric
- Key readings
- Output frequency · Output current · Output voltage · Input power · DC link voltage · Heat sink temperature · Run status · Alarm history
- Available commands
- Frequency reference · Run command · Alarm reset · Function codes
- Compatible models
- FRENIC-Mini C2 · Fuji Electric FRENIC-Mini (C2) series compact inverters with RS-485, all capacities
- Last updated
Registers (317)
317 read, 225 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| F00 Data Protection | Read and write | 0 | FC03 / FC06 | uint16 | |
| F01 Frequency Command 1 | Read and write | 1 | FC03 / FC06 | uint16 | |
| F02 Operation Method | Read and write | 2 | FC03 / FC06 | uint16 | |
| F03 Maximum Frequency 1 | Hz | Read and write | 3 | FC03 / FC06 | uint16 |
| F04 Base Frequency 1 | Hz | Read and write | 4 | FC03 / FC06 | uint16 |
| F05 Rated Voltage at Base Frequency 1 | V | Read and write | |||
| F06 Maximum Output Voltage 1 | V | Read and write | |||
| F07 Acceleration Time 1 | Read and write | ||||
| F08 Deceleration Time 1 | Read and write | ||||
| F09 Torque Boost 1 | % | Read and write | |||
| F10 Thermal Overload, Motor (Select motor characteristics) | Read and write | ||||
| F11 Thermal Overload, Motor (Overload detection level) | Read and write | ||||
| F12 Thermal Overload, Motor (Thermal time constant) | min | Read and write | |||
| F14 Restart after Power Failure (Mode selection) | Read and write | ||||
| F15 Frequency Limiter (High) | Hz | Read and write | |||
| F16 Frequency Limiter (Low) | Hz | Read and write | |||
| F18 Bias (Frequency command 1) | % | Read and write | |||
| F20 DC Braking 1 (Braking starting frequency) | Hz | Read and write | |||
| F21 DC Braking 1 (Braking level) | % | Read and write | |||
| F22 DC Braking 1 (Braking time) | s | Read and write | |||
| F23 Starting Frequency 1 | Hz | Read and write | |||
| F24 Starting Frequency 1 (Holding time) | s | Read and write | |||
| F25 Stop Frequency | Hz | Read and write | |||
| F26 Motor Sound (Carrier frequency) | Read and write | ||||
| F27 Motor Sound (Tone) | Read and write | ||||
| F30 Analog Output [FMA*1] (Voltage adjustment) | % | Read and write | |||
| F31 Analog Output [FMA*1] (Function) | Read and write | ||||
| F37 Load Selection/Auto Torque Boost/Auto Energy Saving | Read and write | ||||
| F39 Stop Frequency (Holding time) | s | Read and write | |||
| F42 Drive Control Selection 1 | Read and write | ||||
| F43 Current Limiter (Mode selection) | Read and write | ||||
| F44 Current Limiter (Level) | % | Read and write | |||
| F50 Thermal Overload, Braking | Read and write | ||||
| F51 Thermal Overload, Braking (Allowable average loss) | kW | Read and write | |||
| E01 Terminal [X1] Function | Read and write | ||||
| E02 Terminal [X2] Function | Read and write | ||||
| E03 Terminal [X3] Function | Read and write | ||||
| E10 Acceleration Time 2 | Read and write | ||||
| E11 Deceleration Time 2 | Read and write | ||||
| E20 Terminal [Y1] Function | Read and write | ||||
| E27 [30A/B/C] Function (Relay output) | Read and write | ||||
| E30 Frequency Arrival (Hysteresis width) | Hz | Read and write | |||
| E31 Frequency Detection 1 (Level) | Hz | Read and write | |||
| E32 Frequency Detection 1 (Hysteresis width) | Hz | Read and write | |||
| E34 Overload Early Warning/Current Detection (Level) | Read and write | ||||
| E35 Overload Early Warning/Current Detection (Timer) | s | Read and write | |||
| E37 Current Detection 2 /Low Current Detection (Level) | Read and write | ||||
| E38 Current Detection 2 /Low Current Detection (Timer) | s | Read and write | |||
