Saia Burgess AWD3

Three-phase CT energy meter for energy, voltage, current, power and cos phi per phase.

The Saia Burgess AWD3 is a three-phase energy meter that measures energy, voltage, current and power through current transformers up to 1500 A in switchboards. This Modbus RTU template reads energy, per-phase values and phase errors, and lets you reset the partial counter and set the Modbus address from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
32, read and write
Key readings
Total energy · Voltage per phase · Current per phase · Active power · Reactive power · Cos phi · Phase errors
Available commands
Partial energy counter reset · Modbus address
Compatible models
AWD3D5WD00C2A00 · AWD3D5WD00C3A00 · AWD3D5WD00C3A44
Last updated

Registers (32)

32 read, 2 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Voltage L1VRead35FC03uint16
Current L1ARead36FC03uint16
Active Power L1kWRead37FC03uint16
Reactive Power L1kvarRead38FC03int16
Cos Phi L1Read39FC03uint16
Voltage L2VRead
Current L2ARead
Active Power L2kWRead
Reactive Power L2kvarRead
Cos Phi L2Read
Voltage L3VRead
Current L3ARead
Active Power L3kWRead
Reactive Power L3kvarRead
Cos Phi L3Read
Total Active PowerkWRead
Total Reactive PowerkvarRead
Energy Total Tariff 1kWhRead
Energy Partial Tariff 1kWhRead and write
Error RegisterRead
Communication StatusRead
Current Transformer RatioRead
Modbus AddressRead and write
Baud RateRead
Response TimeoutmsRead
Firmware VersionRead
Hardware VersionRead
Type DesignationRead
Serial Number LowRead
Serial Number HighRead
Number of Supported RegistersRead
Number of Supported FlagsRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show energy and power per phase of a feeder on a dashboard in ModbusCloud.
  • Log total energy to report consumption per tenant or installation month by month.
  • Get an alert when the error register is not 0, so a missing phase or wrong CT direction stands out.
  • Reset the partial counter at the start of a period and compare it with the previous one.
  • Watch cos phi per phase to spot a poor power factor on a group of machines.

Installation

  1. Connect RS485 terminals D and /D of the meter to the RS485 port of the ModbusCloud Gateway and put a terminator at both ends of the bus.

  2. Make sure phase 1 is connected, otherwise the interface stays silent.

  3. Set the Modbus address on the meter: hold the right key for 3 seconds, then set the address.

  4. In ModbusCloud, add a Modbus device with the same address, 19200 baud, 8E1, and import this template.

  5. Check that voltage reads about 230 V per phase and that the CT ratio matches the transformers.

Things to watch for

The meter does not answer. What should I check?

Phase 1 must be connected and the meter needs 30 seconds after power on. Check the address on the display, swap D and /D, and fit a terminator because the meter has none. Baud rate and parity are detected automatically; the A44 version only talks 8N1.

Why does current show ten times too much?

With CT ratio 5/5 the meter reports current in 0.1 A instead of whole amps. Set the scale of the three current values to 0.1 in ModbusCloud if you use that ratio.

Values change only every few readings. Is that normal?

Yes. The meter refreshes its values every 10 seconds, so faster reads return the same values. Busy buses can make the refresh slower.

How do I write to the meter from ModbusCloud?

The partial energy counter and the Modbus address are writable. The meter only accepts write multiple registers, and the partial counter resets when you write 0 to both of its registers in one message. Writing must be enabled for the gateway first; a wrong address makes the meter unreachable until you set it on the display.

Want to see how it works?

Electrician working in an open distribution board