Iskra IE38MD
Three-phase MID energy meter, 80 A direct, with per-phase measurements and 20 energy counters.
The Iskra IE38MD is a three-phase MID energy meter for direct connection up to 80 A that measures energy, power and power quality per phase on a DIN rail. This Modbus RTU template reads voltages, currents, power, power factor, frequency, THD and all energy counters, and lets you set tariff, counters and communication from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 115200 baud
- Registers
- 679, read and write
- Brand
- Iskra
- Key readings
- Voltage per phase · Current per phase · Active power · Reactive power · Power factor · Frequency · Energy counters · Active tariff
- Available commands
- Active tariff · Energy counter reset · Communication settings · Energy counter configuration · LCD settings
- Compatible models
- IE38MD
- Last updated
Registers (679)
679 read, 154 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Voltage U1 | V | Read | |||
| Voltage U2 | V | Read | |||
| Voltage U3 | V | Read | |||
| Average Phase Voltage | V | Read | |||
| Voltage U12 | V | Read | |||
| Voltage U23 | V | Read | |||
| Voltage U31 | V | Read | |||
| Average Line Voltage | V | Read | |||
| Current I1 | A | Read | |||
| Current I2 | A | Read | |||
| Current I3 | A | Read | |||
| Total Current | A | Read | |||
| Neutral Current Calculated | A | Read | |||
| Neutral Current Measured | A | Read | |||
| Average Current | A | Read | |||
| Active Power L1 | W | Read | |||
| Active Power L2 | W | Read | |||
| Active Power L3 | W | Read | |||
| Active Power Total | W | Read | |||
| Reactive Power L1 | var | Read | |||
| Reactive Power L2 | var | Read | |||
| Reactive Power L3 | var | Read | |||
| Reactive Power Total | var | Read | |||
| Apparent Power L1 | VA | Read | |||
| Apparent Power L2 | VA | Read | |||
| Apparent Power L3 | VA | Read | |||
| Apparent Power Total | VA | Read | |||
| Power Factor L1 | Read | ||||
| Power Factor L2 | Read | ||||
| Power Factor L3 | Read | ||||
| Power Factor Total | Read | ||||
| Cap Ind Power Factor L1 | Read | ||||
| Cap Ind Power Factor L2 | Read | ||||
| Cap Ind Power Factor L3 | Read | ||||
| Cap Ind Power Factor Total | Read | ||||
| Angle U1 I1 | Read | ||||
| Angle U2 I2 | Read | ||||
| Angle U3 I3 | Read | ||||
| Power Angle Total | Read | ||||
| Angle U1 U2 | Read | ||||
| Angle U2 U3 | Read | ||||
| Angle U3 U1 | Read | ||||
| Frequency | Hz | Read | |||
| THD I1 | % | Read | |||
| THD I2 | % | Read | |||
| THD I3 | % | Read | |||
| Internal Temperature | Read | ||||
| Run Time Float | s | Read | |||
| Average Phase Voltage Quick | V | Read | |||
| Average Line Voltage Quick | V | Read | |||
| Total Current Quick | A | Read | |||
| Active Power Total Quick | W | Read | |||
| Reactive Power Total Quick | var | Read | |||
| Apparent Power Total Quick | VA | Read | |||
| Power Factor Total Quick | Read | ||||
| Frequency Quick | Hz | Read | |||
| Energy Counter n1 Float | Read | ||||
| Energy Counter n2 Float | Read | ||||
| Energy Counter n3 Float | Read | ||||
| Energy Counter n4 Float | Read | ||||
| Active Tariff Float | Read | ||||
| Energy Counter n1 Float Energy Block | Read | ||||
| Energy Counter n2 Float Energy Block | Read | ||||
| Energy Counter n3 Float Energy Block | Read | ||||
| Energy Counter n4 Float Energy Block | Read | ||||
| Energy Counter 1 Float | Read | ||||
| Energy Counter 2 Float | Read | ||||
| Energy Counter 3 Float | Read | ||||
| Energy Counter 4 Float | Read | ||||
| Energy Counter 5 Float | Read | ||||
| Energy Counter 6 Float | Read | ||||
| Energy Counter 7 Float | Read | ||||
| Energy Counter 8 Float | Read | ||||
| Energy Counter 9 Float | Read | ||||
| Energy Counter 10 Float | Read | ||||
| Energy Counter 11 Float | Read | ||||
| Energy Counter 12 Float | Read | ||||
| Energy Counter 13 Float | Read | ||||
| Energy Counter 14 Float | Read | ||||
| Energy Counter 15 Float | Read | ||||
