Sentera Sentera RCMFF-3 Modbus RTU template

Sentera RCMFF-3

Room sensor for CO2, temperature and humidity that controls ventilation through its output.

The Sentera RCMFF-3 is a room sensor that measures CO2, temperature, relative humidity and ambient light and controls ventilation through one analogue output. This Modbus RTU template reads CO2, temperature, humidity, dew point and alarm flags and lets you set CO2 alert levels and override the output from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
56, read and write
Brand
Sentera
Key readings
CO2 concentration · Temperature · Relative humidity · Dew point · Ambient light · Output value · Sensor alarms
Available commands
CO2 alert levels · CO2 range for the output · Output override · Sensor selection · LED settings
Compatible models
RCMFF-3 · RCMFG-3 · RCMFH-3
Last updated

Registers (56)

56 read, 32 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
CO2 LevelppmRead
Temperature°CRead
Relative Humidity%RHRead
Dew Point°CRead
Ambient LightluxRead
Active Standby StateRead
Actual Output Value%Read
Output Control ModeRead
Temperature Output Value%Read
Humidity Output Value%Read
CO2 Output Value%Read
CO2 Alert 1Read
CO2 Alert 2Read
CO2 Sensor StateRead
Temperature Alert FlagRead
Temperature Range Limit FlagRead
Temperature Sensor StateRead
Humidity Alert FlagRead
Humidity Range Limit FlagRead
Humidity Sensor StateRead
Ambient Light Sensor StateRead
CO2 Alert 1 LevelppmRead and write
CO2 Alert 2 LevelppmRead and write
Minimum CO2 RangeppmRead and write
Maximum CO2 RangeppmRead and write
CO2 Self CalibrationRead and write
Minimum Temperature Alert°CRead and write
Maximum Temperature Alert°CRead and write
Minimum Humidity Alert%RHRead and write
Maximum Humidity Alert%RHRead and write
Minimum Temperature Range°CRead and write
Maximum Temperature Range°CRead and write
Minimum Humidity Range%RHRead and write
Maximum Humidity Range%RHRead and write
Active Light LevelluxRead and write
Standby Light LevelluxRead and write
Output 1 ModeRead and write
Output 1 Overwrite EnableRead and write
Output 1 Overwrite Value%Read and write
Output 1 PWM Voltage SourceRead and write
Output 1 Minimum%Read and write
Output 1 Maximum%Read and write
Temperature Sensor SelectionRead and write
Humidity Sensor SelectionRead and write
CO2 Sensor SelectionRead and write
LED IndicationRead and write
LED Brightness%Read and write
Modbus AddressRead and write
Modbus Baud RateRead and write
Modbus ParityRead and write
Modbus Safety TimeoutminRead and write
Network TerminationRead and write
Modbus Registers ResetRead and write
Device TypeRead
Hardware VersionRead
Firmware VersionRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show CO2, temperature and humidity per room on a ModbusCloud dashboard.
  • Get an email when CO2 alert 2 is active for a classroom or meeting room.
  • Keep 365 days of CO2 history to show indoor air quality over the seasons.
  • Raise or lower the CO2 alert levels remotely when the use of a room changes.
  • Override the fan output from the portal during commissioning and hand it back to the sensor afterwards.

Installation

  1. Connect 24 V supply, A and B to the sensor and run the RS485 bus to the ModbusCloud Gateway.

  2. Switch on the built-in termination on the last device of the line and terminate the other end at the Gateway.

  3. Give every Sentera device on the bus its own address; the factory default is address 1 at 19200 baud, 8E1.

  4. In ModbusCloud, add a Modbus device with that address and settings and import the Sentera RCMFF-3 template.

  5. Check that CO2, temperature and humidity match the room; CO2 in an empty, aired room is close to outside level.

Things to watch for

The sensor does not answer on the bus. What should I check?

Check the supply, A and B, and that address, baud rate and parity in ModbusCloud match the sensor. The factory setting is address 1, 19200 baud, 8E1. New Sentera devices all start at address 1, so connect them one at a time and give each its own address first.

Why does the CO2 value drift over time?

With self calibration on, the sensor takes the lowest level of the past days as outside air. In a room that never airs out, that lowers the readings. Switch self calibration off in such rooms, or make sure the room reaches outside air level at least once a week.

The output does not follow the value I write. Why?

The override value only works when output override is enabled. Set the enable register to 1 first, then write the value, and set it back to 0 afterwards. When the Modbus safety timeout runs out without traffic, the output goes to its minimum.

What should I watch out for when writing settings?

A new address, baud rate or parity takes effect on the sensor, so update the Modbus device in ModbusCloud right after. Writing 1 to the register reset restores all holding registers above 10 to their defaults, including CO2 levels and output settings.