Accuenergy Accuenergy AcuRev 1310 Modbus RTU template

Accuenergy AcuRev 1310

Three-phase DIN-rail energy meter for submetering with tariff energy, demand and alarm output.

The Accuenergy AcuRev 1310 is a three-phase DIN-rail energy meter that measures current, voltage, power and energy per phase and per tariff for submetering in buildings and panels. This Modbus RTU template reads all measurements, energy counters, peak demand and event records, and lets you set CT and PT ratios, demand, alarm and relay settings from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
1069, read and write
Key readings
Phase currents · Phase and line voltages · Active power · Power factor · Imported and exported energy · Energy per tariff · Peak demand · Frequency
Available commands
CT and PT ratio · Wiring mode · Demand period · Alarm setpoints · Relay output · Energy counters
Compatible models
AcuRev 1312 · AcuRev 1313 · AcuRev 1314
Last updated

Registers (1069)

1064 read, 248 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Total CurrentARead8192FC03float32
Phase A CurrentARead8194FC03float32
Phase B CurrentARead8196FC03float32
Phase C CurrentARead8198FC03float32
Phase Average VoltageVRead8200FC03float32
Phase A VoltageVRead
Phase B VoltageVRead
Phase C VoltageVRead
Line Average VoltageVRead
Line AB VoltageVRead
Line BC VoltageVRead
Line CA VoltageVRead
FrequencyHzRead
Total Active PowerWRead
Phase A Active PowerWRead
Phase B Active PowerWRead
Phase C Active PowerWRead
Total Apparent PowerVARead
Phase A Apparent PowerVARead
Phase B Apparent PowerVARead
Phase C Apparent PowerVARead
Total Reactive PowervarRead
Phase A Reactive PowervarRead
Phase B Reactive PowervarRead
Phase C Reactive PowervarRead
Power FactorRead
PF Phase ARead
PF Phase BRead
PF Phase CRead
Phase Angle of V1 to V1°Read
Phase Angle of V2 to V1°Read
Phase Angle of V3 to V1°Read
Phase Angle of I1 to V1°Read
Phase Angle of I2 to V1°Read
Phase Angle of I3 to V1°Read
Neutral CurrentARead
Residual VoltageVRead
Temperature of Chips°CRead
Load TypeRead
System Active Power DemandWRead
System Reactive Power DemandvarRead
System Apparent Power DemandVARead
Phase A Current DemandARead
Phase B Current DemandARead
Phase C Current DemandARead
System Active Power Demand PredictionWRead
System Reactive Power Demand PredictionvarRead
System Apparent Power Demand PredictionVARead
Phase A Current Demand PredictionARead
Phase B Current Demand PredictionARead
Phase C Current Demand PredictionARead
Residual CurrentARead
Total Active Energy ExportedWhRead and write
Active Energy Exported Phase AWhRead and write
Active Energy Exported Phase BWhRead and write
Active Energy Exported Phase CWhRead and write
Total Active Energy ImportedWhRead and write
Active Energy Imported Phase AWhRead and write
Active Energy Imported Phase BWhRead and write
Active Energy Imported Phase CWhRead and write
Total Apparent Energy ExportedVAhRead and write
Apparent Energy Exported Phase AVAhRead and write
Apparent Energy Exported Phase BVAhRead and write
Apparent Energy Exported Phase CVAhRead and write
Total Apparent Energy ImportedVAhRead and write
Apparent Energy Imported Phase AVAhRead and write
Apparent Energy Imported Phase BVAhRead and write
Apparent Energy Imported Phase CVAhRead and write
