Grundfos Grundfos CIM 200 Modbus RTU template

Grundfos CIM 200

Monitors Grundfos E-pumps via internal CIM 200 Modbus interface

Template for the Grundfos CIM 200, a Modbus RTU communication interface module installed inside Grundfos E-pumps. It reads operational data such as liquid temperature, volume flow, RPM, motor current, alarms, and operation hours from a wide range of compatible pump models.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
10, read only
Key readings
Pump Liquid Temperature · Electronic Temperature · Volume Flow · RPM · Motor Current · Alarm
Compatible models
CIM 200 · CRE · CRNE · CRIE · MTRE · CHIE · CME · TPE · TPE Series 2000 · NBE · NKE · CUE · MAGNA3
Last updated

Registers (10)

10 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
PumpLiquidTemp°CRead
ElectronicTemp°CRead
VolumeFlow m3m³Read
AlarmRead
RPMrpmRead
FrequencyHzRead
MotorCurrentARead
RelativePerformance%Read
OperationTimeHIHrRead
OperationTimeLoHr.Read

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor pump liquid temperature and volume flow on a live cloud dashboard for remote HVAC oversight.
  • Create an alert when the CIM 200 reports an alarm condition so the installer can respond quickly.
  • Log motor current and RPM trends over time to detect early signs of pump wear or blockage.
  • Track cumulative operation hours across multiple Grundfos E-pumps to plan preventive maintenance schedules.
  • Compare electronic temperature readings across pump installations to identify units at risk of overheating.

Installation

  1. Install the CIM 200 module inside the Grundfos E-pump using the internal 10-pin connector, following the Grundfos installation manual.

  2. Wire the RS-485 Modbus RTU bus (A, B, and GND) from the CIM 200 terminal to the ModbusCloud Gateway.

  3. Set the Modbus slave address on the CIM 200 to a unique value that does not conflict with other devices on the bus.

  4. Confirm the baud rate is set to 19200 on both the CIM 200 and the ModbusCloud gateway.

  5. Import the Grundfos CIM 200 template in the ModbusCloud platform and assign it to the correct gateway and slave address.

  6. Verify that live readings such as pump liquid temperature, RPM, and motor current appear on the ModbusCloud dashboard.

Things to watch for

What baud rate should I use for the CIM 200?

The default baud rate is 19200. Make sure this matches the setting on the ModbusCloud gateway. If communication fails, double-check the parity and stop bit settings as well.

Why does the operation time value look incorrect?

Operation time is split across two 32-bit registers: OperationTimeHI at address 326 and OperationTimeLo at address 328. The template combines these automatically, but if registers are read out of order or partially, the value may appear wrong. Ensure both registers are polled in the same read cycle.

Can I control the pump speed or setpoint through this template?

No. The Grundfos CIM 200 template is read-only and does not include control registers. It is designed for monitoring pump status and operational data only.

Which Grundfos pump models are supported?

The template supports all Grundfos E-pumps that accept the CIM 200 module. This includes CRE, CRNE, CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE, NKE, CUE drives, and MAGNA3 pumps.

Want to see how it works?

Electrician working in an open distribution board