| Energy Counter 16 Float | Read | ||||
| Nominal Phase Voltage | Read | ||||
| Nominal Phase Current | Read | ||||
| Nominal Phase Power | Read | ||||
| Nominal Total Power | Read | ||||
| Nominal Total Current | Read | ||||
| Nominal Frequency | Read | ||||
| Status Register | Read | ||||
| Phase Valid Measurement | Read | ||||
| Checksum Status | Read | ||||
| Current Active Tariff | Read | ||||
| Alarm Status Flags G1 G2 | Read | ||||
| Alarm Status Flags G3 G4 | Read | ||||
| Alarm Status Flags GE | Read | ||||
| Logic Functions Values | Read | ||||
| IO 1 Value | Read | ||||
| IO 2 Value | Read | ||||
| IO 3 Value | Read | ||||
| IO 4 Value | Read | ||||
| External Relay Status | Read | ||||
| MID Lock Status | Read | ||||
| Internal Temperature T17 | Read | ||||
| THD U1 Actual | % | Read | |||
| THD U2 Actual | % | Read | |||
| THD U3 Actual | % | Read | |||
| THD I1 Actual | % | Read | |||
| THD I2 Actual | % | Read | |||
| THD I3 Actual | % | Read | |||
| Angle U1 U2 T17 | Read | ||||
| Angle U2 U3 T17 | Read | ||||
| Angle U3 U1 T17 | Read | ||||
| Angle U2 I2 T17 | Read | ||||
| Angle U3 I3 T17 | Read | ||||
| Frequency Raw | Read | ||||
| Voltage U1 Raw | Read | ||||
| Voltage U2 Raw | Read | ||||
| Voltage U3 Raw | Read | ||||
| Average Phase Voltage Raw | Read | ||||
| Voltage U12 Raw | Read | ||||
| Voltage U23 Raw | Read | ||||
| Voltage U31 Raw | Read | ||||
| Average Line Voltage Raw | Read | ||||
| Current I1 Raw | Read | ||||
| Current I2 Raw | Read | ||||
| Current I3 Raw | Read | ||||
| Neutral Current Calculated Raw | Read | ||||
| Average Current Raw | Read | ||||
| Total Current Raw | Read | ||||
| Apparent Power Total Raw | Read | ||||
| Apparent Power L1 Raw | Read | ||||
| Apparent Power L2 Raw | Read | ||||
| Apparent Power L3 Raw | Read | ||||
| Active Power Total Raw | Read | ||||
| Active Power L1 Raw | Read | ||||
| Active Power L2 Raw | Read | ||||
| Active Power L3 Raw | Read | ||||
| Reactive Power Total Raw | Read | ||||
| Reactive Power L1 Raw | Read | ||||
| Reactive Power L2 Raw | Read | ||||
| Reactive Power L3 Raw | Read | ||||
| Power Factor Total Raw | Read | ||||
| Power Factor L1 Raw | Read | ||||
| Power Factor L2 Raw | Read | ||||
| Power Factor L3 Raw | Read | ||||
| Last Average Interval Duration | s | Read | |||
| Time Since Last Average | s | Read | |||
| Average Measurements Counter | Read | ||||
| Average Timestamp | Read | ||||
| Interval Avg Frequency Raw | Read | ||||
| Interval Avg Voltage U1 Raw | Read | ||||
| Interval Avg Voltage U2 Raw | Read | ||||
| Interval Avg Voltage U3 Raw | Read | ||||
| Interval Avg Average Phase Voltage Raw | Read | ||||
| Interval Avg Voltage U12 Raw | Read | ||||
| Interval Avg Voltage U23 Raw | Read | ||||
| Interval Avg Voltage U31 Raw | Read | ||||
| Interval Avg Average Line Voltage Raw | Read | ||||
| Interval Avg Current I1 Raw | Read | ||||
| Interval Avg Current I2 Raw | Read | ||||
| Interval Avg Current I3 Raw | Read | ||||
| Interval Avg Average Current Raw | Read | ||||
| Interval Avg Total Current Raw | Read | ||||
| Interval Avg Apparent Power Total Raw | Read | ||||
| Interval Avg Apparent Power L1 Raw | Read | ||||
| Interval Avg Apparent Power L2 Raw | Read | ||||
| Interval Avg Apparent Power L3 Raw | Read | ||||
| Interval Avg Active Power Total Raw | Read | ||||
| Interval Avg Active Power L1 Raw | Read | ||||
| Interval Avg Active Power L2 Raw | Read | ||||
| Interval Avg Active Power L3 Raw | Read | ||||
| Interval Avg Reactive Power Total Raw | Read | ||||
| Interval Avg Reactive Power L1 Raw | Read | ||||
| Interval Avg Reactive Power L2 Raw | Read | ||||
| Interval Avg Reactive Power L3 Raw | Read | ||||
| Interval Avg Power Factor Total Raw | Read | ||||
| Interval Avg Power Factor L1 Raw | Read | ||||
| Interval Avg Power Factor L2 Raw | Read | ||||
| Interval Avg Power Factor L3 Raw | Read | ||||
| Interval Avg Angle U1 U2 | Read | ||||