Total Reactive Imported Q1varhRead and write
Reactive Imported Q1 Phase AvarhRead and write
Reactive Imported Q1 Phase BvarhRead and write
Reactive Imported Q1 Phase CvarhRead and write
Total Reactive Imported Q2varhRead and write
Reactive Imported Q2 Phase AvarhRead and write
Reactive Imported Q2 Phase BvarhRead and write
Reactive Imported Q2 Phase CvarhRead and write
Total Reactive Energy Exported Q3varhRead and write
Reactive Energy Exported Q3 Phase AvarhRead and write
Reactive Energy Exported Q3 Phase BvarhRead and write
Reactive Energy Exported Q3 Phase CvarhRead and write
Total Reactive Energy Exported Q4varhRead and write
Reactive Energy Exported Q4 Phase AvarhRead and write
Reactive Energy Exported Q4 Phase BvarhRead and write
Reactive Energy Exported Q4 Phase CvarhRead and write
Total Active EnergyWhRead and write
Total Active Energy Tariff 1WhRead and write
Total Active Energy Tariff 2WhRead and write
Total Active Energy Tariff 3WhRead and write
Total Active Energy Tariff 4WhRead and write
Net Active EnergyWhRead and write
Net Active Energy Tariff 1WhRead and write
Net Active Energy Tariff 2WhRead and write
Net Active Energy Tariff 3WhRead and write
Net Active Energy Tariff 4WhRead and write
Imported Active Energy Tariff 1WhRead and write
Imported Active Energy Tariff 2WhRead and write
Imported Active Energy Tariff 3WhRead and write
Imported Active Energy Tariff 4WhRead and write
Exported Active Energy Tariff 1WhRead and write
Exported Active Energy Tariff 2WhRead and write
Exported Active Energy Tariff 3WhRead and write
Exported Active Energy Tariff 4WhRead and write
Total Reactive Energy ImportedvarhRead and write
Total Reactive Energy Imported Tariff 1varhRead and write
Total Reactive Energy Imported Tariff 2varhRead and write
Total Reactive Energy Imported Tariff 3varhRead and write
Total Reactive Energy Imported Tariff 4varhRead and write
Total Reactive Energy ExportedvarhRead and write
Exported Reactive Energy Tariff 1varhRead and write
Exported Reactive Energy Tariff 2varhRead and write
Exported Reactive Energy Tariff 3varhRead and write
Exported Reactive Energy Tariff 4varhRead and write
Total Reactive EnergyvarhRead and write
Total Reactive Energy Tariff 1varhRead and write
Total Reactive Energy Tariff 2varhRead and write
Total Reactive Energy Tariff 3varhRead and write
Total Reactive Energy Tariff 4varhRead and write
Net Reactive EnergyvarhRead and write
Net Reactive Energy Tariff 1varhRead and write
Net Reactive Energy Tariff 2varhRead and write
Net Reactive Energy Tariff 3varhRead and write
Net Reactive Energy Tariff 4varhRead and write
Total Reactive Energy Imported Q1 Tariff 1varhRead and write
Total Reactive Energy Imported Q1 Tariff 2varhRead and write
Total Reactive Energy Imported Q1 Tariff 3varhRead and write
Total Reactive Energy Imported Q1 Tariff 4varhRead and write
Total Reactive Energy Imported Q2 Tariff 1varhRead and write
Total Reactive Energy Imported Q2 Tariff 2varhRead and write
Total Reactive Energy Imported Q2 Tariff 3varhRead and write
Total Reactive Energy Imported Q2 Tariff 4varhRead and write
Total Reactive Energy Exported Q3 Tariff 1varhRead and write
Total Reactive Energy Exported Q3 Tariff 2varhRead and write
Total Reactive Energy Exported Q3 Tariff 3varhRead and write
