Wavin Sentio
Underfloor heating and cooling controller with temperature, humidity and setpoints for up to 16 rooms.
The Wavin Sentio CCU-208 is a central control unit that runs underfloor heating and cooling and radiators room by room in homes and small buildings. This Modbus RTU template reads air and floor temperature, humidity, dew point, states and alarms for up to 16 rooms, and lets you write setpoints, room modes, standby and vacation from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 19200 baud
- Registers
- 808, read and write
- Brand
- Wavin
- Key readings
- Air temperature · Floor temperature · Relative humidity · Dew point · Heating or cooling state · Outdoor temperature · Warnings and errors
- Available commands
- Room temperature setpoint · Room mode · Standby and vacation · Thermostat lock · Heating or cooling mode
- Compatible models
- Sentio CCU-208
- Last updated
Registers (808)
807 read, 341 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Heating/Cooling Mode | Read | 20 | FC04 | uint16 | |
| System Warning | Read | 1 | FC02 | bool | |
| System Error | Read | 2 | FC02 | bool | |
| Room 1 Air Temperature | °C | Read | 104 | FC04 | int16 |
| Room 1 Floor Temperature | °C | Read | 105 | FC04 | int16 |
| Room 1 Relative Humidity | %RH | Read | |||
| Room 1 Dew Point | °C | Read | |||
| Room 1 Desired Temperature | °C | Read | |||
| Room 1 Heating/Cooling State | Read | ||||
| Room 1 Blocking Source | Read | ||||
| Room 1 Warning | Read | ||||
| Room 1 Error | Read | ||||
| Room 1 Low Battery | Read | ||||
| Room 1 Peripheral Lost | Read | ||||
| Room 1 Radiators State | Read | ||||
| Room 1 Underfloor State | Read | ||||
| Room 1 Drying State | Read | ||||
| Room 1 Thermal Integration State | Read | ||||
| Room 1 Ventilation State | Read | ||||
| Room 1 Blocking Source Radiators | Read | ||||
| Room 1 Blocking Source Underfloor | Read | ||||
| Room 1 Blocking Source Drying | Read | ||||
| Room 1 Blocking Source Integration | Read | ||||
| Room 1 Blocking Source Ventilation | Read | ||||
| Room 1 Room Type | Read | ||||
| Room 1 Associated Radiators | Read | ||||
| Room 1 Associated Underfloor | Read | ||||
| Room 1 Associated Drying | Read | ||||
| Room 1 Associated Thermal Integration | Read | ||||
| Room 1 Associated Ventilation | Read | ||||
| Room 1 Associated Heating Source | Read | ||||
| Room 1 Temperature Setpoint | °C | Read and write | |||
| Room 1 Mode | Read and write | ||||
| Room 1 Mode Override | Read and write | ||||
| Room 1 Standby Temperature | °C | Read and write | |||
| Room 1 Vacation Temperature | °C | Read and write | |||
| Room 1 Temperature Preset | Read and write | ||||
| Room 1 Thermostat Lock | Read and write | ||||
| Room 1 Exclude From Vacation | Read and write | ||||
| Room 1 Adaptive Mode | Read and write | ||||
| Room 1 Thermal Integration Heating Offset | Read and write | ||||
| Room 1 Thermal Integration Hysteresis | Read and write | ||||
| Room 1 Humidity Threshold Heating | %RH | Read and write | |||
| Room 1 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 1 Humidity Hysteresis | Read and write | ||||
| Room 1 Drying Cooling Water Offset | Read and write | ||||
| Room 1 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 1 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 1 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 1 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 1 Name | Read and write | ||||
| Room 2 Air Temperature | °C | Read | |||
| Room 2 Floor Temperature | °C | Read | |||
| Room 2 Relative Humidity | %RH | Read | |||
| Room 2 Dew Point | °C | Read | |||
| Room 2 Desired Temperature | °C | Read | |||
| Room 2 Heating/Cooling State | Read | ||||
| Room 2 Blocking Source | Read | ||||
| Room 2 Warning | Read | ||||
| Room 2 Error | Read | ||||
| Room 2 Low Battery | Read | ||||
| Room 2 Peripheral Lost | Read | ||||
| Room 2 Radiators State | Read | ||||
| Room 2 Underfloor State | Read | ||||
| Room 2 Drying State | Read | ||||
| Room 2 Thermal Integration State | Read | ||||
| Room 2 Ventilation State | Read | ||||
| Room 2 Blocking Source Radiators | Read | ||||
| Room 2 Blocking Source Underfloor | Read | ||||
| Room 2 Blocking Source Drying | Read | ||||
| Room 2 Blocking Source Integration | Read | ||||
| Room 2 Blocking Source Ventilation | Read | ||||
| Room 2 Room Type | Read | ||||
| Room 2 Associated Radiators | Read | ||||
| Room 2 Associated Underfloor | Read | ||||
| Room 2 Associated Drying | Read | ||||
| Room 2 Associated Thermal Integration | Read | ||||
| Room 2 Associated Ventilation | Read | ||||
| Room 2 Associated Heating Source | Read | ||||
| Room 2 Temperature Setpoint | °C | Read and write | |||
| Room 2 Mode | Read and write | ||||
| Room 2 Mode Override | Read and write | ||||
| Room 2 Standby Temperature | °C | Read and write | |||
| Room 2 Vacation Temperature | °C | Read and write | |||
| Room 2 Temperature Preset | Read and write | ||||
| Room 2 Thermostat Lock | Read and write | ||||
| Room 2 Exclude From Vacation | Read and write | ||||
| Room 2 Adaptive Mode | Read and write | ||||
| Room 2 Thermal Integration Heating Offset | Read and write | ||||
| Room 2 Thermal Integration Hysteresis | Read and write | ||||
| Room 2 Humidity Threshold Heating | %RH | Read and write | |||