| Interval Avg Angle U2 U3 | Read | ||||
| Interval Avg Angle U3 U1 | Read | ||||
| Interval Avg Angle U1 I1 | Read | ||||
| Interval Avg Angle U2 I2 | Read | ||||
| Interval Avg Angle U3 I3 | Read | ||||
| Interval Avg Power Angle Total | Read | ||||
| Interval Avg THD U1 | % | Read | |||
| Interval Avg THD U2 | % | Read | |||
| Interval Avg THD U3 | % | Read | |||
| Interval Avg THD I1 | % | Read | |||
| Interval Avg THD I2 | % | Read | |||
| Interval Avg THD I3 | % | Read | |||
| Interval Max Frequency Raw | Read | ||||
| Interval Max Voltage U1 Raw | Read | ||||
| Interval Max Voltage U2 Raw | Read | ||||
| Interval Max Voltage U3 Raw | Read | ||||
| Interval Max Average Phase Voltage Raw | Read | ||||
| Interval Max Voltage U12 Raw | Read | ||||
| Interval Max Voltage U23 Raw | Read | ||||
| Interval Max Voltage U31 Raw | Read | ||||
| Interval Max Average Line Voltage Raw | Read | ||||
| Interval Max Current I1 Raw | Read | ||||
| Interval Max Current I2 Raw | Read | ||||
| Interval Max Current I3 Raw | Read | ||||
| Interval Max Average Current Raw | Read | ||||
| Interval Max Total Current Raw | Read | ||||
| Interval Max Apparent Power Total Raw | Read | ||||
| Interval Max Apparent Power L1 Raw | Read | ||||
| Interval Max Apparent Power L2 Raw | Read | ||||
| Interval Max Apparent Power L3 Raw | Read | ||||
| Interval Max Active Power Total Raw | Read | ||||
| Interval Max Active Power L1 Raw | Read | ||||
| Interval Max Active Power L2 Raw | Read | ||||
| Interval Max Active Power L3 Raw | Read | ||||
| Interval Max Reactive Power Total Raw | Read | ||||
| Interval Max Reactive Power L1 Raw | Read | ||||
| Interval Max Reactive Power L2 Raw | Read | ||||
| Interval Max Reactive Power L3 Raw | Read | ||||
| Interval Max Power Factor Total Raw | Read | ||||
| Interval Max Power Factor L1 Raw | Read | ||||
| Interval Max Power Factor L2 Raw | Read | ||||
| Interval Max Power Factor L3 Raw | Read | ||||
| Interval Max Angle U1 U2 | Read | ||||
| Interval Max Angle U2 U3 | Read | ||||
| Interval Max Angle U3 U1 | Read | ||||
| Interval Max Angle U1 I1 | Read | ||||
| Interval Max Angle U2 I2 | Read | ||||
| Interval Max Angle U3 I3 | Read | ||||
| Interval Max Power Angle Total | Read | ||||
| Interval Max THD U1 | % | Read | |||
| Interval Max THD U2 | % | Read | |||
| Interval Max THD U3 | % | Read | |||
| Interval Max THD U12 | % | Read | |||
| Interval Max THD U23 | % | Read | |||
| Interval Max THD U31 | % | Read | |||
| Interval Max THD I1 | % | Read | |||
| Interval Max THD I2 | % | Read | |||
| Interval Max THD I3 | % | Read | |||
| Interval Max Internal Temperature | Read | ||||
| Interval Min Frequency Raw | Read | ||||
| Interval Min Voltage U1 Raw | Read | ||||
| Interval Min Voltage U2 Raw | Read | ||||
| Interval Min Voltage U3 Raw | Read | ||||
| Interval Min Average Phase Voltage Raw | Read | ||||
| Interval Min Voltage U12 Raw | Read | ||||
| Interval Min Voltage U23 Raw | Read | ||||
| Interval Min Voltage U31 Raw | Read | ||||
| Interval Min Average Line Voltage Raw | Read | ||||
| Interval Min Current I1 Raw | Read | ||||
| Interval Min Current I2 Raw | Read | ||||
| Interval Min Current I3 Raw | Read | ||||
| Interval Min Average Current Raw | Read | ||||
| Interval Min Total Current Raw | Read | ||||
| Interval Min Apparent Power Total Raw | Read | ||||
| Interval Min Apparent Power L1 Raw | Read | ||||
| Interval Min Apparent Power L2 Raw | Read | ||||
| Interval Min Apparent Power L3 Raw | Read | ||||
| Interval Min Active Power Total Raw | Read | ||||
| Interval Min Active Power L1 Raw | Read | ||||
| Interval Min Active Power L2 Raw | Read | ||||
| Interval Min Active Power L3 Raw | Read | ||||
| Interval Min Reactive Power Total Raw | Read | ||||
| Interval Min Reactive Power L1 Raw | Read | ||||
| Interval Min Reactive Power L2 Raw | Read | ||||
| Interval Min Reactive Power L3 Raw | Read | ||||
| Interval Min Power Factor Total Raw | Read | ||||