| E39 Coefficient for Constant Feeding Rate Time | Read and write | ||||
| E40 PID Display Coefficient A | Read and write | ||||
| E41 PID Display Coefficient B | Read and write | ||||
| E42 LED Display Filter | s | Read and write | |||
| E43 LED Monitor (Item selection) | Read and write | ||||
| E45 LCD Monitor (Item selection) | Read and write | ||||
| E46 LCD Monitor (Language selection) | Read and write | ||||
| E47 LCD Monitor (Contrast control) | Read and write | ||||
| E48 LED Monitor (Speed monitor item) | Read and write | ||||
| E50 Coefficient for Speed Indication | Read and write | ||||
| E51 Display Coefficient for Input Watt-hour Data | Read and write | ||||
| E52 Keypad (Menu display mode) | Read and write | ||||
| E60 Built-in Potentiometer (Function selection) | Read and write | ||||
| E61 Terminal [12] Extended Function | Read and write | ||||
| E62 Terminal [C1] Extended Function | Read and write | ||||
| E98 Terminal [FWD] Function | Read and write | ||||
| E99 Terminal [REV] Function | Read and write | ||||
| C01 Jump Frequency 1 | Hz | Read and write | |||
| C02 Jump Frequency 2 | Hz | Read and write | |||
| C03 Jump Frequency 3 | Hz | Read and write | |||
| C04 Jump Frequency (Hysteresis width) | Hz | Read and write | |||
| C05 Multi-Frequency 1 | Hz | Read and write | |||
| C06 Multi-Frequency 2 | Hz | Read and write | |||
| C07 Multi-Frequency 3 | Hz | Read and write | |||
| C08 Multi-Frequency 4 | Hz | Read and write | |||
| C09 Multi-Frequency 5 | Hz | Read and write | |||
| C10 Multi-Frequency 6 | Hz | Read and write | |||
| C11 Multi-Frequency 7 | Hz | Read and write | |||
| C12 Multi-Frequency 8 | Hz | Read and write | |||
| C13 Multi-Frequency 9 | Hz | Read and write | |||
| C14 Multi-Frequency 10 | Hz | Read and write | |||
| C15 Multi-Frequency 11 | Hz | Read and write | |||
| C16 Multi-Frequency 12 | Hz | Read and write | |||
| C17 Multi-Frequency 13 | Hz | Read and write | |||
| C18 Multi-Frequency 14 | Hz | Read and write | |||
| C19 Multi-Frequency 15 | Hz | Read and write | |||
| C20 Jogging Frequency | Hz | Read and write | |||
| C21 Timer Operation/Pattern Operation Selection | Read and write | ||||
| C30 Frequency Command 2 | Read and write | ||||
| C32 Analog Input Adjustment for [12] (Gain) | % | Read and write | |||
| C33 Analog Input Adjustment for [12] (Filter time constant) | s | Read and write | |||
| C34 Analog Input Adjustment for [12] (Gain base point) | % | Read and write | |||
| C37 Analog Input Adjustment for [C1] (Gain) | % | Read and write | |||
| C38 Analog Input Adjustment for [C1] (Filter time constant) | s | Read and write | |||
| C39 Analog Input Adjustment for [C1] (Gain base point) | % | Read and write | |||
| C40 Analog Input [C1] (Range selection) | Read and write | ||||
| C50 Bias (Frequency command 1) (Bias base point) | % | Read and write | |||
| C51 Bias (PID command 1) (Bias value) | % | Read and write | |||
| C52 Bias (PID command 1) (Bias base point) | % | Read and write | |||
| C94 Jump Frequency 4 | Hz | Read and write | |||
| C95 Jump Frequency 5 | Hz | Read and write | |||
| C96 Jump Frequency 6 | Hz | Read and write | |||
| C99 Multi-frequency 1 (0.01 Hz resolution) | Hz | Read and write | |||
| P02 Motor 1 (Rated Capacity) | kW | Read and write | |||
| P03 Motor 1 (Rated current) | Read and write | ||||
| P06 Motor 1 (No-load current) | Read and write | ||||
| P07 Motor 1 (%R1) | % | Read and write | |||
| P08 Motor 1 (%X) | % | Read and write | |||
| P09 Motor 1 (Slip compensation gain for driving) | % | Read and write | |||