Total Reactive Energy Exported Q3 Tariff 4varhRead and write
Total Reactive Energy Exported Q4 Tariff 1varhRead and write
Total Reactive Energy Exported Q4 Tariff 2varhRead and write
Total Reactive Energy Exported Q4 Tariff 3varhRead and write
Total Reactive Energy Exported Q4 Tariff 4varhRead and write
Wiring Check ResultRead
Seal StatusRead
Prev Month Total Active Energy ImportedWhRead
Prev Month Active Energy Imported Phase AWhRead
Prev Month Active Energy Imported Phase BWhRead
Prev Month Active Energy Imported Phase CWhRead
Prev Month Total Active Energy Imported Tariff 1WhRead
Prev Month Total Active Energy Imported Tariff 2WhRead
Prev Month Total Active Energy Imported Tariff 3WhRead
Prev Month Total Active Energy Imported Tariff 4WhRead
Prev Month Total Active Energy ExportedWhRead
Prev Month Active Energy Exported Phase AWhRead
Prev Month Active Energy Exported Phase BWhRead
Prev Month Active Energy Exported Phase CWhRead
Prev Month Total Active Energy Exported Tariff 1WhRead
Prev Month Total Active Energy Exported Tariff 2WhRead
Prev Month Total Active Energy Exported Tariff 3WhRead
Prev Month Total Active Energy Exported Tariff 4WhRead
Prev Month Total Active EnergyWhRead
Prev Month Total Active Energy Tariff 1WhRead
Prev Month Total Active Energy Tariff 2WhRead
Prev Month Total Active Energy Tariff 3WhRead
Prev Month Total Active Energy Tariff 4WhRead
Prev Month Net Active EnergyWhRead
Prev Month Net Active Energy Tariff 1WhRead
Prev Month Net Active Energy Tariff 2WhRead
Prev Month Net Active Energy Tariff 3WhRead
Prev Month Net Active Energy Tariff 4WhRead
Prev Month Total Reactive Energy Imported Q1varhRead
Prev Month Reactive Energy Imported Q1 Phase AvarhRead
Prev Month Reactive Energy Imported Q1 Phase BvarhRead
Prev Month Reactive Energy Imported Q1 Phase CvarhRead
Prev Month Total Reactive Energy Imported Q1 Tariff 1varhRead
Prev Month Total Reactive Energy Imported Q1 Tariff 2varhRead
Prev Month Total Reactive Energy Imported Q1 Tariff 3varhRead
Prev Month Total Reactive Energy Imported Q1 Tariff 4varhRead
Prev Month Total Reactive Energy Imported Q2varhRead
Prev Month Reactive Energy Imported Q2 Phase AvarhRead
Prev Month Reactive Energy Imported Q2 Phase BvarhRead
Prev Month Reactive Energy Imported Q2 Phase CvarhRead
Prev Month Total Reactive Energy Imported Q2 Tariff 1varhRead
Prev Month Total Reactive Energy Imported Q2 Tariff 2varhRead
Prev Month Total Reactive Energy Imported Q2 Tariff 3varhRead
Prev Month Total Reactive Energy Imported Q2 Tariff 4varhRead
Prev Month Total Reactive Energy Exported Q3varhRead
Prev Month Reactive Energy Exported Q3 Phase AvarhRead
Prev Month Reactive Energy Exported Q3 Phase BvarhRead
Prev Month Reactive Energy Exported Q3 Phase CvarhRead
Prev Month Total Reactive Energy Exported Q3 Tariff 1varhRead
Prev Month Total Reactive Energy Exported Q3 Tariff 2varhRead
Prev Month Total Reactive Energy Exported Q3 Tariff 3varhRead
Prev Month Total Reactive Energy Exported Q3 Tariff 4varhRead
Prev Month Total Reactive Energy Exported Q4varhRead
Prev Month Reactive Energy Exported Q4 Phase AvarhRead
Prev Month Reactive Energy Exported Q4 Phase BvarhRead
Prev Month Reactive Energy Exported Q4 Phase CvarhRead
Prev Month Total Reactive Energy Exported Q4 Tariff 1varhRead