| Interval Min Power Factor L1 Raw | Read | ||||
| Interval Min Power Factor L2 Raw | Read | ||||
| Interval Min Power Factor L3 Raw | Read | ||||
| Interval Min Angle U1 U2 | Read | ||||
| Interval Min Angle U2 U3 | Read | ||||
| Interval Min Angle U3 U1 | Read | ||||
| Interval Min Angle U1 I1 | Read | ||||
| Interval Min Angle U2 I2 | Read | ||||
| Interval Min Angle U3 I3 | Read | ||||
| Interval Min Power Angle Total | Read | ||||
| Interval Min THD U1 | % | Read | |||
| Interval Min THD U2 | % | Read | |||
| Interval Min THD U3 | % | Read | |||
| Interval Min THD U12 | % | Read | |||
| Interval Min THD U23 | % | Read | |||
| Interval Min THD U31 | % | Read | |||
| Interval Min THD I1 | % | Read | |||
| Interval Min THD I2 | % | Read | |||
| Interval Min THD I3 | % | Read | |||
| Interval Min Internal Temperature | Read | ||||
| Energy Counter n1 | Read | ||||
| Energy Counter n2 | Read | ||||
| Energy Counter n3 | Read | ||||
| Energy Counter n4 | Read | ||||
| Energy Counter 1 | Read | ||||
| Energy Counter 2 | Read | ||||
| Energy Counter 3 | Read | ||||
| Energy Counter 4 | Read | ||||
| Energy Counter 5 | Read | ||||
| Energy Counter 6 | Read | ||||
| Energy Counter 7 | Read | ||||
| Energy Counter 8 | Read | ||||
| Energy Counter 9 | Read | ||||
| Energy Counter 10 | Read | ||||
| Energy Counter 11 | Read | ||||
| Energy Counter 12 | Read | ||||
| Energy Counter 13 | Read | ||||
| Energy Counter 14 | Read | ||||
| Energy Counter 15 | Read | ||||
| Energy Counter 16 | Read | ||||
| Energy Counter n1 Exponent | Read | ||||
| Energy Counter n2 Exponent | Read | ||||
| Energy Counter n3 Exponent | Read | ||||
| Energy Counter n4 Exponent | Read | ||||
| Energy Counter 1 Exponent | Read | ||||
| Energy Counter 2 Exponent | Read | ||||
| Energy Counter 3 Exponent | Read | ||||
| Energy Counter 4 Exponent | Read | ||||
| Energy Counter 5 Exponent | Read | ||||
| Energy Counter 6 Exponent | Read | ||||
| Energy Counter 7 Exponent | Read | ||||
| Energy Counter 8 Exponent | Read | ||||
| Energy Counter 9 Exponent | Read | ||||
| Energy Counter 10 Exponent | Read | ||||
| Energy Counter 11 Exponent | Read | ||||
| Energy Counter 12 Exponent | Read | ||||
| Energy Counter 13 Exponent | Read | ||||
| Energy Counter 14 Exponent | Read | ||||
| Energy Counter 15 Exponent | Read | ||||
| Energy Counter 16 Exponent | Read | ||||
| Energy Counter n1 x1000 | Read | ||||
| Energy Counter n2 x1000 | Read | ||||
| Energy Counter n3 x1000 | Read | ||||
| Energy Counter n4 x1000 | Read | ||||
| Energy Counter 1 x1000 | Read | ||||
| Energy Counter 2 x1000 | Read | ||||
| Energy Counter 3 x1000 | Read | ||||
| Energy Counter 4 x1000 | Read | ||||
| Energy Counter 5 x1000 | Read | ||||
| Energy Counter 6 x1000 | Read | ||||
| Energy Counter 7 x1000 | Read | ||||
| Energy Counter 8 x1000 | Read | ||||
| Energy Counter 9 x1000 | Read | ||||
| Energy Counter 10 x1000 | Read | ||||
| Energy Counter 11 x1000 | Read | ||||
| Energy Counter 12 x1000 | Read | ||||
| Energy Counter 13 x1000 | Read | ||||
| Energy Counter 14 x1000 | Read | ||||
| Energy Counter 15 x1000 | Read | ||||
| Energy Counter 16 x1000 | Read | ||||
| Run Time | s | Read | |||
| Run Time 34999 | s | Read | |||
| Logger Measurement Parameter | Read | ||||
| Logger Time Interval | min | Read | |||
| Logger Valid Results | Read | ||||
| Logger Last Result Time | min | Read | |||
| Logger Value 1 | Read | ||||
| Logger Value 2 | Read | ||||
| Logger Value 3 | Read | ||||
| Logger Value 4 | Read | ||||
| Logger Value 5 | Read | ||||
| Logger Value 6 | Read | ||||
| Logger Value 7 | Read | ||||
| Logger Value 8 | Read | ||||
| Logger Value 9 | Read | ||||
| Logger Value 10 | Read | ||||
| Logger Value 11 | Read | ||||
| Logger Value 12 | Read | ||||
| Logger Value 13 | Read | ||||
| Logger Value 14 | Read | ||||
| Logger Value 15 | Read | ||||
| Logger Value 16 | Read | ||||
| Logger Value 17 | Read | ||||