| Room 2 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 2 Humidity Hysteresis | Read and write | ||||
| Room 2 Drying Cooling Water Offset | Read and write | ||||
| Room 2 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 2 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 2 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 2 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 2 Name | Read and write | ||||
| Room 3 Air Temperature | °C | Read | |||
| Room 3 Floor Temperature | °C | Read | |||
| Room 3 Relative Humidity | %RH | Read | |||
| Room 3 Dew Point | °C | Read | |||
| Room 3 Desired Temperature | °C | Read | |||
| Room 3 Heating/Cooling State | Read | ||||
| Room 3 Blocking Source | Read | ||||
| Room 3 Warning | Read | ||||
| Room 3 Error | Read | ||||
| Room 3 Low Battery | Read | ||||
| Room 3 Peripheral Lost | Read | ||||
| Room 3 Radiators State | Read | ||||
| Room 3 Underfloor State | Read | ||||
| Room 3 Drying State | Read | ||||
| Room 3 Thermal Integration State | Read | ||||
| Room 3 Ventilation State | Read | ||||
| Room 3 Blocking Source Radiators | Read | ||||
| Room 3 Blocking Source Underfloor | Read | ||||
| Room 3 Blocking Source Drying | Read | ||||
| Room 3 Blocking Source Integration | Read | ||||
| Room 3 Blocking Source Ventilation | Read | ||||
| Room 3 Room Type | Read | ||||
| Room 3 Associated Radiators | Read | ||||
| Room 3 Associated Underfloor | Read | ||||
| Room 3 Associated Drying | Read | ||||
| Room 3 Associated Thermal Integration | Read | ||||
| Room 3 Associated Ventilation | Read | ||||
| Room 3 Associated Heating Source | Read | ||||
| Room 3 Temperature Setpoint | °C | Read and write | |||
| Room 3 Mode | Read and write | ||||
| Room 3 Mode Override | Read and write | ||||
| Room 3 Standby Temperature | °C | Read and write | |||
| Room 3 Vacation Temperature | °C | Read and write | |||
| Room 3 Temperature Preset | Read and write | ||||
| Room 3 Thermostat Lock | Read and write | ||||
| Room 3 Exclude From Vacation | Read and write | ||||
| Room 3 Adaptive Mode | Read and write | ||||
| Room 3 Thermal Integration Heating Offset | Read and write | ||||
| Room 3 Thermal Integration Hysteresis | Read and write | ||||
| Room 3 Humidity Threshold Heating | %RH | Read and write | |||
| Room 3 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 3 Humidity Hysteresis | Read and write | ||||
| Room 3 Drying Cooling Water Offset | Read and write | ||||
| Room 3 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 3 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 3 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 3 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 3 Name | Read and write | ||||
| Room 4 Air Temperature | °C | Read | |||
| Room 4 Floor Temperature | °C | Read | |||
| Room 4 Relative Humidity | %RH | Read | |||
| Room 4 Dew Point | °C | Read | |||
| Room 4 Desired Temperature | °C | Read | |||
| Room 4 Heating/Cooling State | Read | ||||
| Room 4 Blocking Source | Read | ||||
| Room 4 Warning | Read | ||||
| Room 4 Error | Read | ||||
| Room 4 Low Battery | Read | ||||
| Room 4 Peripheral Lost | Read | ||||
| Room 4 Radiators State | Read | ||||
| Room 4 Underfloor State | Read | ||||
| Room 4 Drying State | Read | ||||
| Room 4 Thermal Integration State | Read | ||||
| Room 4 Ventilation State | Read | ||||
| Room 4 Blocking Source Radiators | Read | ||||
| Room 4 Blocking Source Underfloor | Read | ||||
| Room 4 Blocking Source Drying | Read | ||||
| Room 4 Blocking Source Integration | Read | ||||
| Room 4 Blocking Source Ventilation | Read | ||||
| Room 4 Room Type | Read | ||||
| Room 4 Associated Radiators | Read | ||||
| Room 4 Associated Underfloor | Read | ||||
| Room 4 Associated Drying | Read | ||||
| Room 4 Associated Thermal Integration | Read | ||||
| Room 4 Associated Ventilation | Read | ||||
| Room 4 Associated Heating Source | Read | ||||
| Room 4 Temperature Setpoint | °C | Read and write | |||
| Room 4 Mode | Read and write | ||||
| Room 4 Mode Override | Read and write | ||||
| Room 4 Standby Temperature | °C | Read and write | |||
| Room 4 Vacation Temperature | °C | Read and write | |||
| Room 4 Temperature Preset | Read and write | ||||
| Room 4 Thermostat Lock | Read and write | ||||
| Room 4 Exclude From Vacation | Read and write | ||||
| Room 4 Adaptive Mode | Read and write | ||||
| Room 4 Thermal Integration Heating Offset | Read and write | ||||
| Room 4 Thermal Integration Hysteresis | Read and write | ||||
| Room 4 Humidity Threshold Heating | %RH | Read and write | |||
| Room 4 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 4 Humidity Hysteresis | Read and write | ||||
| Room 4 Drying Cooling Water Offset | Read and write | ||||
| Room 4 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 4 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 4 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 4 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 4 Name | Read and write | ||||
| Room 5 Air Temperature | °C | Read | |||
| Room 5 Floor Temperature | °C | Read | |||
| Room 5 Relative Humidity | %RH | Read | |||
| Room 5 Dew Point | °C | Read | |||
| Room 5 Desired Temperature | °C | Read | |||
| Room 5 Heating/Cooling State | Read | ||||
