Lumel N30U
Panel meter for temperature, resistance and standard signals, with four alarms and an analog output.
The Lumel N30U is a programmable panel meter that measures temperature with RTDs and thermocouples, resistance and 0 to 10 V or 0 to 20 mA signals in control cabinets. This Modbus RTU template reads the displayed value, minimum and maximum and alarm status, and lets you set alarm thresholds, display colours and the input configuration from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 9600 baud
- Registers
- 106, read and write
- Brand
- Lumel
- Key readings
- Displayed value · Measured value · Minimum and maximum · Alarm relay status · Terminal temperature · Meter events
- Available commands
- Alarm thresholds · Display colour thresholds · Input type · Individual characteristic · Analog output range
- Compatible models
- N30U (firmware 2.00 or later)
- Last updated
Registers (106)
106 read, 93 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Displayed Value | Read | 7010 | FC03 | float32 | |
| Measured Value | Read | 7020 | FC03 | float32 | |
| Minimum Value | Read | 7006 | FC03 | float32 | |
| Maximum Value | Read | 7008 | FC03 | float32 | |
| Terminal Temperature | °C | Read | 7018 | FC03 | float32 |
| Thermocouple EMF | mV | Read | |||
| Input Resistance | Ω | Read | |||
| Analog Output Control | % | Read | |||
| Current Time | Read | ||||
| Meter Status | Read | ||||
| Wire Resistance | Read | ||||
| ADC Word | Read | ||||
| Device Identifier | Read | ||||
| Status 1 | Read and write | ||||
| Status 2 | Read and write | ||||
| Colour Change Lower Threshold | Read and write | ||||
| Colour Change Upper Threshold | Read and write | ||||
| Display Narrowing Lower Threshold | Read and write | ||||
| Display Narrowing Upper Threshold | Read and write | ||||
| Alarm 1 Lower Threshold | Read and write | ||||
| Alarm 1 Upper Threshold | Read and write | ||||
| Alarm 2 Lower Threshold | Read and write | ||||
| Alarm 2 Upper Threshold | Read and write | ||||
| Alarm 3 Lower Threshold | Read and write | ||||
| Alarm 3 Upper Threshold | Read and write | ||||
| Alarm 4 Lower Threshold | Read and write | ||||
| Alarm 4 Upper Threshold | Read and write | ||||
| Analog Output Lower Threshold | Read and write | ||||
| Analog Output Upper Threshold | Read and write | ||||
| Characteristic Point 1 Input | Read and write | ||||
| Characteristic Point 1 Output | Read and write | ||||
| Characteristic Point 2 Input | Read and write | ||||
| Characteristic Point 2 Output | Read and write | ||||
| Characteristic Point 3 Input | Read and write | ||||
| Characteristic Point 3 Output | Read and write | ||||
| Characteristic Point 4 Input | Read and write | ||||
| Characteristic Point 4 Output | Read and write | ||||
| Characteristic Point 5 Input | Read and write | ||||
| Characteristic Point 5 Output | Read and write | ||||
| Characteristic Point 6 Input | Read and write | ||||
| Characteristic Point 6 Output | Read and write | ||||
| Characteristic Point 7 Input | Read and write | ||||
| Characteristic Point 7 Output | Read and write | ||||
| Characteristic Point 8 Input | Read and write | ||||
| Characteristic Point 8 Output | Read and write | ||||
| Characteristic Point 9 Input | Read and write | ||||
| Characteristic Point 9 Output | Read and write | ||||
| Characteristic Point 10 Input | Read and write | ||||
| Characteristic Point 10 Output | Read and write | ||||
| Characteristic Point 11 Input | Read and write | ||||
| Characteristic Point 11 Output | Read and write | ||||
| Characteristic Point 12 Input | Read and write | ||||
| Characteristic Point 12 Output | Read and write | ||||
| Characteristic Point 13 Input | Read and write | ||||
| Characteristic Point 13 Output | Read and write | ||||
| Characteristic Point 14 Input | Read and write | ||||
| Characteristic Point 14 Output | Read and write | ||||
| Characteristic Point 15 Input | Read and write | ||||
| Characteristic Point 15 Output | Read and write | ||||
| Characteristic Point 16 Input | Read and write | ||||
| Characteristic Point 16 Output | Read and write | ||||
| Characteristic Point 17 Input | Read and write | ||||
| Characteristic Point 17 Output | Read and write | ||||