| Logger Value 18 | Read | ||||
| Logger Value 19 | Read | ||||
| Logger Value 20 | Read | ||||
| Logger Value 21 | Read | ||||
| Logger Value 22 | Read | ||||
| Logger Value 23 | Read | ||||
| Logger Value 24 | Read | ||||
| Logger Value 25 | Read | ||||
| Logger Value 26 | Read | ||||
| Logger Value 27 | Read | ||||
| Logger Value 28 | Read | ||||
| Logger Value 29 | Read | ||||
| Logger Value 30 | Read | ||||
| Logger Value 31 | Read | ||||
| Logger Value 32 | Read | ||||
| Logger Value 33 | Read | ||||
| Logger Value 34 | Read | ||||
| Logger Value 35 | Read | ||||
| Logger Value 36 | Read | ||||
| Logger Value 37 | Read | ||||
| Logger Value 38 | Read | ||||
| Logger Value 39 | Read | ||||
| Logger Value 40 | Read | ||||
| Logger Value 41 | Read | ||||
| Logger Value 42 | Read | ||||
| Logger Value 43 | Read | ||||
| Logger Value 44 | Read | ||||
| Logger Value 45 | Read | ||||
| Logger Value 46 | Read | ||||
| Logger Value 47 | Read | ||||
| Logger Value 48 | Read | ||||
| Logger Value 49 | Read | ||||
| Logger Value 50 | Read | ||||
| Logger Value 51 | Read | ||||
| Logger Value 52 | Read | ||||
| Logger Value 53 | Read | ||||
| Logger Value 54 | Read | ||||
| Logger Value 55 | Read | ||||
| Logger Value 56 | Read | ||||
| Logger Value 57 | Read | ||||
| Logger Value 58 | Read | ||||
| Logger Value 59 | Read | ||||
| Logger Value 60 | Read | ||||
| Logger Value 61 | Read | ||||
| Logger Value 62 | Read | ||||
| Logger Value 63 | Read | ||||
| Logger Value 64 | Read | ||||
| Logger Value 65 | Read | ||||
| Logger Value 66 | Read | ||||
| Logger Value 67 | Read | ||||
| Logger Value 68 | Read | ||||
| Logger Value 69 | Read | ||||
| Logger Value 70 | Read | ||||
| Logger Value 71 | Read | ||||
| Logger Value 72 | Read | ||||
| Logger Value 73 | Read | ||||
| Logger Value 74 | Read | ||||
| Logger Value 75 | Read | ||||
| Logger Value 76 | Read | ||||
| Logger Value 77 | Read | ||||
| Logger Value 78 | Read | ||||
| Logger Value 79 | Read | ||||
| Logger Value 80 | Read | ||||
| Logger Value 81 | Read | ||||
| Logger Value 82 | Read | ||||
| Logger Value 83 | Read | ||||
| Logger Value 84 | Read | ||||
| Logger Value 85 | Read | ||||
| Logger Value 86 | Read | ||||
| Logger Value 87 | Read | ||||
| Logger Value 88 | Read | ||||
| Logger Value 89 | Read | ||||
| Logger Value 90 | Read | ||||
| Logger Value 91 | Read | ||||
| Logger Value 92 | Read | ||||
| Logger Value 93 | Read | ||||
| Logger Value 94 | Read | ||||
| Logger Value 95 | Read | ||||
| Logger Value 96 | Read | ||||
| Logger Value 97 | Read | ||||
| Logger Value 98 | Read | ||||
| Logger Value 99 | Read | ||||
| Logger Value 100 | Read | ||||
| Logger Value 101 | Read | ||||
| Logger Value 102 | Read | ||||
| Logger Value 103 | Read | ||||
| Logger Value 104 | Read | ||||
| Logger Value 105 | Read | ||||
| Logger Value 106 | Read | ||||
| Logger Value 107 | Read | ||||
| Logger Value 108 | Read | ||||
| Logger Value 109 | Read | ||||
| Logger Value 110 | Read | ||||
| Logger Value 111 | Read | ||||
| Logger Value 112 | Read | ||||
| Logger Value 113 | Read | ||||
| Logger Value 114 | Read | ||||
| Logger Value 115 | Read | ||||
| Logger Value 116 | Read | ||||
| Logger Value 117 | Read | ||||
| Logger Value 118 | Read | ||||
| Logger Value 119 | Read | ||||
| Logger Value 120 | Read | ||||
| Logger Value 121 | Read | ||||
| Logger Value 122 | Read | ||||
| Logger Value 123 | Read | ||||
| Logger Value 124 | Read | ||||
| Logger Value 125 | Read | ||||
| Logger Value 126 | Read | ||||
| Logger Value 127 | Read | ||||
| Logger Value 128 | Read | ||||
| User Password | Read and write | ||||
| Factory Password | Read and write | ||||
| Level 1 User Password | Read and write | ||||
| Level 2 User Password | Read and write | ||||
| Active Access Level | Read and write | ||||
| Manual Password Activation | Read and write | ||||
| Operator Command | Read and write | ||||
| Reset Command Register 2 | Read and write | ||||