| Room 5 Blocking Source | Read | ||||
| Room 5 Warning | Read | ||||
| Room 5 Error | Read | ||||
| Room 5 Low Battery | Read | ||||
| Room 5 Peripheral Lost | Read | ||||
| Room 5 Radiators State | Read | ||||
| Room 5 Underfloor State | Read | ||||
| Room 5 Drying State | Read | ||||
| Room 5 Thermal Integration State | Read | ||||
| Room 5 Ventilation State | Read | ||||
| Room 5 Blocking Source Radiators | Read | ||||
| Room 5 Blocking Source Underfloor | Read | ||||
| Room 5 Blocking Source Drying | Read | ||||
| Room 5 Blocking Source Integration | Read | ||||
| Room 5 Blocking Source Ventilation | Read | ||||
| Room 5 Room Type | Read | ||||
| Room 5 Associated Radiators | Read | ||||
| Room 5 Associated Underfloor | Read | ||||
| Room 5 Associated Drying | Read | ||||
| Room 5 Associated Thermal Integration | Read | ||||
| Room 5 Associated Ventilation | Read | ||||
| Room 5 Associated Heating Source | Read | ||||
| Room 5 Temperature Setpoint | °C | Read and write | |||
| Room 5 Mode | Read and write | ||||
| Room 5 Mode Override | Read and write | ||||
| Room 5 Standby Temperature | °C | Read and write | |||
| Room 5 Vacation Temperature | °C | Read and write | |||
| Room 5 Temperature Preset | Read and write | ||||
| Room 5 Thermostat Lock | Read and write | ||||
| Room 5 Exclude From Vacation | Read and write | ||||
| Room 5 Adaptive Mode | Read and write | ||||
| Room 5 Thermal Integration Heating Offset | Read and write | ||||
| Room 5 Thermal Integration Hysteresis | Read and write | ||||
| Room 5 Humidity Threshold Heating | %RH | Read and write | |||
| Room 5 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 5 Humidity Hysteresis | Read and write | ||||
| Room 5 Drying Cooling Water Offset | Read and write | ||||
| Room 5 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 5 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 5 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 5 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 5 Name | Read and write | ||||
| Room 6 Air Temperature | °C | Read | |||
| Room 6 Floor Temperature | °C | Read | |||
| Room 6 Relative Humidity | %RH | Read | |||
| Room 6 Dew Point | °C | Read | |||
| Room 6 Desired Temperature | °C | Read | |||
| Room 6 Heating/Cooling State | Read | ||||
| Room 6 Blocking Source | Read | ||||
| Room 6 Warning | Read | ||||
| Room 6 Error | Read | ||||
| Room 6 Low Battery | Read | ||||
| Room 6 Peripheral Lost | Read | ||||
| Room 6 Radiators State | Read | ||||
| Room 6 Underfloor State | Read | ||||
| Room 6 Drying State | Read | ||||
| Room 6 Thermal Integration State | Read | ||||
| Room 6 Ventilation State | Read | ||||
| Room 6 Blocking Source Radiators | Read | ||||
| Room 6 Blocking Source Underfloor | Read | ||||
| Room 6 Blocking Source Drying | Read | ||||
| Room 6 Blocking Source Integration | Read | ||||
| Room 6 Blocking Source Ventilation | Read | ||||
| Room 6 Room Type | Read | ||||
| Room 6 Associated Radiators | Read | ||||
| Room 6 Associated Underfloor | Read | ||||
| Room 6 Associated Drying | Read | ||||
| Room 6 Associated Thermal Integration | Read | ||||
| Room 6 Associated Ventilation | Read | ||||
| Room 6 Associated Heating Source | Read | ||||
| Room 6 Temperature Setpoint | °C | Read and write | |||
| Room 6 Mode | Read and write | ||||
| Room 6 Mode Override | Read and write | ||||
| Room 6 Standby Temperature | °C | Read and write | |||
| Room 6 Vacation Temperature | °C | Read and write | |||
| Room 6 Temperature Preset | Read and write | ||||
| Room 6 Thermostat Lock | Read and write | ||||
| Room 6 Exclude From Vacation | Read and write | ||||
| Room 6 Adaptive Mode | Read and write | ||||
| Room 6 Thermal Integration Heating Offset | Read and write | ||||
| Room 6 Thermal Integration Hysteresis | Read and write | ||||
| Room 6 Humidity Threshold Heating | %RH | Read and write | |||
| Room 6 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 6 Humidity Hysteresis | Read and write | ||||
| Room 6 Drying Cooling Water Offset | Read and write | ||||
| Room 6 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 6 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 6 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 6 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 6 Name | Read and write | ||||
| Room 7 Air Temperature | °C | Read | |||
| Room 7 Floor Temperature | °C | Read | |||
| Room 7 Relative Humidity | %RH | Read | |||
| Room 7 Dew Point | °C | Read | |||
| Room 7 Desired Temperature | °C | Read | |||
| Room 7 Heating/Cooling State | Read | ||||
| Room 7 Blocking Source | Read | ||||
| Room 7 Warning | Read | ||||
| Room 7 Error | Read | ||||
| Room 7 Low Battery | Read | ||||
| Room 7 Peripheral Lost | Read | ||||
| Room 7 Radiators State | Read | ||||
| Room 7 Underfloor State | Read | ||||
| Room 7 Drying State | Read | ||||
| Room 7 Thermal Integration State | Read | ||||
| Room 7 Ventilation State | Read | ||||
| Room 7 Blocking Source Radiators | Read | ||||
| Room 7 Blocking Source Underfloor | Read | ||||
| Room 7 Blocking Source Drying | Read | ||||
| Room 7 Blocking Source Integration | Read | ||||
| Room 7 Blocking Source Ventilation | Read | ||||
| Room 7 Room Type | Read | ||||
| Room 7 Associated Radiators | Read | ||||