| P10 Motor 1 (Slip compensation response time) | s | Read and write | |||
| P11 Motor 1 (Slip compensation gain for braking) | % | Read and write | |||
| P12 Motor 1 (Rated slip frequency) | Hz | Read and write | |||
| P60 Motor 1 (PMSM Armature resistance) | Read and write | ||||
| P61 Motor 1 (PMSM d-axis inductance) | Read and write | ||||
| P62 Motor 1 (PMSM q-axis inductance) | Read and write | ||||
| P63 Motor 1 (PMSM Induced voltage) | V | Read and write | |||
| P74 Motor 1 (PMSM Reference current at starting) | % | Read and write | |||
| P89 Motor 1 (PMSM Reserved) | % | Read and write | |||
| P90 Motor 1 (PMSM Overcurrent protection level) | Read and write | ||||
| P91 Motor 1 (V/f Dumping Control Compensation gain of d-axis) | Read and write | ||||
| P92 Motor 1 (V/f Dumping Control Compensation gain of q-axis) | Read and write | ||||
| P93 Motor 1 (Control Change Level) | % | Read and write | |||
| P99 Motor 1 Selection | Read and write | ||||
| H03 Data Initialization | Read and write | ||||
| H04 Auto-reset (Times) | Read and write | ||||
| H05 Auto-reset (Reset interval) | s | Read and write | |||
| H06 Cooling Fan ON/OFF Control | Read and write | ||||
| H07 Acceleration/Deceleration Pattern | Read and write | ||||
| H08 Rotational Direction Limitation | Read and write | ||||
| H11 Deceleration Mode | Read and write | ||||
| H12 Instantaneous Overcurrent Limiting (Mode selection) | Read and write | ||||
| H13 Restart after Power Failure (Restart time) | s | Read and write | |||
| H14 Restart after Power Failure (Frequency fall rate) | Read and write | ||||
| H15 Restart after Power Failure (Continuous running level) | V | Read and write | |||
| H26 Thermistor (for motor) (Mode selection) | Read and write | ||||
| H27 Thermistor (Level) | V | Read and write | |||
| H30 Communications Link Function (Mode selection) | Read and write | ||||
| H42 Capacitance of DC Link Bus Capacitor | Read and write | ||||
| H43 Cumulative Run Time of Cooling Fan | h | Read and write | |||
| H44 Startup Counter for Motor 1 | Read and write | ||||
| H45 Mock Alarm | Read and write | ||||
| H47 Initial Capacitance of DC Link Bus Capacitor | Read and write | ||||
| H48 Cumulative Run Time of Capacitors on Printed Circuit | h | Read and write | |||
| H50 Non-linear V/f Pattern 1 (Frequency) | Hz | Read and write | |||
| H51 Non-linear V/f Pattern 1 (Voltage) | V | Read and write | |||
| H52 Non-linear V/f Pattern 2 (Frequency) | Hz | Read and write | |||
| H53 Non-linear V/f Pattern 2 (Voltage) | V | Read and write | |||
| H54 ACC/DEC Time (Jogging) | Read and write | ||||
| H61 UP/DOWN Control (Initial frequency setting) | Read and write | ||||
| H63 Low Limiter (Mode selection) | Read and write | ||||
| H64 Low Limiter (Lower limiting frequency) | Hz | Read and write | |||
| H69 Automatic Deceleration (Mode selection) | Read and write | ||||
| H70 Overload Prevention Control | Read and write | ||||
| H71 Deceleration Characteristics | Read and write | ||||
| H76 Torque Limiter (Frequency increment limit for braking) | Hz | Read and write | |||
| H78 Maintenance Interval (M1) | Read and write | ||||
| H79 Preset Startup Count for Maintenance (M1) | Read and write | ||||
| H80 Output Current Fluctuation Damping Gain for Motor 1 | Read and write | ||||
| H89 Reserved. | Read and write | ||||
| H91 PID Feedback Wire Break Detection | s | Read and write | |||
| H92 Continuity of Running (P) | Read and write | ||||
| H93 Continuity of Running (I) | Read and write | ||||
| H94 Cumulative Motor Run Time 1 | Read and write | ||||