| IR External Relay Command | Read and write | ||||
| Select Active Tariff | Read and write | ||||
| Reset Energy Command 1 | Read and write | ||||
| Reset Energy Command 2 | Read and write | ||||
| Installation Password | Read and write | ||||
| Connection And Total Energy Calculation | Read and write | ||||
| Description | Read and write | ||||
| Location | Read and write | ||||
| Connection Mode | Read and write | ||||
| CT Secondary | Read and write | ||||
| CT Primary | Read and write | ||||
| VT Secondary | Read and write | ||||
| VT Primary | Read and write | ||||
| Current Input Range | % | Read and write | |||
| Voltage Input Range | % | Read and write | |||
| Nominal Frequency Setting | Hz | Read and write | |||
| CT Connection | Read and write | ||||
| Time | Read and write | ||||
| Date | Read and write | ||||
| Automatic Summer Time Change | Read and write | ||||
| LCD Configuration | Read and write | ||||
| LCD Contrast | Read and write | ||||
| LCD Backlight Intensity | Read and write | ||||
| LCD Backlight Time Off | min | Read and write | |||
| LCD Scroll Interval | s | Read and write | |||
| LCD Custom Screen 1 Line 1 | Read and write | ||||
| LCD Custom Screen 1 Line 2 | Read and write | ||||
| LCD Custom Screen 1 Line 3 | Read and write | ||||
| LCD Custom Screen 2 Line 1 | Read and write | ||||
| LCD Custom Screen 2 Line 2 | Read and write | ||||
| LCD Custom Screen 2 Line 3 | Read and write | ||||
| LCD Custom Screen 3 Line 1 | Read and write | ||||
| LCD Custom Screen 3 Line 2 | Read and write | ||||
| LCD Custom Screen 3 Line 3 | Read and write | ||||
| LCD Scroll Parameters 1 | Read and write | ||||
| LCD Scroll Parameters 2 | Read and write | ||||
| LCD Scroll Parameters 3 | Read and write | ||||
| LCD Scroll Parameters 4 | Read and write | ||||
| LCD Return Mode | Read and write | ||||
| Average Interval | s | Read and write | |||
| Touch Key Control | Read and write | ||||
| Port 1 Modbus Address | Read and write | ||||
| Port 1 Baud Rate | Read and write | ||||
| Port 1 Stop Bits | Read and write | ||||
| Port 1 Parity | Read and write | ||||
| Port 1 Data Bits | Read and write | ||||
| Port 1 TCP Port | Read and write | ||||
| Port 1 IP Host Name | Read and write | ||||
| Port 1 IP Address | Read and write | ||||
| Port 1 Subnet Mask | Read and write | ||||
| Port 1 Default Router | Read and write | ||||
| WiFi Password | Read and write | ||||
| WiFi SSID | Read and write | ||||
| Bluetooth | Read and write | ||||
| Port 2 Modbus Address | Read and write | ||||
| Port 2 Baud Rate | Read and write | ||||
| Port 2 Stop Bits | Read and write | ||||
| Port 2 Parity | Read and write | ||||
| Port 2 Data Bits | Read and write | ||||
| M-Bus Primary Address | Read and write | ||||
| M-Bus Baud Rate | Read and write | ||||
| M-Bus Secondary Address | Read and write | ||||
| Active Tariff Setting | Read and write | ||||
| Common Energy Counter Exponent | Read and write | ||||
| Total Energy Calculation | Read and write | ||||
| Reactive Power Calculation | Read and write | ||||
| Energy Counter n1 Parameter | Read and write | ||||
| Energy Counter n1 Configuration | Read and write | ||||
| Energy Counter n1 Exponent Setting | Read and write | ||||
| Energy Counter n1 Tariff Selector | Read and write | ||||
| Energy Counter n2 Parameter | Read and write | ||||
| Energy Counter n2 Configuration | Read and write | ||||
| Energy Counter n2 Exponent Setting | Read and write | ||||
| Energy Counter n2 Tariff Selector | Read and write | ||||
| Energy Counter n3 Parameter | Read and write | ||||
| Energy Counter n3 Configuration | Read and write | ||||
| Energy Counter n3 Exponent Setting | Read and write | ||||
| Energy Counter n3 Tariff Selector | Read and write | ||||
| Energy Counter n4 Parameter | Read and write | ||||
| Energy Counter n4 Configuration | Read and write | ||||
| Energy Counter n4 Exponent Setting | Read and write | ||||