| Room 7 Associated Underfloor | Read | ||||
| Room 7 Associated Drying | Read | ||||
| Room 7 Associated Thermal Integration | Read | ||||
| Room 7 Associated Ventilation | Read | ||||
| Room 7 Associated Heating Source | Read | ||||
| Room 7 Temperature Setpoint | °C | Read and write | |||
| Room 7 Mode | Read and write | ||||
| Room 7 Mode Override | Read and write | ||||
| Room 7 Standby Temperature | °C | Read and write | |||
| Room 7 Vacation Temperature | °C | Read and write | |||
| Room 7 Temperature Preset | Read and write | ||||
| Room 7 Thermostat Lock | Read and write | ||||
| Room 7 Exclude From Vacation | Read and write | ||||
| Room 7 Adaptive Mode | Read and write | ||||
| Room 7 Thermal Integration Heating Offset | Read and write | ||||
| Room 7 Thermal Integration Hysteresis | Read and write | ||||
| Room 7 Humidity Threshold Heating | %RH | Read and write | |||
| Room 7 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 7 Humidity Hysteresis | Read and write | ||||
| Room 7 Drying Cooling Water Offset | Read and write | ||||
| Room 7 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 7 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 7 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 7 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 7 Name | Read and write | ||||
| Room 8 Air Temperature | °C | Read | |||
| Room 8 Floor Temperature | °C | Read | |||
| Room 8 Relative Humidity | %RH | Read | |||
| Room 8 Dew Point | °C | Read | |||
| Room 8 Desired Temperature | °C | Read | |||
| Room 8 Heating/Cooling State | Read | ||||
| Room 8 Blocking Source | Read | ||||
| Room 8 Warning | Read | ||||
| Room 8 Error | Read | ||||
| Room 8 Low Battery | Read | ||||
| Room 8 Peripheral Lost | Read | ||||
| Room 8 Radiators State | Read | ||||
| Room 8 Underfloor State | Read | ||||
| Room 8 Drying State | Read | ||||
| Room 8 Thermal Integration State | Read | ||||
| Room 8 Ventilation State | Read | ||||
| Room 8 Blocking Source Radiators | Read | ||||
| Room 8 Blocking Source Underfloor | Read | ||||
| Room 8 Blocking Source Drying | Read | ||||
| Room 8 Blocking Source Integration | Read | ||||
| Room 8 Blocking Source Ventilation | Read | ||||
| Room 8 Room Type | Read | ||||
| Room 8 Associated Radiators | Read | ||||
| Room 8 Associated Underfloor | Read | ||||
| Room 8 Associated Drying | Read | ||||
| Room 8 Associated Thermal Integration | Read | ||||
| Room 8 Associated Ventilation | Read | ||||
| Room 8 Associated Heating Source | Read | ||||
| Room 8 Temperature Setpoint | °C | Read and write | |||
| Room 8 Mode | Read and write | ||||
| Room 8 Mode Override | Read and write | ||||
| Room 8 Standby Temperature | °C | Read and write | |||
| Room 8 Vacation Temperature | °C | Read and write | |||
| Room 8 Temperature Preset | Read and write | ||||
| Room 8 Thermostat Lock | Read and write | ||||
| Room 8 Exclude From Vacation | Read and write | ||||
| Room 8 Adaptive Mode | Read and write | ||||
| Room 8 Thermal Integration Heating Offset | Read and write | ||||
| Room 8 Thermal Integration Hysteresis | Read and write | ||||
| Room 8 Humidity Threshold Heating | %RH | Read and write | |||
| Room 8 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 8 Humidity Hysteresis | Read and write | ||||
| Room 8 Drying Cooling Water Offset | Read and write | ||||
| Room 8 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 8 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 8 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 8 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 8 Name | Read and write | ||||
| Room 9 Air Temperature | °C | Read | |||
| Room 9 Floor Temperature | °C | Read | |||
| Room 9 Relative Humidity | %RH | Read | |||
| Room 9 Dew Point | °C | Read | |||
| Room 9 Desired Temperature | °C | Read | |||
| Room 9 Heating/Cooling State | Read | ||||
| Room 9 Blocking Source | Read | ||||
| Room 9 Warning | Read | ||||
| Room 9 Error | Read | ||||
| Room 9 Low Battery | Read | ||||
| Room 9 Peripheral Lost | Read | ||||
| Room 9 Radiators State | Read | ||||
| Room 9 Underfloor State | Read | ||||
| Room 9 Drying State | Read | ||||
| Room 9 Thermal Integration State | Read | ||||
| Room 9 Ventilation State | Read | ||||
| Room 9 Blocking Source Radiators | Read | ||||
| Room 9 Blocking Source Underfloor | Read | ||||
| Room 9 Blocking Source Drying | Read | ||||
| Room 9 Blocking Source Integration | Read | ||||
| Room 9 Blocking Source Ventilation | Read | ||||
| Room 9 Room Type | Read | ||||
| Room 9 Associated Radiators | Read | ||||
| Room 9 Associated Underfloor | Read | ||||
| Room 9 Associated Drying | Read | ||||
| Room 9 Associated Thermal Integration | Read | ||||
| Room 9 Associated Ventilation | Read | ||||
| Room 9 Associated Heating Source | Read | ||||
| Room 9 Temperature Setpoint | °C | Read and write | |||
| Room 9 Mode | Read and write | ||||
| Room 9 Mode Override | Read and write | ||||
| Room 9 Standby Temperature | °C | Read and write | |||
| Room 9 Vacation Temperature | °C | Read and write | |||
| Room 9 Temperature Preset | Read and write | ||||
| Room 9 Thermostat Lock | Read and write | ||||
| Room 9 Exclude From Vacation | Read and write | ||||
| Room 9 Adaptive Mode | Read and write | ||||