| H95 DC Braking (Braking response mode) | Read and write | ||||
| H96 STOP Key Priority / Start Check Function | Read and write | ||||
| H97 Clear Alarm Data | Read and write | ||||
| H98 Protection / Maintenance Function (Mode selection) | Read and write | ||||
| A01 Maximum Frequency 2 | Hz | Read and write | |||
| A02 Base Frequency 2 | Hz | Read and write | |||
| A03 Rated Voltage at Base Frequency 2 | V | Read and write | |||
| A04 Maximum Output Voltage 2 | V | Read and write | |||
| A05 Torque Boost 2 | % | Read and write | |||
| A06 Thermal Overload, Motor 2 (Select motor characteristics) | Read and write | ||||
| A07 Thermal Overload, Motor 2 (Overload detection level) | Read and write | ||||
| A08 Thermal Overload, Motor 2 (Thermal time constant) | min | Read and write | |||
| A09 DC Braking 2 (Braking starting frequency) | Hz | Read and write | |||
| A10 DC Braking 2 (Braking level) | % | Read and write | |||
| A11 DC Braking 2 (Braking time) | s | Read and write | |||
| A12 Starting Frequency 2 | Hz | Read and write | |||
| A13 Load Selection/Auto Torque Boost/Auto Energy Saving | Read and write | ||||
| A14 Drive Control Selection 2 | Read and write | ||||
| A16 Motor 2 (Rated Capacity) | kW | Read and write | |||
| A17 Motor 2 (Rated current) | Read and write | ||||
| A20 Motor 2 (No-load current) | Read and write | ||||
| A21 Motor 2 (%R1) | % | Read and write | |||
| A22 Motor 2 (%X) | % | Read and write | |||
| A23 Motor 2 (Slip compensation gain for driving) | % | Read and write | |||
| A24 Motor 2 (Slip compensation response time) | s | Read and write | |||
| A25 Motor 2 (Slip compensation gain for braking) | % | Read and write | |||
| A26 Motor 2 (Rated slip frequency) | Hz | Read and write | |||
| A39 Motor 2 Selection | Read and write | ||||
| A41 Output Current Fluctuation Damping Gain for Motor 2 | Read and write | ||||
| A51 Cumulative Motor Run Time 2 | Read and write | ||||
| A52 Startup Counter for Motor 2 | Read and write | ||||
| S01 Frequency Reference (p.u.) | Read and write | ||||
| S05 Frequency Reference | Hz | Read and write | |||
| S06 Operation Command | Read and write | ||||
| S08 Acceleration Time F07 | Read and write | ||||
| S09 Deceleration Time F08 | Read and write | ||||
| S13 PID Command | Read and write | ||||
| S14 Alarm Reset Command | Read and write | ||||
| M01 Frequency Reference (p.u.) (Final command) | Read | ||||
| M05 Frequency Reference (Final command) | Hz | Read | |||
| M06 Output Frequency 1(p.u.) | Read | ||||
| M09 Output Frequency | Hz | Read | |||
| M10 Input Power | % | Read | |||
| M11 Output Current Effective Value | % | Read | |||
| M12 Output Voltage Effective Value | V | Read | |||
| M13 Operation Command (Final command) | Read | ||||
| M14 Operation Status | Read | ||||
| M15 General-purpose Output Terminal Information | Read | ||||
| M16 Alarm Contents (Latest) | Read | ||||
| M17 Alarm Contents (Last) | Read | ||||
| M18 Alarm Contents (2nd last) | Read | ||||
| M19 Alarm Contents (3rd last) | Read | ||||
| M20 Cumulative Operation Time | h | Read | |||
| M21 DC link Circuit Voltage | V | Read | |||
| M23 Model Code | Read | ||||
| M24 Capacity Code | Read | ||||
| M25 ROM Version | Read | ||||
| M26 Transmission Error Transaction Code | Read | ||||
| M27 Frequency Reference on Alarm (p.u.) (Final Command) | Read | ||||
| M31 Frequency Reference on Alarm (Final Command) | Hz | Read | |||
| M32 Output Frequency 1 on Alarm (p.u.) | Read | ||||
| M33 Torque Value on Alarm | % | Read | |||
| M35 Output Frequency on Alarm | Hz | Read | |||
