Vaisala Vaisala HMP Series Modbus RTU template

Vaisala HMP Series

Humidity and temperature probes for demanding processes, with dew point, sensor purge and condensation prevention.

The Vaisala HMP Series are humidity and temperature probes for demanding processes such as compressed air lines, ovens, dryers and spaces with constant high humidity. This Modbus RTU template reads relative humidity, temperature, dew point, the other humidity values and the probe status, and lets you set pressure compensation, condensation prevention, sensor purge and filtering from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
95, read and write
Brand
Vaisala
Key readings
Relative humidity · Temperature · Dew/frost point · Absolute humidity · Mixing ratio · Water vapor pressure · Enthalpy · Device status
Available commands
Pressure compensation · Condensation prevention · Sensor purge · Measurement filtering · Modbus address and bit rate · Humidity and temperature adjustment
Compatible models
HMP1 · HMP3 · HMP4 · HMP5 · HMP7 · HMP8 · HMP9 · MMP8 · TMP1
Last updated

Registers (95)

92 read, 42 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Relative Humidity%RHRead
Temperature°CRead
Dew Point Temperature°CRead
Dew/Frost Point Temperature°CRead
Dew/Frost Point Temperature at 1 atm°CRead
Dew Point Temperature at 1 atm°CRead
Absolute Humidityg/m³Read
Mixing Ratiog/kgRead
Wet-Bulb Temperature°CRead
Water ConcentrationppmRead
Water Vapor PressurehPaRead
Water Vapor Saturation PressurehPaRead
EnthalpyRead
Water ActivityRead
Dew/Frost Point Depression°CRead
Absolute Humidity at NTPg/m³Read
Water Concentration in OilppmRead
Relative Saturation%Read
Water Concentration (Wet Basis)%Read
Relative Humidity (Dew/Frost)%RHRead
Water Mass FractionppmRead
Relative Humidity (Integer)%RHRead
Temperature (Integer)°CRead
Dew Point Temperature (Integer)°CRead
Dew/Frost Point Temperature (Integer)°CRead
Dew/Frost Point at 1 atm (Integer)°CRead
Dew Point at 1 atm (Integer)°CRead
Absolute Humidity (Integer)g/m³Read
Mixing Ratio (Integer)g/kgRead
Wet-Bulb Temperature (Integer)°CRead
Water Concentration (Integer)ppmRead
Water Vapor Pressure (Integer)hPaRead
Water Vapor Saturation Pressure (Integer)hPaRead
Enthalpy (Integer)Read
Water Activity (Integer)Read
Dew/Frost Point Depression (Integer)°CRead
Absolute Humidity at NTP (Integer)g/m³Read
Water Concentration in Oil (Integer)ppmRead
Relative Saturation (Integer)%Read
Water Concentration (Wet Basis) (Integer)%Read
Relative Humidity (Dew/Frost) (Integer)%RHRead
Water Vapor Mass Fraction (Integer)ppmRead
Error StatusRead
Online StatusRead
Error CodeRead
Security HashRead
RH Measurement StatusRead
T Measurement StatusRead
Td/f Measurement StatusRead
Device StatusRead
Pressure Compensation SetpointhPaRead and write
Temperature Compensation Setpoint°CRead and write
Condensation PreventionRead and write
Start Sensor PurgeRead and write
Sensor Purge IntervalminRead and write
Interval PurgeRead and write
Startup PurgeRead and write
Measurement Filtering FactorRead and write
Measurement FilteringRead and write
Modbus AddressRead and write
Bit RateRead and write
Parity, Data and Stop BitsRead and write
Response DelaymsRead and write
Restart DeviceWrite
Calibration Mode PasscodeRead and write
Calibration YearRead and write
Calibration MonthRead and write
Calibration DayRead and write
Calibration TextRead and write
RH Adjustment Reference Point 1%RHRead and write
RH Adjustment Measured RH Point 1%RHRead and write
RH Adjustment Measured T Point 1°CRead and write
RH Adjustment Reference Point 2%RHRead and write
RH Adjustment Measured RH Point 2%RHRead and write
RH Adjustment Measured T Point 2°CRead and write
RH Adjustment Reference Point 3%RHRead and write
RH Adjustment Measured RH Point 3%RHRead and write
RH Adjustment Measured T Point 3°CRead and write
RH Adjustment Reference Point 4%RHRead and write
RH Adjustment Measured RH Point 4%RHRead and write
RH Adjustment Measured T Point 4°CRead and write
RH Adjustment Reference Point 5%RHRead and write
RH Adjustment Measured RH Point 5%RHRead and write
RH Adjustment Measured T Point 5°CRead and write
Activate RH AdjustmentRead and write
Restore Factory RH AdjustmentWrite
T Adjustment Reference Point 1°CRead and write
T Adjustment Measured T Point 1°CRead and write
T Adjustment Reference Point 2°CRead and write
T Adjustment Measured T Point 2°CRead and write
Activate T AdjustmentRead and write
Restore Factory T AdjustmentWrite
Signed Integer TestRead
Floating Point TestRead
Text String TestRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show humidity, temperature and dew point per greenhouse compartment, drying chamber or air line on a dashboard and keep 365 days of history.
  • Get an email, in-app or webhook alert when the dew point in a compressed air line rises above the limit you set.
  • Raise an alert when Error Code is not 0 or Device Status reports an error, for example a humidity measurement error from a wet sensor.
  • Track Online Status to see when sensor purge or condensation prevention locks the readings, and leave those moments out of your analysis.
  • Update the pressure compensation from the portal when an HMP4 or HMP8 sits in a line above atmospheric pressure.
  • Start a sensor purge or switch the automatic purge on from the portal, for example after cleaning the probe or before a calibration.