| Room 9 Thermal Integration Heating Offset | Read and write | ||||
| Room 9 Thermal Integration Hysteresis | Read and write | ||||
| Room 9 Humidity Threshold Heating | %RH | Read and write | |||
| Room 9 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 9 Humidity Hysteresis | Read and write | ||||
| Room 9 Drying Cooling Water Offset | Read and write | ||||
| Room 9 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 9 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 9 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 9 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 9 Name | Read and write | ||||
| Room 10 Air Temperature | °C | Read | |||
| Room 10 Floor Temperature | °C | Read | |||
| Room 10 Relative Humidity | %RH | Read | |||
| Room 10 Dew Point | °C | Read | |||
| Room 10 Desired Temperature | °C | Read | |||
| Room 10 Heating/Cooling State | Read | ||||
| Room 10 Blocking Source | Read | ||||
| Room 10 Warning | Read | ||||
| Room 10 Error | Read | ||||
| Room 10 Low Battery | Read | ||||
| Room 10 Peripheral Lost | Read | ||||
| Room 10 Radiators State | Read | ||||
| Room 10 Underfloor State | Read | ||||
| Room 10 Drying State | Read | ||||
| Room 10 Thermal Integration State | Read | ||||
| Room 10 Ventilation State | Read | ||||
| Room 10 Blocking Source Radiators | Read | ||||
| Room 10 Blocking Source Underfloor | Read | ||||
| Room 10 Blocking Source Drying | Read | ||||
| Room 10 Blocking Source Integration | Read | ||||
| Room 10 Blocking Source Ventilation | Read | ||||
| Room 10 Room Type | Read | ||||
| Room 10 Associated Radiators | Read | ||||
| Room 10 Associated Underfloor | Read | ||||
| Room 10 Associated Drying | Read | ||||
| Room 10 Associated Thermal Integration | Read | ||||
| Room 10 Associated Ventilation | Read | ||||
| Room 10 Associated Heating Source | Read | ||||
| Room 10 Temperature Setpoint | °C | Read and write | |||
| Room 10 Mode | Read and write | ||||
| Room 10 Mode Override | Read and write | ||||
| Room 10 Standby Temperature | °C | Read and write | |||
| Room 10 Vacation Temperature | °C | Read and write | |||
| Room 10 Temperature Preset | Read and write | ||||
| Room 10 Thermostat Lock | Read and write | ||||
| Room 10 Exclude From Vacation | Read and write | ||||
| Room 10 Adaptive Mode | Read and write | ||||
| Room 10 Thermal Integration Heating Offset | Read and write | ||||
| Room 10 Thermal Integration Hysteresis | Read and write | ||||
| Room 10 Humidity Threshold Heating | %RH | Read and write | |||
| Room 10 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 10 Humidity Hysteresis | Read and write | ||||
| Room 10 Drying Cooling Water Offset | Read and write | ||||
| Room 10 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 10 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 10 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 10 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 10 Name | Read and write | ||||
| Room 11 Air Temperature | °C | Read | |||
| Room 11 Floor Temperature | °C | Read | |||
| Room 11 Relative Humidity | %RH | Read | |||
| Room 11 Dew Point | °C | Read | |||
| Room 11 Desired Temperature | °C | Read | |||
| Room 11 Heating/Cooling State | Read | ||||
| Room 11 Blocking Source | Read | ||||
| Room 11 Warning | Read | ||||
| Room 11 Error | Read | ||||
| Room 11 Low Battery | Read | ||||
| Room 11 Peripheral Lost | Read | ||||
| Room 11 Radiators State | Read | ||||
| Room 11 Underfloor State | Read | ||||
| Room 11 Drying State | Read | ||||
| Room 11 Thermal Integration State | Read | ||||
| Room 11 Ventilation State | Read | ||||
| Room 11 Blocking Source Radiators | Read | ||||
| Room 11 Blocking Source Underfloor | Read | ||||
| Room 11 Blocking Source Drying | Read | ||||
| Room 11 Blocking Source Integration | Read | ||||
| Room 11 Blocking Source Ventilation | Read | ||||
| Room 11 Room Type | Read | ||||
| Room 11 Associated Radiators | Read | ||||
| Room 11 Associated Underfloor | Read | ||||
| Room 11 Associated Drying | Read | ||||
| Room 11 Associated Thermal Integration | Read | ||||
| Room 11 Associated Ventilation | Read | ||||
| Room 11 Associated Heating Source | Read | ||||
| Room 11 Temperature Setpoint | °C | Read and write | |||
| Room 11 Mode | Read and write | ||||
| Room 11 Mode Override | Read and write | ||||
| Room 11 Standby Temperature | °C | Read and write | |||
| Room 11 Vacation Temperature | °C | Read and write | |||
| Room 11 Temperature Preset | Read and write | ||||
| Room 11 Thermostat Lock | Read and write | ||||
| Room 11 Exclude From Vacation | Read and write | ||||
| Room 11 Adaptive Mode | Read and write | ||||
| Room 11 Thermal Integration Heating Offset | Read and write | ||||
| Room 11 Thermal Integration Hysteresis | Read and write | ||||
| Room 11 Humidity Threshold Heating | %RH | Read and write | |||
| Room 11 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 11 Humidity Hysteresis | Read and write | ||||
| Room 11 Drying Cooling Water Offset | Read and write | ||||
| Room 11 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 11 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 11 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 11 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 11 Name | Read and write | ||||