| M36 Input Power on Alarm | % | Read | |||
| M37 Output Current Effective Value on Alarm | % | Read | |||
| M38 Output Voltage Effective Value on Alarm | V | Read | |||
| M39 Operation Command on Alarm | Read | ||||
| M40 Operation Status on Alarm | Read | ||||
| M41 Output terminal Information on Alarm | Read | ||||
| M42 Cumulative Operation Time on Alarm | h | Read | |||
| M43 DC Link Circuit Voltage on Alarm | V | Read | |||
| M45 Heat Sink Temperature on Alarm | °C | Read | |||
| M46 Life of Main Circuit Capacitor | % | Read | |||
| M47 Life of PC Board Electrolytic Capacitor | h | Read | |||
| M48 Life of Cooling Fan | h | Read | |||
| M49 Input Terminal Voltage[12] (p.u.) | Read | ||||
| M50 Input Terminal Current[C1] (p.u.) | Read | ||||
| M62 Heat Sink Temperature | °C | Read | |||
| M68 PID Final Command | Read | ||||
| M69 Inverter Rated Current | Read | ||||
| M70 Operation Status 2 | Read | ||||
| M71 Input Terminal Information | Read | ||||
| M72 PID Feedback Value | Read | ||||
| M73 PID Output | Read | ||||
| M74 Running Status 2 | Read | ||||
| M81 Remaining Time Before The Next Motor 1 Maintenance | h | Read | |||
| M85 Remaining Startup Times Before The Next Maintenance | Read | ||||
| J01 PID Control (Mode selection) | Read and write | ||||
| J02 PID Control (Remote command SV) | Read and write | ||||
| J03 PID Control P (Gain) | Read and write | ||||
| J04 PID Control I (Integral time) | s | Read and write | |||
| J05 PID Control D (Differential time) | s | Read and write | |||
| J06 PID Control (Feedback filter) | s | Read and write | |||
| J15 PID Control (Stop frequency for slow flowrate) | Hz | Read and write | |||
| J16 PID Control (Slow flowrate level stop latency) | s | Read and write | |||
| J17 PID Control (Starting frequency) | Hz | Read and write | |||
| J23 PID Control (Starting feedback deviation level) | % | Read and write | |||
| J24 PID Control (Starting latency from the flow rate stop) | s | Read and write | |||
| J68 Brake Signal (Brake OFF current) | % | Read and write | |||
| J69 Brake Signal (Brake OFF frequency/speed) | Hz | Read and write | |||
| J70 Brake Signal (Brake OFF timer) | s | Read and write | |||
| J71 Brake Signal (Brake ON frequency/speed) | Hz | Read and write | |||
| J72 Brake Signal (Brake ON timer) | s | Read and write | |||
| y01 RS-485 Communication (Station address) | Read and write | ||||
| y02 RS-485 Communication (Communications error processing) | Read and write | ||||
| y03 RS-485 Communication (Timer) | s | Read and write | |||
| y04 RS-485 Communication (Baud rate) | Read and write | ||||
| y05 RS-485 Communication (Data length) | Read and write | ||||
| y06 RS-485 Communication (Parity check) | Read and write | ||||
| y07 RS-485 Communication (Stop bits) | Read and write | ||||
| y08 RS-485 Communication (No-response error detection time) | s | Read and write | |||
| y09 RS-485 Communication (Response interval) | s | Read and write | |||
| y10 RS-485 Communication (Protocol selection) | Read and write | ||||
| W01 Running Status | Read | ||||
| W02 Frequency Reference | Hz | Read | |||
| W03 Output Frequency (Before slip compensation) | Hz | Read | |||
| W04 Output Frequency (After slip compensation) | Hz | Read | |||
| W05 Output Current | Read | ||||
| W06 Output Voltage | V | Read | |||
| W09 Load Shaft Speed | Read | ||||
| W10 Line Speed | Read | ||||
| W11 PID Process Command | Read | ||||
| W12 PID Feedback Value | Read | ||||
| W17 Load Shaft Set Value | Read | ||||
| W18 Line Speed Set Value | Read | ||||