Installation

  1. Connect pin 4 (RS-485+, black) and pin 2 (RS-485-, white) of the M12 probe cable to the RS485 port of the ModbusCloud Gateway, and pin 3 (blue) to ground. Keep the RS-485 line within 30 m.

  2. Power the probe with 15 to 30 V DC on pin 1 (brown). The HMP7 needs 18 to 30 V DC, and its probe heating stays off below 18 V.

  3. The probe answers at address 240 with 19200 baud, no parity, 8 data bits and 2 stop bits. With more probes on one line, up to ten, give each its own address, for example with Vaisala Insight.

  4. In ModbusCloud, add a Modbus device on the gateway with these settings and import the Vaisala HMP Series template.

  5. Check that Floating Point Test reads -123.45 and that Relative Humidity and Temperature show plausible values.

Things to watch for

The probe does not answer on the RS485 bus. What should I check?

Check 19200 baud, no parity, 8 data bits and 2 stop bits at address 240. Many masters default to 1 stop bit. Check that RS-485+ is on pin 4 and RS-485- on pin 2, and swap them if nothing answers. Every probe on the line needs its own address. Check the supply: at least 15 V DC, and 18 V DC for the HMP7. A red LED on the probe body means the probe reports an error.

Relative humidity shows no value on my HMP7. Why?

While condensation prevention warms the sensor or probe head, the probe returns values that depend on its own temperature, such as relative humidity, as not available. Dew point stays available. Write the ambient temperature from another sensor to Temperature Compensation Setpoint, or switch Condensation Prevention off. During a sensor purge all values freeze for a few minutes and Online Status reads 0.

The values look plausible but do not match my reference. How do I check the readout?

Read Floating Point Test. It must show -123.45, and Signed Integer Test -12345. The probe sends 32-bit values low word first, and a wrong word order can still give values that look right. The template already uses the order of the probe. In a pressurized line, set Pressure Compensation Setpoint to the process pressure, otherwise the mixing ratio and other pressure-dependent values are off.

Writing a setting returns an error or has no effect. Why?

The probe only accepts writes as write multiple (function code 16). Pressure compensation, filtering factor and adjustment values are 32-bit and always go that way. If a single 16-bit setting such as Condensation Prevention returns an error, change it with Vaisala Insight. The probe confirms a write even when it rejects the value, so read the register back. Writing registers in ModbusCloud is off by default and is enabled per gateway on request.

Can I calibrate the probe from ModbusCloud?

The template contains the adjustment registers, but Vaisala recommends its calibration service, Vaisala Insight or a compatible handheld meter. An adjustment needs a stable reference, a sensor purge first, the passcode 1300 to open calibration mode, and the calibration date and text each written in one go. The probe rejects corrections larger than 10 %RH or 0.5 °C. You can follow the values in ModbusCloud while the probe stabilizes.

Want to see how it works?