| Room 12 Air Temperature | °C | Read | |||
| Room 12 Floor Temperature | °C | Read | |||
| Room 12 Relative Humidity | %RH | Read | |||
| Room 12 Dew Point | °C | Read | |||
| Room 12 Desired Temperature | °C | Read | |||
| Room 12 Heating/Cooling State | Read | ||||
| Room 12 Blocking Source | Read | ||||
| Room 12 Warning | Read | ||||
| Room 12 Error | Read | ||||
| Room 12 Low Battery | Read | ||||
| Room 12 Peripheral Lost | Read | ||||
| Room 12 Radiators State | Read | ||||
| Room 12 Underfloor State | Read | ||||
| Room 12 Drying State | Read | ||||
| Room 12 Thermal Integration State | Read | ||||
| Room 12 Ventilation State | Read | ||||
| Room 12 Blocking Source Radiators | Read | ||||
| Room 12 Blocking Source Underfloor | Read | ||||
| Room 12 Blocking Source Drying | Read | ||||
| Room 12 Blocking Source Integration | Read | ||||
| Room 12 Blocking Source Ventilation | Read | ||||
| Room 12 Room Type | Read | ||||
| Room 12 Associated Radiators | Read | ||||
| Room 12 Associated Underfloor | Read | ||||
| Room 12 Associated Drying | Read | ||||
| Room 12 Associated Thermal Integration | Read | ||||
| Room 12 Associated Ventilation | Read | ||||
| Room 12 Associated Heating Source | Read | ||||
| Room 12 Temperature Setpoint | °C | Read and write | |||
| Room 12 Mode | Read and write | ||||
| Room 12 Mode Override | Read and write | ||||
| Room 12 Standby Temperature | °C | Read and write | |||
| Room 12 Vacation Temperature | °C | Read and write | |||
| Room 12 Temperature Preset | Read and write | ||||
| Room 12 Thermostat Lock | Read and write | ||||
| Room 12 Exclude From Vacation | Read and write | ||||
| Room 12 Adaptive Mode | Read and write | ||||
| Room 12 Thermal Integration Heating Offset | Read and write | ||||
| Room 12 Thermal Integration Hysteresis | Read and write | ||||
| Room 12 Humidity Threshold Heating | %RH | Read and write | |||
| Room 12 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 12 Humidity Hysteresis | Read and write | ||||
| Room 12 Drying Cooling Water Offset | Read and write | ||||
| Room 12 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 12 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 12 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 12 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 12 Name | Read and write | ||||
| Room 13 Air Temperature | °C | Read | |||
| Room 13 Floor Temperature | °C | Read | |||
| Room 13 Relative Humidity | %RH | Read | |||
| Room 13 Dew Point | °C | Read | |||
| Room 13 Desired Temperature | °C | Read | |||
| Room 13 Heating/Cooling State | Read | ||||
| Room 13 Blocking Source | Read | ||||
| Room 13 Warning | Read | ||||
| Room 13 Error | Read | ||||
| Room 13 Low Battery | Read | ||||
| Room 13 Peripheral Lost | Read | ||||
| Room 13 Radiators State | Read | ||||
| Room 13 Underfloor State | Read | ||||
| Room 13 Drying State | Read | ||||
| Room 13 Thermal Integration State | Read | ||||
| Room 13 Ventilation State | Read | ||||
| Room 13 Blocking Source Radiators | Read | ||||
| Room 13 Blocking Source Underfloor | Read | ||||
| Room 13 Blocking Source Drying | Read | ||||
| Room 13 Blocking Source Integration | Read | ||||
| Room 13 Blocking Source Ventilation | Read | ||||
| Room 13 Room Type | Read | ||||
| Room 13 Associated Radiators | Read | ||||
| Room 13 Associated Underfloor | Read | ||||
| Room 13 Associated Drying | Read | ||||
| Room 13 Associated Thermal Integration | Read | ||||
| Room 13 Associated Ventilation | Read | ||||
| Room 13 Associated Heating Source | Read | ||||
| Room 13 Temperature Setpoint | °C | Read and write | |||
| Room 13 Mode | Read and write | ||||
| Room 13 Mode Override | Read and write | ||||
| Room 13 Standby Temperature | °C | Read and write | |||
| Room 13 Vacation Temperature | °C | Read and write | |||
| Room 13 Temperature Preset | Read and write | ||||
| Room 13 Thermostat Lock | Read and write | ||||
| Room 13 Exclude From Vacation | Read and write | ||||
| Room 13 Adaptive Mode | Read and write | ||||
| Room 13 Thermal Integration Heating Offset | Read and write | ||||
| Room 13 Thermal Integration Hysteresis | Read and write | ||||
| Room 13 Humidity Threshold Heating | %RH | Read and write | |||
| Room 13 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 13 Humidity Hysteresis | Read and write | ||||
| Room 13 Drying Cooling Water Offset | Read and write | ||||
| Room 13 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 13 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 13 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 13 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 13 Name | Read and write | ||||
| Room 14 Air Temperature | °C | Read | |||
| Room 14 Floor Temperature | °C | Read | |||
| Room 14 Relative Humidity | %RH | Read | |||
| Room 14 Dew Point | °C | Read | |||
| Room 14 Desired Temperature | °C | Read | |||
| Room 14 Heating/Cooling State | Read | ||||
| Room 14 Blocking Source | Read | ||||
| Room 14 Warning | Read | ||||
| Room 14 Error | Read | ||||
| Room 14 Low Battery | Read | ||||
| Room 14 Peripheral Lost | Read | ||||
| Room 14 Radiators State | Read | ||||
| Room 14 Underfloor State | Read | ||||
| Room 14 Drying State | Read | ||||
