Riello UPS Multi Sentry
Online UPS for critical loads: mains, output, battery, load and alarms over the network.
The Riello UPS Multi Sentry is an online double-conversion UPS that protects servers and critical equipment in data centres, server rooms and utility buildings. This Modbus TCP template reads mains, output and battery values, load, remaining backup time and alarms, and lets you start a battery test or a controlled shutdown from ModbusCloud.
- Protocol
- Modbus TCP
- Connection
- Ethernet, Modbus TCP
- Registers
- 78, read and write
- Brand
- Riello UPS
- Key readings
- Input voltage · Output voltage · Output current · Load per phase · Battery charge · Remaining backup time · UPS temperature · UPS alarms
- Available commands
- Shutdown and restore · Battery test · Transfer to bypass
- Compatible models
- Multi Sentry MSM · Multi Sentry MST
- Last updated
Registers (78)
78 read, 3 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Input Voltage V1 | V | Read | |||
| Input Voltage V2 | V | Read | |||
| Input Voltage V3 | V | Read | |||
| Input Current L1 | A | Read | |||
| Input Current L2 | A | Read | |||
| Input Current L3 | A | Read | |||
| Input Frequency | Hz | Read | |||
| Output Voltage V1 | V | Read | |||
| Output Voltage V2 | V | Read | |||
| Output Voltage V3 | V | Read | |||
| Output Current L1 | A | Read | |||
| Output Current L2 | A | Read | |||
| Output Current L3 | A | Read | |||
| Output Peak Current L1 | A | Read | |||
| Output Peak Current L2 | A | Read | |||
| Output Peak Current L3 | A | Read | |||
| Load L1 | % | Read | |||
| Load L2 | % | Read | |||
| Load L3 | % | Read | |||
| Output Active Power L1 | kW | Read | |||
| Output Active Power L2 | kW | Read | |||
| Output Active Power L3 | kW | Read | |||
| Output Frequency | Hz | Read | |||
| Bypass Voltage V1 | V | Read | |||
| Bypass Voltage V2 | V | Read | |||
| Bypass Voltage V3 | V | Read | |||
| Bypass Frequency | Hz | Read | |||
| Battery Voltage | V | Read | |||
| Positive Battery Voltage | V | Read | |||
| Negative Battery Voltage | V | Read | |||
| Battery Current | A | Read | |||
| Remaining Battery Capacity | % | Read | |||
| Remaining Backup Time | min | Read | |||
| Total Output Energy | kWh | Read | |||
| Internal UPS Temperature | °C | Read | |||
| Sensor 1 Temperature | °C | Read | |||
| Sensor 2 Temperature | °C | Read | |||
| Test In Progress | Read | ||||
| Shutdown Active | Read | ||||
| Battery Charged | Read | ||||
| Battery Charging | Read | ||||
| Bypass Bad | Read | ||||
| Normal Operation | Read | ||||
| On Bypass | Read | ||||
| Battery Low | Read | ||||
| Battery Working | Read | ||||
| UPS Locked | Read | ||||
| Output Powered | Read | ||||
| Input Mains Present | Read | ||||
| Alarm Temperature | Read | ||||
| Alarm Overload | Read | ||||
| UPS Failure | Read | ||||
| Communication Lost With UPS | Read | ||||
| Status Word 1 | Read | ||||
| Status Word 2 | Read | ||||
| Status Word 3 | Read | ||||
| Status Word 4 | Read | ||||
| Output Nominal Voltage | V | Read | |||
| Output Nominal Frequency | Hz | Read | |||
| Output Nominal Power | VA | Read | |||
| Battery Nominal Capacity | Read | ||||
| Battery Benches | Read | ||||
| Battery Type | Read | ||||
| Command Code | Read and write | ||||
| Shutdown Delay Time | s | Read and write | |||
| Restore Delay Time | min | Read and write | |||
| Command Result | Read | ||||
| Correct Messages Counter | Read | ||||
| Incorrect Messages Counter | Read | ||||
| Special Flags S | Read | ||||
| Special Flags C | Read | ||||
| Special Flags B | Read | ||||
| Special Flags R1 | Read | ||||
| Special Flags R2 I1 | Read | ||||
| Special Flags I2 | Read | ||||
| Special Flags A1 | Read | ||||
| Special Flags A2 | Read | ||||
| NetMan Firmware Version | Read |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show input, output and battery values of every UPS on one dashboard per site.
- Get an alarm by email as soon as the UPS switches to battery or the battery is low.
- Track load per phase and output energy in the history to see how much spare capacity is left.
- Watch the remaining backup time and the internal temperature to plan battery replacement.
- Start a battery test remotely and check the result without visiting the site.
Installation
Fit a NetMan 204 card in a free communication slot of the Multi Sentry and connect it to the network of the ModbusCloud Gateway.
Open the web interface of the card, give it a fixed IP address and check that Modbus TCP is active on port 502.
In ModbusCloud, add a Modbus TCP device with the IP address of the card, port 502 and unit ID 1, and import this template.
Check that the input and output voltages come in with plausible values, then set up dashboards and alarms.
Things to watch for
The UPS does not answer. What should I check?
Check that the gateway reaches the IP address of the NetMan 204 card and that nothing blocks port 502 between them. After a restart the card needs about two minutes before it answers. If the card answers but every value stays empty, check the state Communication Lost With UPS: the card is then not talking to the UPS itself.
Some values show 65535 or -1. Is the template wrong?
No. The card returns 0xFFFF for a value the UPS does not provide, for example bypass values on some versions or a temperature sensor that is not connected. Leave those registers out of your dashboard or ignore that value in alarms.
How do I send a command such as a battery test?
Write the code to Command Code: 20 for a battery test, 1 for shutdown, 2 for shutdown and restore, 12 for bypass, 3 to cancel a shutdown or bypass command. Set Shutdown Delay Time and Restore Delay Time first when you use them. Command Result then shows the code when the UPS carried it out, or the code plus 100 when it did not.
Can I read several UPS units on one gateway?
Yes. Every UPS has its own NetMan 204 card with its own IP address. Add each card as a separate Modbus TCP device in ModbusCloud and import the template for each one.
Want to see how it works?