Sentera RSTHM-2

Room transmitter for temperature, humidity and light, powered over its Modbus cable.

The Sentera RSTHM-2 is a room transmitter that measures temperature, relative humidity and ambient light and is powered over its Modbus cable. This Modbus RTU template reads temperature, humidity, dew point, light level and alarm flags and lets you set alert limits and light levels from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
34, read and write
Brand
Sentera
Key readings
Temperature · Relative humidity · Dew point · Ambient light · Active or standby · Sensor alarms
Available commands
Alert limits · Light levels for active and standby · LED brightness
Compatible models
RSTHM-2
Last updated

Registers (34)

34 read, 17 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Temperature°CRead
Relative Humidity%RHRead
Dew Point°CRead
Ambient LightluxRead
Active Standby StateRead
Temperature Output Value%Read
Humidity Output Value%Read
Temperature Alert FlagRead
Temperature Range Limit FlagRead
Temperature Sensor StateRead
Humidity Alert FlagRead
Humidity Range Limit FlagRead
Humidity Sensor StateRead
Ambient Light Sensor StateRead
Minimum Temperature Alert°CRead and write
Maximum Temperature Alert°CRead and write
Minimum Humidity Alert%RHRead and write
Maximum Humidity Alert%RHRead and write
Minimum Temperature Range°CRead and write
Maximum Temperature Range°CRead and write
Minimum Humidity Range%RHRead and write
Maximum Humidity Range%RHRead and write
Active Light LevelluxRead and write
Standby Light LevelluxRead and write
LED IndicationRead and write
LED Brightness%Read and write
Modbus AddressRead and write
Modbus Baud RateRead and write
Modbus ParityRead and write
Network TerminationRead and write
Modbus Registers ResetRead and write
Device TypeRead
Hardware VersionRead
Firmware VersionRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show temperature, humidity and dew point per room on a ModbusCloud dashboard.
  • Get an email when a room stays too humid or a sensor reports a fault.
  • Use the active or standby state to see when rooms are in use over 365 days of history.
  • Change the alert limits of a room remotely when its use changes.
  • Compare room humidity with the ventilation settings to check demand controlled ventilation.

Installation

  1. Connect the transmitter with an RJ45 Modbus cable that carries 24 VDC Power over Modbus, and run A and B to the ModbusCloud Gateway.

  2. Switch on the built-in termination on the last device of the line and terminate the other end at the Gateway.

  3. Give every Sentera device on the bus its own address; the factory default is address 1 at 19200 baud, 8E1.

  4. In ModbusCloud, add a Modbus device with that address and settings and import the Sentera RSTHM-2 template.

  5. Check that temperature, humidity and light level match the room.

Things to watch for

The transmitter has no power or does not answer. What should I check?

The RSTHM-2 takes 24 VDC from its RJ45 Modbus cable, so check that the cable carries the Power over Modbus supply. Then check A and B and that address, baud rate and parity in ModbusCloud match the factory setting of address 1, 19200 baud, 8E1, or the values you set.

Why does the light state stay on Low light intensity?

The transmitter reports Active above the active light level and Standby below the standby level. Between the two it reports low light intensity. Set both levels to match the room, for example 100 lux and 10 lux.

Several transmitters on one bus do not all show up. Why?

New Sentera devices all start at address 1. Connect them one at a time, give each its own address over Modbus, and add each one in ModbusCloud with its own address.

What should I watch out for when writing settings?

A new address, baud rate or parity takes effect on the transmitter, so update the Modbus device in ModbusCloud right after. Writing 1 to the register reset restores all holding registers to their defaults, including the address and your alert limits.