Prev Month Total Reactive Energy Exported Q4 Tariff 2varhRead
Prev Month Total Reactive Energy Exported Q4 Tariff 3varhRead
Prev Month Total Reactive Energy Exported Q4 Tariff 4varhRead
Prev Month Total Reactive Energy ImportedvarhRead
Prev Month Total Reactive Energy Imported Tariff 1varhRead
Prev Month Total Reactive Energy Imported Tariff 2varhRead
Prev Month Total Reactive Energy Imported Tariff 3varhRead
Prev Month Total Reactive Energy Imported Tariff 4varhRead
Prev Month Total Reactive Energy ExportedvarhRead
Prev Month Total Reactive Energy Exported Tariff 1varhRead
Prev Month Total Reactive Energy Exported Tariff 2varhRead
Prev Month Total Reactive Energy Exported Tariff 3varhRead
Prev Month Total Reactive Energy Exported Tariff 4varhRead
Prev Month Total Reactive EnergyvarhRead
Prev Month Total Reactive Energy Tariff 1varhRead
Prev Month Total Reactive Energy Tariff 2varhRead
Prev Month Total Reactive Energy Tariff 3varhRead
Prev Month Total Reactive Energy Tariff 4varhRead
Prev Month Net Reactive EnergyvarhRead
Prev Month Net Reactive Energy Tariff 1varhRead
Prev Month Net Reactive Energy Tariff 2varhRead
Prev Month Net Reactive Energy Tariff 3varhRead
Prev Month Net Reactive Energy Tariff 4varhRead
Prev Month Total Apparent Energy ImportedVAhRead
Prev Month Apparent Energy Imported Phase AVAhRead
Prev Month Apparent Energy Imported Phase BVAhRead
Prev Month Apparent Energy Imported Phase CVAhRead
Prev Month Total Apparent Energy ExportedVAhRead
Prev Month Apparent Energy Exported Phase AVAhRead
Prev Month Apparent Energy Exported Phase BVAhRead
Prev Month Apparent Energy Exported Phase CVAhRead
Two Months Ago Total Active Energy ImportedWhRead
Two Months Ago Active Energy Imported Phase AWhRead
Two Months Ago Active Energy Imported Phase BWhRead
Two Months Ago Active Energy Imported Phase CWhRead
Two Months Ago Total Active Energy Imported Tariff 1WhRead
Two Months Ago Total Active Energy Imported Tariff 2WhRead
Two Months Ago Total Active Energy Imported Tariff 3WhRead
Two Months Ago Total Active Energy Imported Tariff 4WhRead
Two Months Ago Total Active Energy ExportedWhRead
Two Months Ago Active Energy Exported Phase AWhRead
Two Months Ago Active Energy Exported Phase BWhRead
Two Months Ago Active Energy Exported Phase CWhRead
Two Months Ago Total Active Energy Exported Tariff 1WhRead
Two Months Ago Total Active Energy Exported Tariff 2WhRead
Two Months Ago Total Active Energy Exported Tariff 3WhRead
Two Months Ago Total Active Energy Exported Tariff 4WhRead
Two Months Ago Total Active EnergyWhRead
Two Months Ago Total Active Energy Tariff 1WhRead
Two Months Ago Total Active Energy Tariff 2WhRead
Two Months Ago Total Active Energy Tariff 3WhRead
Two Months Ago Total Active Energy Tariff 4WhRead
Two Months Ago Net Active EnergyWhRead
Two Months Ago Net Active Energy Tariff 1WhRead
Two Months Ago Net Active Energy Tariff 2WhRead
Two Months Ago Net Active Energy Tariff 3WhRead
Two Months Ago Net Active Energy Tariff 4WhRead
Two Months Ago Total Reactive Energy Imported Q1varhRead
Two Months Ago Reactive Energy Imported Q1 Phase AvarhRead
Two Months Ago Reactive Energy Imported Q1 Phase BvarhRead
Two Months Ago Reactive Energy Imported Q1 Phase CvarhRead
Two Months Ago Total Reactive Energy Imported Q1 Tariff 1varhRead
