PRO-VENT PRO-VENT RC7 Premium Modbus RTU template

PRO-VENT RC7 Premium

Controls and monitors a PRO-VENT RC7 Premium recuperator via Modbus RTU.

Template for the PRO-VENT RC7 Premium recuperator via Modbus RTU. Reads ventilation status, temperatures, air quality (CO2, PM1, PM2.5, PM10), humidity, bypass position, and filter status. Allows control of ventilation gear, bypass mode, heater/cooler modes, and set temperatures.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
41, read and write
Key readings
Supply/Extract/Inlet/Outside temperatures · CO2 concentration · Relative humidity · PM1, PM2.5, PM10 values · Current supply and extract ventilation capacity · Filter replacement status
Available commands
Ventilation gear set · Bypass workmode · Set temperature device 1 and 2 · Heater/cooler workmode device 1 and 2
Compatible models
RC7 Premium
Last updated

Registers (41)

39 read, 9 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Ventilation gear setRead and write
Heater or cooler workmode device 1Read and write
Current yearRead
Current minuteRead
Current monthRead
Current hourRead
Current workmodeRead
Maximum CO2 concentrationppmRead
Maximum relative air humidity%Read
Bypass workmodeRead and write
GHE workmodeRead
Set temperature for the device 1°CRead and write
Set temperature for the device 2°CRead and write
Heater or cooler workmode device 2Read and write
CleanR workmodeRead
Set point value of PM10 for normal filtrationppmRead
Airing timesRead and write
Day ionization modeRead
Ionization mode at nightRead
Time to replace filtershRead
Current supply ventilation capacityRead
Current ventilation capacityRead
Current position of the bypass%Read
The current power of the pre-heaterWRead
Current position of the recirculation damper%Read
CO2 concentrationppmRead
Relative humidity%Read
Supply air temperature°CRead
Extract air temperature°CRead
Inlet temperature°CRead
The discharge temperature°CRead
Outside temperature°CRead
The current value of PM10ppmRead
The current value of PM2.5ppmRead
The current value of PM1ppmRead
Ventilation workmodeRead
Filters will need to be replaced soon.Read
Bypass stateRead
Airflow statusRead
AiringWrite
GHE workmodeWrite

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor indoor air quality including CO2, PM2.5, and humidity on a live dashboard for residential customers.
  • Create an alert when the filter replacement status indicates the filter needs changing.
  • Remotely adjust ventilation gear and bypass mode to optimize energy recovery during seasonal changes.
  • Set up notifications when CO2 concentration exceeds a healthy threshold for more than 15 minutes.
  • Track supply and extract temperatures over time to verify heat recovery efficiency.
  • Control heater and cooler workmodes remotely to maintain comfortable indoor temperatures.

Installation

  1. Connect the ModbusCloud Gateway to the PRO-VENT RC7 Premium using a twisted pair RS-485 cable wired to the A and B terminals.

  2. Configure the Modbus RTU settings on the RC7 Premium to 19200 baud, odd parity, and assign a unique Modbus slave address.

  3. Set the same baud rate (19200), parity (odd), and slave address on the ModbusCloud gateway to match the RC7 Premium configuration.

  4. Import the PRO-VENT RC7 Premium template from the ModbusCloud template library and assign it to the configured gateway.

  5. Verify that all read registers return valid data on the ModbusCloud dashboard, paying attention to shared register addresses that use different function codes.

  6. Test write operations such as ventilation gear set and bypass workmode to confirm correct control of the unit.

Things to watch for

Why do I get unexpected values when reading bypass or GHE workmode registers?

Some register addresses are shared between different read and write functions, for example address 11. Make sure you are using the correct Modbus function code for each operation. Using the wrong function code can return data from a different parameter.

What baud rate and parity settings does the RC7 Premium require?

The RC7 Premium uses 19200 baud with odd parity. Both the gateway and the recuperator must be configured identically, otherwise communication will fail.

What data format do the registers use?

All registers are uint16 (unsigned 16-bit integer). No special byte order or scaling beyond the default is needed, but always verify sensor readings against the unit display after initial setup.

Can I connect multiple PRO-VENT units on the same RS-485 bus?

Yes, as long as each unit has a unique Modbus slave address. Make sure the RS-485 bus is properly terminated and that the total cable length stays within RS-485 specifications.