| Energy Counter n4 Tariff Selector | Read and write | ||||
| Energy Counter 1 Parameter | Read and write | ||||
| Energy Counter 1 Configuration | Read and write | ||||
| Energy Counter 1 Exponent Setting | Read and write | ||||
| Energy Counter 1 Tariff Selector | Read and write | ||||
| Energy Counter 2 Parameter | Read and write | ||||
| Energy Counter 2 Configuration | Read and write | ||||
| Energy Counter 2 Exponent Setting | Read and write | ||||
| Energy Counter 2 Tariff Selector | Read and write | ||||
| Energy Counter 3 Parameter | Read and write | ||||
| Energy Counter 3 Configuration | Read and write | ||||
| Energy Counter 3 Exponent Setting | Read and write | ||||
| Energy Counter 3 Tariff Selector | Read and write | ||||
| Energy Counter 4 Parameter | Read and write | ||||
| Energy Counter 4 Configuration | Read and write | ||||
| Energy Counter 4 Exponent Setting | Read and write | ||||
| Energy Counter 4 Tariff Selector | Read and write | ||||
| Energy Counter 5 Parameter | Read and write | ||||
| Energy Counter 5 Configuration | Read and write | ||||
| Energy Counter 5 Exponent Setting | Read and write | ||||
| Energy Counter 5 Tariff Selector | Read and write | ||||
| Energy Counter 6 Parameter | Read and write | ||||
| Energy Counter 6 Configuration | Read and write | ||||
| Energy Counter 6 Exponent Setting | Read and write | ||||
| Energy Counter 6 Tariff Selector | Read and write | ||||
| Energy Counter 7 Parameter | Read and write | ||||
| Energy Counter 7 Configuration | Read and write | ||||
| Energy Counter 7 Exponent Setting | Read and write | ||||
| Energy Counter 7 Tariff Selector | Read and write | ||||
| Energy Counter 8 Parameter | Read and write | ||||
| Energy Counter 8 Configuration | Read and write | ||||
| Energy Counter 8 Exponent Setting | Read and write | ||||
| Energy Counter 8 Tariff Selector | Read and write | ||||
| Energy Counter 9 Parameter | Read and write | ||||
| Energy Counter 9 Configuration | Read and write | ||||
| Energy Counter 9 Exponent Setting | Read and write | ||||
| Energy Counter 9 Tariff Selector | Read and write | ||||
| Energy Counter 10 Parameter | Read and write | ||||
| Energy Counter 10 Configuration | Read and write | ||||
| Energy Counter 10 Exponent Setting | Read and write | ||||
| Energy Counter 10 Tariff Selector | Read and write | ||||
| Energy Counter 11 Parameter | Read and write | ||||
| Energy Counter 11 Configuration | Read and write | ||||
| Energy Counter 11 Exponent Setting | Read and write | ||||
| Energy Counter 11 Tariff Selector | Read and write | ||||
| Energy Counter 12 Parameter | Read and write | ||||
| Energy Counter 12 Configuration | Read and write | ||||
| Energy Counter 12 Exponent Setting | Read and write | ||||
| Energy Counter 12 Tariff Selector | Read and write | ||||
| Energy Counter 13 Parameter | Read and write | ||||
| Energy Counter 13 Configuration | Read and write | ||||
| Energy Counter 13 Exponent Setting | Read and write | ||||
| Energy Counter 13 Tariff Selector | Read and write | ||||
| Energy Counter 14 Parameter | Read and write | ||||
| Energy Counter 14 Configuration | Read and write | ||||
| Energy Counter 14 Exponent Setting | Read and write | ||||
| Energy Counter 14 Tariff Selector | Read and write | ||||
| Energy Counter 15 Parameter | Read and write | ||||
| Energy Counter 15 Configuration | Read and write | ||||
| Energy Counter 15 Exponent Setting | Read and write | ||||
| Energy Counter 15 Tariff Selector | Read and write | ||||
| Energy Counter 16 Parameter | Read and write | ||||
| Energy Counter 16 Configuration | Read and write | ||||
| Energy Counter 16 Exponent Setting | Read and write | ||||
| Energy Counter 16 Tariff Selector | Read and write | ||||
| Memory Reference | Read | ||||
| Model Number | Read | ||||
| Serial Number | Read | ||||
| Software Reference | Read | ||||
| Hardware Reference | Read | ||||
| Calibration Voltage | V | Read | |||