Two Months Ago Total Reactive Energy Imported Q1 Tariff 2varhRead
Two Months Ago Total Reactive Energy Imported Q1 Tariff 3varhRead
Two Months Ago Total Reactive Energy Imported Q1 Tariff 4varhRead
Two Months Ago Total Reactive Energy Imported Q2varhRead
Two Months Ago Reactive Energy Imported Q2 Phase AvarhRead
Two Months Ago Reactive Energy Imported Q2 Phase BvarhRead
Two Months Ago Reactive Energy Imported Q2 Phase CvarhRead
Two Months Ago Total Reactive Energy Imported Q2 Tariff 1varhRead
Two Months Ago Total Reactive Energy Imported Q2 Tariff 2varhRead
Two Months Ago Total Reactive Energy Imported Q2 Tariff 3varhRead
Two Months Ago Total Reactive Energy Imported Q2 Tariff 4varhRead
Two Months Ago Total Reactive Energy Exported Q3varhRead
Two Months Ago Reactive Energy Exported Q3 Phase AvarhRead
Two Months Ago Reactive Energy Exported Q3 Phase BvarhRead
Two Months Ago Reactive Energy Exported Q3 Phase CvarhRead
Two Months Ago Total Reactive Energy Exported Q3 Tariff 1varhRead
Two Months Ago Total Reactive Energy Exported Q3 Tariff 2varhRead
Two Months Ago Total Reactive Energy Exported Q3 Tariff 3varhRead
Two Months Ago Total Reactive Energy Exported Q3 Tariff 4varhRead
Two Months Ago Total Reactive Energy Exported Q4varhRead
Two Months Ago Reactive Energy Exported Q4 Phase AvarhRead
Two Months Ago Reactive Energy Exported Q4 Phase BvarhRead
Two Months Ago Reactive Energy Exported Q4 Phase CvarhRead
Two Months Ago Total Reactive Energy Exported Q4 Tariff 1varhRead
Two Months Ago Total Reactive Energy Exported Q4 Tariff 2varhRead
Two Months Ago Total Reactive Energy Exported Q4 Tariff 3varhRead
Two Months Ago Total Reactive Energy Exported Q4 Tariff 4varhRead
Two Months Ago Total Reactive Energy ImportedvarhRead
Two Months Ago Total Reactive Energy Imported Tariff 1varhRead
Two Months Ago Total Reactive Energy Imported Tariff 2varhRead
Two Months Ago Total Reactive Energy Imported Tariff 3varhRead
Two Months Ago Total Reactive Energy Imported Tariff 4varhRead
Two Months Ago Total Reactive Energy ExportedvarhRead
Two Months Ago Total Reactive Energy Exported Tariff 1varhRead
Two Months Ago Total Reactive Energy Exported Tariff 2varhRead
Two Months Ago Total Reactive Energy Exported Tariff 3varhRead
Two Months Ago Total Reactive Energy Exported Tariff 4varhRead
Two Months Ago Total Reactive EnergyvarhRead
Two Months Ago Total Reactive Energy Tariff 1varhRead
Two Months Ago Total Reactive Energy Tariff 2varhRead
Two Months Ago Total Reactive Energy Tariff 3varhRead
Two Months Ago Total Reactive Energy Tariff 4varhRead
Two Months Ago Net Reactive EnergyvarhRead
Two Months Ago Net Reactive Energy Tariff 1varhRead
Two Months Ago Net Reactive Energy Tariff 2varhRead
Two Months Ago Net Reactive Energy Tariff 3varhRead
Two Months Ago Net Reactive Energy Tariff 4varhRead
Two Months Ago Total Apparent Energy ImportedVAhRead
Two Months Ago Apparent Energy Imported Phase AVAhRead
Two Months Ago Apparent Energy Imported Phase BVAhRead
Two Months Ago Apparent Energy Imported Phase CVAhRead
Two Months Ago Total Apparent Energy ExportedVAhRead
Two Months Ago Apparent Energy Exported Phase AVAhRead
Two Months Ago Apparent Energy Exported Phase BVAhRead
Two Months Ago Apparent Energy Exported Phase CVAhRead
