Riello UPS NetMan 208

Network card for Riello UPS systems with voltages, load, battery status and alarms over Modbus TCP.

The Riello UPS NetMan 208 is a network card that makes the status of a Riello UPS available on the local network, from mains and output voltages to battery charge and alarms. This Modbus TCP template reads voltages, load, battery charge, back-up time and the alarm flags, and lets you send shutdown and battery test commands from ModbusCloud.

Protocol
Modbus TCP
Connection
Ethernet, Modbus TCP
Registers
44, read and write
Key readings
Input and output voltage · Load per phase · Battery charge · Remaining back-up time · Battery voltage · UPS temperature · On battery · UPS failure
Available commands
Shutdown and restore command · Battery test · Shutdown delay · Restore delay
Compatible models
NetMan 208 · Riello UPS with a NetMan 208 network card
Last updated

Registers (44)

44 read, 3 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Input Voltage L1VRead11FC03uint16
Input Voltage L2VRead12FC03uint16
Input Voltage L3VRead13FC03uint16
Input FrequencyHzRead17FC03uint16
Output Voltage L1VRead25FC03uint16
Output Voltage L2VRead
Output Voltage L3VRead
Output FrequencyHzRead
Load L1%Read
Load L2%Read
Load L3%Read
Bypass Voltage L1VRead
Bypass Voltage L2VRead
Bypass Voltage L3VRead
Bypass FrequencyHzRead
Battery VoltageVRead
Battery Charge%Read
AutonomyminRead
Internal UPS Temperature°CRead
Test In ProgressRead
Shutdown ActiveRead
Battery ChargedRead
Bypass BadRead
Normal OperationRead
On BypassRead
Battery LowRead
Battery WorkingRead
UPS LockedRead
Output PoweredRead
Input Mains PresentRead
Temperature AlarmRead
Overload AlarmRead
UPS FailureRead
Communication Lost With UPSRead
Command CodeRead and write
Shutdown Delay TimesRead and write
Restore Delay TimeminRead and write
Command ResultRead
Output Nominal VoltageVRead
Output Nominal FrequencyHzRead
Output Nominal Apparent PowerkVARead
Output Nominal Active PowerkWRead
Battery Nominal CapacityRead
Battery BenchesRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Get an email from ModbusCloud as soon as the UPS switches to battery or loses mains power.
  • Set an alarm on remaining back-up time so you know when the battery can no longer carry the load.
  • Track load per phase in the history to see whether the UPS still has room for new equipment.
  • Alert on overload, temperature and UPS failure flags across all sites in one fleet overview.
  • Start a battery test from the portal and read the command result afterwards.
  • Compare battery voltage and charge over months to spot an ageing battery before it fails.

Installation

  1. Connect the NetMan 208 to the network where the ModbusCloud Gateway hangs, or to the Gateway's LAN port.

  2. Give the card a fixed IP address or a DHCP reservation, and turn on Modbus in its web interface under Modbus/BACnet.

  3. In ModbusCloud, add a Modbus TCP device with the IP address of the card, port 502 and unit ID 1, then import this template.

  4. Check that Input Mains Present reads 1 and that the output voltage matches the nominal voltage.

Things to watch for

The card does not answer on port 502. What should I check?

Check that Modbus is turned on in the NetMan 208 web interface, that the IP address is correct and that the Gateway and the card are in the same network or can route to each other. A firewall between them must allow TCP port 502.

Why do the L2 and L3 values show 65535?

On a single-phase UPS the registers for phase 2 and 3 report 65535 because those phases do not exist. Hide them in your dashboard or ignore them in your alarm rules.

Communication Lost With UPS is 1. Is the UPS down?

Not necessarily. The flag means the card no longer talks to the UPS itself. Check that the card is seated properly in the slot and restart the card. While the flag is set, the other values are not current.

What should I know before writing a command?

Command 1 shuts the UPS down and removes power from the load after the shutdown delay. Command 2 also restores it after the restore delay. Set the delay registers first, write the command code, then read Command Result: the code itself means accepted, code plus 100 means the UPS did not handle it. Command 3 cancels a pending shutdown.

Want to see how it works?

Electrician working in an open distribution board