| W19 Constant Feed Time Set Value | Read | ||||
| W20 Constant Feed Time | Read | ||||
| W21 Input Power | Read | ||||
| W27 Timer Operation Remaining Time | s | Read | |||
| W28 Operation Command Source | Read | ||||
| W29 Frequency and PID Command Source | Read | ||||
| W32 PID Output | % | Read | |||
| W40 Control Circuit Terminal (Input) | Read | ||||
| W41 Control Circuit Terminal (Output) | Read | ||||
| W42 Communications Control Signal (Input) | Read | ||||
| W43 Communications Control Signal (Output) | Read | ||||
| W44 Terminal [12] Input Voltage | V | Read | |||
| W45 Terminal [C1] Input Current | mA | Read | |||
| W46 Terminal [FMA*3] Output Voltage | V | Read | |||
| W67 Cumulative Run Time of Capacitors on Printed Circuit | h | Read | |||
| W68 Cumulative Run Time of Cooling Fan | h | Read | |||
| W70 Cumulative Operation Time | h | Read | |||
| W71 DC link Circuit Voltage | V | Read | |||
| W73 Heat Sink Maximum Temperature | °C | Read | |||
| W74 Maximum Effective Current Value | Read | ||||
| W75 Main Circuit Capacitor's Capacitor | % | Read | |||
| W76 Cumulative Ope. Time of Capacitor on PC Board | h | Read | |||
| W77 Cumulative Ope. Time of Cooling Fan | h | Read | |||
| W78 Number of Startups | Read | ||||
| W79 Cumulative Ope. Time of Motor Driving | h | Read | |||
| W81 Integrating Electric Power | Read | ||||
| W82 Data Used Integrating Electric Power | Read | ||||
| W83 Number of RS-485 Ch1 Errors | Read | ||||
| W84 Contents of RS-485 Ch1 Error | Read | ||||
| W87 Inverter's ROM Version | Read | ||||
| W89 Remote Keypad's ROM Version | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show output frequency, current and DC link voltage of each drive on a ModbusCloud dashboard.
- Send an email alert when a new alarm code appears in the latest alarm register.
- Keep 365 days of history of current and heat sink temperature to spot a pump that works harder over time.
- Write a new frequency reference from ModbusCloud when the drive runs under communication control.
- Export the cumulative run time and capacitor life values as CSV for maintenance planning.
Installation
Wire the RS-485 port of the FRENIC-Mini to RS485 A and B of the ModbusCloud Gateway and terminate the bus at both ends.
On the keypad, set y10 to 0 (Modbus RTU) and check y01 (station address), y04 (baud rate) and y06 (parity).
To start and stop the drive over Modbus, set H30 so the run command and frequency come from communication.
In ModbusCloud, add a Modbus device with 19200 baud, no parity, 8 data bits and 2 stop bits, or the values you set, and import this template.
Check that output frequency and output current match the keypad display.
Things to watch for
The drive does not answer. What should I check?
The factory setting of y10 is 1, the FRENIC Loader protocol. Set y10 to 0 for Modbus RTU. Then check station address, baud rate and parity: with y06 = 0 Modbus RTU uses no parity and 2 stop bits.
Writing the frequency reference or run command has no effect. Why?
The drive only follows commands from the RS-485 link when H30 allows it. Check H30 and the frequency command source F01, and make sure the drive is not in local mode on the keypad. The setting codes F to y and the command codes S are writable; only change a setting when you know what it does and note the old value.
Acceleration time and some motor values look like odd numbers. Are they wrong?
These function codes use a Fuji floating point word with sign, exponent and mantissa. The template reads the raw word; the register comment explains how to turn it into seconds or another value.