This Month Total Imported Active Demand PeakWRead
This Month Total Imported Active Demand Peak Time YY-MMRead
This Month Total Imported Active Demand Peak Time DD-hhRead
This Month Total Imported Active Demand Peak Time mm-ssRead
This Month Imported Active Demand Tariff 1 PeakWRead
This Month Imported Active Demand Tariff 1 Peak Time YY-MMRead
This Month Imported Active Demand Tariff 1 Peak Time DD-hhRead
This Month Imported Active Demand Tariff 1 Peak Time mm-ssRead
This Month Imported Active Demand Tariff 2 PeakWRead
This Month Imported Active Demand Tariff 2 Peak Time YY-MMRead
This Month Imported Active Demand Tariff 2 Peak Time DD-hhRead
This Month Imported Active Demand Tariff 2 Peak Time mm-ssRead
This Month Imported Active Demand Tariff 3 PeakWRead
This Month Imported Active Demand Tariff 3 Peak Time YY-MMRead
This Month Imported Active Demand Tariff 3 Peak Time DD-hhRead
This Month Imported Active Demand Tariff 3 Peak Time mm-ssRead
This Month Imported Active Demand Tariff 4 PeakWRead
This Month Imported Active Demand Tariff 4 Peak Time YY-MMRead
This Month Imported Active Demand Tariff 4 Peak Time DD-hhRead
This Month Imported Active Demand Tariff 4 Peak Time mm-ssRead
This Month Total Exported Active Demand PeakWRead
This Month Total Exported Active Demand Peak Time YY-MMRead
This Month Total Exported Active Demand Peak Time DD-hhRead
This Month Total Exported Active Demand Peak Time mm-ssRead
This Month Exported Active Demand Tariff 1 PeakWRead
This Month Exported Active Demand Tariff 1 Peak Time YY-MMRead
This Month Exported Active Demand Tariff 1 Peak Time DD-hhRead
This Month Exported Active Demand Tariff 1 Peak Time mm-ssRead
This Month Exported Active Demand Tariff 2 PeakWRead
This Month Exported Active Demand Tariff 2 Peak Time YY-MMRead
This Month Exported Active Demand Tariff 2 Peak Time DD-hhRead
This Month Exported Active Demand Tariff 2 Peak Time mm-ssRead
This Month Exported Active Demand Tariff 3 PeakWRead
This Month Exported Active Demand Tariff 3 Peak Time YY-MMRead
This Month Exported Active Demand Tariff 3 Peak Time DD-hhRead
This Month Exported Active Demand Tariff 3 Peak Time mm-ssRead
This Month Exported Active Demand Tariff 4 PeakWRead
This Month Exported Active Demand Tariff 4 Peak Time YY-MMRead
This Month Exported Active Demand Tariff 4 Peak Time DD-hhRead
This Month Exported Active Demand Tariff 4 Peak Time mm-ssRead
This Month Total Imported Reactive Demand PeakvarRead
This Month Total Imported Reactive Demand Peak Time YY-MMRead
This Month Total Imported Reactive Demand Peak Time DD-hhRead
This Month Total Imported Reactive Demand Peak Time mm-ssRead
This Month Imported Reactive Demand Tariff 1 PeakvarRead
This Month Imported Reactive Demand Tariff 1 Peak Time YY-MMRead
This Month Imported Reactive Demand Tariff 1 Peak Time DD-hhRead
This Month Imported Reactive Demand Tariff 1 Peak Time mm-ssRead
This Month Imported Reactive Demand Tariff 2 PeakvarRead
This Month Imported Reactive Demand Tariff 2 Peak Time YY-MMRead
This Month Imported Reactive Demand Tariff 2 Peak Time DD-hhRead
This Month Imported Reactive Demand Tariff 2 Peak Time mm-ssRead
This Month Imported Reactive Demand Tariff 3 PeakvarRead
This Month Imported Reactive Demand Tariff 3 Peak Time YY-MMRead
This Month Imported Reactive Demand Tariff 3 Peak Time DD-hhRead