| Room 14 Thermal Integration State | Read | ||||
| Room 14 Ventilation State | Read | ||||
| Room 14 Blocking Source Radiators | Read | ||||
| Room 14 Blocking Source Underfloor | Read | ||||
| Room 14 Blocking Source Drying | Read | ||||
| Room 14 Blocking Source Integration | Read | ||||
| Room 14 Blocking Source Ventilation | Read | ||||
| Room 14 Room Type | Read | ||||
| Room 14 Associated Radiators | Read | ||||
| Room 14 Associated Underfloor | Read | ||||
| Room 14 Associated Drying | Read | ||||
| Room 14 Associated Thermal Integration | Read | ||||
| Room 14 Associated Ventilation | Read | ||||
| Room 14 Associated Heating Source | Read | ||||
| Room 14 Temperature Setpoint | °C | Read and write | |||
| Room 14 Mode | Read and write | ||||
| Room 14 Mode Override | Read and write | ||||
| Room 14 Standby Temperature | °C | Read and write | |||
| Room 14 Vacation Temperature | °C | Read and write | |||
| Room 14 Temperature Preset | Read and write | ||||
| Room 14 Thermostat Lock | Read and write | ||||
| Room 14 Exclude From Vacation | Read and write | ||||
| Room 14 Adaptive Mode | Read and write | ||||
| Room 14 Thermal Integration Heating Offset | Read and write | ||||
| Room 14 Thermal Integration Hysteresis | Read and write | ||||
| Room 14 Humidity Threshold Heating | %RH | Read and write | |||
| Room 14 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 14 Humidity Hysteresis | Read and write | ||||
| Room 14 Drying Cooling Water Offset | Read and write | ||||
| Room 14 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 14 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 14 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 14 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 14 Name | Read and write | ||||
| Room 15 Air Temperature | °C | Read | |||
| Room 15 Floor Temperature | °C | Read | |||
| Room 15 Relative Humidity | %RH | Read | |||
| Room 15 Dew Point | °C | Read | |||
| Room 15 Desired Temperature | °C | Read | |||
| Room 15 Heating/Cooling State | Read | ||||
| Room 15 Blocking Source | Read | ||||
| Room 15 Warning | Read | ||||
| Room 15 Error | Read | ||||
| Room 15 Low Battery | Read | ||||
| Room 15 Peripheral Lost | Read | ||||
| Room 15 Radiators State | Read | ||||
| Room 15 Underfloor State | Read | ||||
| Room 15 Drying State | Read | ||||
| Room 15 Thermal Integration State | Read | ||||
| Room 15 Ventilation State | Read | ||||
| Room 15 Blocking Source Radiators | Read | ||||
| Room 15 Blocking Source Underfloor | Read | ||||
| Room 15 Blocking Source Drying | Read | ||||
| Room 15 Blocking Source Integration | Read | ||||
| Room 15 Blocking Source Ventilation | Read | ||||
| Room 15 Room Type | Read | ||||
| Room 15 Associated Radiators | Read | ||||
| Room 15 Associated Underfloor | Read | ||||
| Room 15 Associated Drying | Read | ||||
| Room 15 Associated Thermal Integration | Read | ||||
| Room 15 Associated Ventilation | Read | ||||
| Room 15 Associated Heating Source | Read | ||||
| Room 15 Temperature Setpoint | °C | Read and write | |||
| Room 15 Mode | Read and write | ||||
| Room 15 Mode Override | Read and write | ||||
| Room 15 Standby Temperature | °C | Read and write | |||
| Room 15 Vacation Temperature | °C | Read and write | |||
| Room 15 Temperature Preset | Read and write | ||||
| Room 15 Thermostat Lock | Read and write | ||||
| Room 15 Exclude From Vacation | Read and write | ||||
| Room 15 Adaptive Mode | Read and write | ||||
| Room 15 Thermal Integration Heating Offset | Read and write | ||||
| Room 15 Thermal Integration Hysteresis | Read and write | ||||
| Room 15 Humidity Threshold Heating | %RH | Read and write | |||
| Room 15 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 15 Humidity Hysteresis | Read and write | ||||
| Room 15 Drying Cooling Water Offset | Read and write | ||||
| Room 15 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 15 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 15 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 15 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 15 Name | Read and write | ||||
| Room 16 Air Temperature | °C | Read | |||
| Room 16 Floor Temperature | °C | Read | |||
| Room 16 Relative Humidity | %RH | Read | |||
| Room 16 Dew Point | °C | Read | |||
| Room 16 Desired Temperature | °C | Read | |||
| Room 16 Heating/Cooling State | Read | ||||
| Room 16 Blocking Source | Read | ||||
| Room 16 Warning | Read | ||||
| Room 16 Error | Read | ||||
| Room 16 Low Battery | Read | ||||
| Room 16 Peripheral Lost | Read | ||||
| Room 16 Radiators State | Read | ||||
| Room 16 Underfloor State | Read | ||||
| Room 16 Drying State | Read | ||||
| Room 16 Thermal Integration State | Read | ||||
| Room 16 Ventilation State | Read | ||||
| Room 16 Blocking Source Radiators | Read | ||||
| Room 16 Blocking Source Underfloor | Read | ||||
| Room 16 Blocking Source Drying | Read | ||||
| Room 16 Blocking Source Integration | Read | ||||
| Room 16 Blocking Source Ventilation | Read | ||||
| Room 16 Room Type | Read | ||||
| Room 16 Associated Radiators | Read | ||||
| Room 16 Associated Underfloor | Read | ||||
| Room 16 Associated Drying | Read | ||||
| Room 16 Associated Thermal Integration | Read | ||||
| Room 16 Associated Ventilation | Read | ||||