| Calibration Current | A | Read | |||
| Accuracy Class | Read | ||||
| MiNet Flag | Read | ||||
| COM1 Communication Type | Read | ||||
| Memory Type | Read | ||||
| IO 1 Type | Read | ||||
| IO 2 Type | Read | ||||
| IO 3 Type | Read | ||||
| IO 4 Type | Read | ||||
| Ethernet MAC Address | Read | ||||
| Ethernet Software Reference | Read | ||||
| Ethernet IP Address | Read | ||||
| Phase Module 1 Software Reference | Read | ||||
| Phase Module 2 Software Reference | Read | ||||
| Phase Module 3 Software Reference | Read | ||||
| Phase Module 1 Checksum | Read | ||||
| Phase Module 2 Checksum | Read | ||||
| Phase Module 3 Checksum | Read | ||||
| Phase Module 1 Calibration Checksum | Read | ||||
| Phase Module 2 Calibration Checksum | Read | ||||
| Phase Module 3 Calibration Checksum | Read | ||||
| Measurement Module Software Reference | Read | ||||
| Measurement Module Checksum | Read | ||||
| Measurement Module Calibration Checksum | Read | ||||
| MID Setting Data Checksum | Read | ||||
| Setting Data Checksum | Read | ||||
| Software Checksum | Read | ||||
| Calibration Time Stamp | Read | ||||
| MID Unlock Counter | Read | ||||
| FW Upgrade Counter | Read | ||||
| Software Checksum HI | Read | ||||
| Measurement Module Checksum HI | Read | ||||
| Phase Module 1 Checksum HI | Read | ||||
| Phase Module 2 Checksum HI | Read | ||||
| Phase Module 3 Checksum HI | Read | ||||
| Software Options | Read | ||||
| Active Communication Port | Read | ||||
| Modbus Max Registers Per Read | Read | ||||
| Device Group | Read | ||||
| Actual Time | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show power and current per phase of a distribution board on a ModbusCloud dashboard.
- Get an email alert when the current on one phase stays above a threshold or the status register is not 0.
- Keep 365 days of energy counter history and export it as CSV for tenant or charge point billing.
- Compare the interval maximum power per week to find peak loads before a grid connection is upgraded.
- Switch the active tariff from ModbusCloud with a scheduled automation when no tariff input is wired.
Installation
Connect RS485 A and B of the IE38MD to the RS485 port of the ModbusCloud Gateway, use twisted pair cable and terminate both ends of the bus.
Check address and speed on the meter: default 33, 115200 baud, 8 data bits, no parity, 2 stop bits. Give every meter on the bus a unique address.
In ModbusCloud, add a Modbus RTU device with the same settings and import this template.
Check that Voltage U1 and Frequency show plausible values, then load the meter and check the currents and powers.
Things to watch for
The meter does not answer. What should I check?
The IE38MD ships at 115200 baud with 2 stop bits and address 33, which differs from many other meters on a shared bus. Set the device in ModbusCloud to the same values or change the meter, swap A and B if needed and check the termination. Only the IE38MD variant has RS485.
Why are the raw values so large?
The registers ending in Raw use the native Iskra format, where the top byte holds a decimal exponent. Use the float registers without Raw for dashboards and alarms; they give the value directly in volts, amps or watts.
The energy counter shows a different unit than expected.
Each counter adds up the quantity set in its Parameter register (active, reactive or apparent energy, per phase or total) with its own exponent. Read Energy Counter Exponent and the counter Parameter to see what a counter holds before you build a report on it.
What should I watch out for when writing settings?
Settings are protected by access levels; without the right password level the meter refuses the write. Changing the address, speed or parity cuts the connection until ModbusCloud uses the new values. A counter reset cannot be undone, and on a MID meter only resettable counters can be reset.
More Iskra templates
Want to see how it works?