| Characteristic Point 18 Input | Read and write | ||||
| Characteristic Point 18 Output | Read and write | ||||
| Characteristic Point 19 Input | Read and write | ||||
| Characteristic Point 19 Output | Read and write | ||||
| Characteristic Point 20 Input | Read and write | ||||
| Characteristic Point 20 Output | Read and write | ||||
| Characteristic Point 21 Input | Read and write | ||||
| Characteristic Point 21 Output | Read and write | ||||
| Input Type | Read and write | ||||
| Averaging Time | s | Read and write | |||
| Characteristic Points | Read and write | ||||
| Decimal Point Position | Read and write | ||||
| Colour Below Lower Threshold | Read and write | ||||
| Colour Between Thresholds | Read and write | ||||
| Colour Above Upper Threshold | Read and write | ||||
| Alarm 1 Input | Read and write | ||||
| Alarm 1 Type | Read and write | ||||
| Alarm 1 Delay | s | Read and write | |||
| Alarm 1 LED Latch | Read and write | ||||
| Alarm 2 Input | Read and write | ||||
| Alarm 2 Type | Read and write | ||||
| Alarm 2 Delay | s | Read and write | |||
| Alarm 2 LED Latch | Read and write | ||||
| Alarm 3 Input | Read and write | ||||
| Alarm 3 Type | Read and write | ||||
| Alarm 3 Delay | s | Read and write | |||
| Alarm 3 LED Latch | Read and write | ||||
| Alarm 4 Input | Read and write | ||||
| Alarm 4 Type | Read and write | ||||
| Alarm 4 Delay | s | Read and write | |||
| Alarm 4 LED Latch | Read and write | ||||
| Analog Output Input | Read and write | ||||
| Analog Output Type | Read and write | ||||
| Baud Rate | Read and write | ||||
| Transmission Mode | Read and write | ||||
| Modbus Address | Read and write | ||||
| Apply Interface Settings | Read and write | ||||
| Restore Default Parameters | Read and write | ||||
| Parameter Password | Read and write | ||||
| Clock Time | Read and write | ||||
| Unit Highlight | Read and write | ||||
| Reset Min Max | Read and write | ||||
| Math Function | Read and write |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show cold room or process temperatures from several N30U meters on one ModbusCloud dashboard.
- Send an email alert when the displayed value passes a threshold you set in ModbusCloud.
- Keep 365 days of history of a 4 to 20 mA level or pressure signal shown on the meter.
- Adjust an alarm threshold or delay on site from the portal without opening the cabinet.
- Get an alert when an alarm relay switches on, using the relay bits of Status 2.
Installation
Check that the meter has the RS485 option and connect terminals A and B to the RS485 port of the ModbusCloud Gateway, with a 120 ohm termination at both ends of the bus.
On the meter, set the address (Addr), baud rate (bAud) and frame format (prot). The default is address 1, 9600 baud, 8N2.
In ModbusCloud, add a Modbus RTU device with the same address and serial settings and import the Lumel N30U template.
Check that Device Identifier reads 183 and that Displayed Value matches the display.
Things to watch for
The meter does not answer on the bus. What should I check?
Check the order code: only versions with the RS485 option have Modbus. Then compare address, baud rate and frame format with the device in ModbusCloud; the default is 8N2, two stop bits, which many tools do not use by default. Address 0 switches the interface off. Swap A and B if the settings match.
I changed the baud rate over Modbus but nothing happened.
New RS485 settings are only used after you write 1 to Apply Interface Settings. After that the meter talks at the new speed and format, so change the device in ModbusCloud to match at the same time.
Why do Terminal Temperature, EMF or Input Resistance stay at zero?
They are only measured for the input that uses them: terminal temperature and EMF with thermocouples or time measurement, resistance with RTDs or resistance inputs. With a voltage or current input these values are not updated.
Is it safe to write settings from ModbusCloud?
Thresholds and colours are harmless, but writing Input Type, the characteristic or Restore Default Parameters changes what the meter shows and switches. Read the current value first and change one setting at a time. If a password is set on the meter, front panel changes still need it.
More Lumel templates