| Room 16 Associated Heating Source | Read | ||||
| Room 16 Temperature Setpoint | °C | Read and write | |||
| Room 16 Mode | Read and write | ||||
| Room 16 Mode Override | Read and write | ||||
| Room 16 Standby Temperature | °C | Read and write | |||
| Room 16 Vacation Temperature | °C | Read and write | |||
| Room 16 Temperature Preset | Read and write | ||||
| Room 16 Thermostat Lock | Read and write | ||||
| Room 16 Exclude From Vacation | Read and write | ||||
| Room 16 Adaptive Mode | Read and write | ||||
| Room 16 Thermal Integration Heating Offset | Read and write | ||||
| Room 16 Thermal Integration Hysteresis | Read and write | ||||
| Room 16 Humidity Threshold Heating | %RH | Read and write | |||
| Room 16 Humidity Threshold Cooling | %RH | Read and write | |||
| Room 16 Humidity Hysteresis | Read and write | ||||
| Room 16 Drying Cooling Water Offset | Read and write | ||||
| Room 16 Drying Cooling Water Offset Hysteresis | Read and write | ||||
| Room 16 Dew Point Cooling Threshold | °C | Read and write | |||
| Room 16 Dew Point Cooling Threshold Hysteresis | Read and write | ||||
| Room 16 Humidity High Alarm Limit | %RH | Read and write | |||
| Room 16 Name | Read and write | ||||
| Outdoor Air Temperature | °C | Read | |||
| Outdoor Air Temperature Filtered | °C | Read | |||
| Outdoor Air Temperature Geometrical | °C | Read | |||
| Outdoor Warning | Read | ||||
| Outdoor Error | Read | ||||
| Outdoor Low Battery | Read | ||||
| Outdoor Peripheral Lost | Read | ||||
| Outdoor Air Temperature BMS Override | °C | Read and write | |||
| Outdoor Zone Name | Read | ||||
| Standby | Read and write | ||||
| Vacation | Read and write | ||||
| Heating/Cooling Mode BMS Override | Read and write | ||||
| Cooling Minimum Outdoor Temperature | °C | Read and write | |||
| Heating Maximum Outdoor Temperature | °C | Read and write | |||
| Cooling to Heating Change-over Temperature | °C | Read and write | |||
| Heating to Cooling Change-over Temperature | °C | Read and write | |||
| Datetime | Read and write | ||||
| Daylight Saving Time | Read and write | ||||
| Update Mode | Read and write | ||||
| Timezone Number | Read and write | ||||
| Modbus Slave Address | Read and write | ||||
| Modbus Baudrate | Read and write | ||||
| Modbus Mode | Read and write | ||||
| Modbus Password | Write | ||||
| Modbus Parity | Read and write | ||||
| Modbus Stop Bits | Read and write | ||||
| Location Name | Read and write | ||||
| Address Space Major Version | Read | ||||
| Address Space Minor Version | Read | ||||
| Address Space Major Version Holding | Read and write | ||||
| Address Space Minor Version Holding | Read and write | ||||
| Device Type | Read | ||||
| Hardware Version | Read | ||||
| Software Version | Read | ||||
| Software Version Minor | Read | ||||
| Serial Number Prefix | Read | ||||
| Serial Number | Read |
Loading registers…

Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show air and floor temperature, humidity and dew point for every room on one dashboard.
- Get an alert when a room reports a lost thermostat or a low battery.
- Alarm on a high dew point or humidity during floor cooling to prevent condensation.
- Put the whole building in vacation or standby mode from ModbusCloud when it is empty.
- Change a room setpoint remotely after a call from the occupant.
- Keep a year of room temperature history to settle comfort complaints.
Installation
Activate Modbus RTU on the Sentio display under System, Installer settings, Modbus configuration, and choose read only or read/write. The unit restarts.
Connect port A of the central control unit (pin 6 A, pin 3 B, pin 1 or 2 GND) to RS485 A and B on the ModbusCloud Gateway, with a 120 ohm termination at the bus ends.
Check address and speed: default address 1 at 19200 baud, 8 data bits, no parity, 1 stop bit.
In ModbusCloud, add a Modbus device with these settings and import this template.
Check that the air temperature of room 1 shows a realistic value; rooms that do not exist return no data.
Things to watch for
The control unit does not answer at all. What should I check?
Modbus is disabled by default and must be activated on a Sentio display. Use port A, the leftmost RJ-45 socket, and check A and B: pin 6 is A, pin 3 is B. Settings are 19200 baud, 8N1, address 1 unless changed. After activation port A no longer works for the display.
Why do some rooms give an error or no values?
Only rooms that exist in the installation have data. Reading a room that is not configured, or a sensor that is not fitted, can return an illegal data address or the invalid value 327.67. Remove the registers of unused rooms in ModbusCloud.
My write to a setpoint is not accepted. Why?
Writing needs Modbus mode read/write. In write-with-password mode you first write the password (default 1234) to the password register; writes are then accepted for 11 minutes. In schedule mode, vacation, standby or a temporary override the room setpoint is not used, so also check the room mode.
The unit sometimes returns a busy error.
After a change via the display, app or Modbus the unit saves its configuration and answers with server device busy for a moment. It also does this during start-up. The next reading normally succeeds; it is not a wiring fault.
Want to see how it works?