This Month Imported Reactive Demand Tariff 3 Peak Time mm-ssRead
This Month Imported Reactive Demand Tariff 4 PeakvarRead
This Month Imported Reactive Demand Tariff 4 Peak Time YY-MMRead
This Month Imported Reactive Demand Tariff 4 Peak Time DD-hhRead
This Month Imported Reactive Demand Tariff 4 Peak Time mm-ssRead
This Month Total Exported Reactive Demand PeakvarRead
This Month Total Exported Reactive Demand Peak Time YY-MMRead
This Month Total Exported Reactive Demand Peak Time DD-hhRead
This Month Total Exported Reactive Demand Peak Time mm-ssRead
This Month Exported Reactive Demand Tariff 1 PeakvarRead
This Month Exported Reactive Demand Tariff 1 Peak Time YY-MMRead
This Month Exported Reactive Demand Tariff 1 Peak Time DD-hhRead
This Month Exported Reactive Demand Tariff 1 Peak Time mm-ssRead
This Month Exported Reactive Demand Tariff 2 PeakvarRead
This Month Exported Reactive Demand Tariff 2 Peak Time YY-MMRead
This Month Exported Reactive Demand Tariff 2 Peak Time DD-hhRead
This Month Exported Reactive Demand Tariff 2 Peak Time mm-ssRead
This Month Exported Reactive Demand Tariff 3 PeakvarRead
This Month Exported Reactive Demand Tariff 3 Peak Time YY-MMRead
This Month Exported Reactive Demand Tariff 3 Peak Time DD-hhRead
This Month Exported Reactive Demand Tariff 3 Peak Time mm-ssRead
This Month Exported Reactive Demand Tariff 4 PeakvarRead
This Month Exported Reactive Demand Tariff 4 Peak Time YY-MMRead
This Month Exported Reactive Demand Tariff 4 Peak Time DD-hhRead
This Month Exported Reactive Demand Tariff 4 Peak Time mm-ssRead
This Month Total Apparent Demand PeakVARead
This Month Total Apparent Demand Peak Time YY-MMRead
This Month Total Apparent Demand Peak Time DD-hhRead
This Month Total Apparent Demand Peak Time mm-ssRead
This Month Phase A Current Demand PeakARead
This Month Phase A Current Demand Peak Time YY-MMRead
This Month Phase A Current Demand Peak Time DD-hhRead
This Month Phase A Current Demand Peak Time mm-ssRead
This Month Phase B Current Demand PeakARead
This Month Phase B Current Demand Peak Time YY-MMRead
This Month Phase B Current Demand Peak Time DD-hhRead
This Month Phase B Current Demand Peak Time mm-ssRead
This Month Phase C Current Demand PeakARead
This Month Phase C Current Demand Peak Time YY-MMRead
This Month Phase C Current Demand Peak Time DD-hhRead
This Month Phase C Current Demand Peak Time mm-ssRead
Last Month Total Imported Active Demand PeakWRead
Last Month Total Imported Active Demand Peak Time YY-MMRead
Last Month Total Imported Active Demand Peak Time DD-hhRead
Last Month Total Imported Active Demand Peak Time mm-ssRead
Last Month Imported Active Demand Tariff 1 PeakWRead
Last Month Imported Active Demand Tariff 1 Peak Time YY-MMRead
Last Month Imported Active Demand Tariff 1 Peak Time DD-hhRead
Last Month Imported Active Demand Tariff 1 Peak Time mm-ssRead
Last Month Imported Active Demand Tariff 2 PeakWRead
Last Month Imported Active Demand Tariff 2 Peak Time YY-MMRead
Last Month Imported Active Demand Tariff 2 Peak Time DD-hhRead
Last Month Imported Active Demand Tariff 2 Peak Time mm-ssRead
Last Month Imported Active Demand Tariff 3 PeakWRead
Last Month Imported Active Demand Tariff 3 Peak Time YY-MMRead
Last Month Imported Active Demand Tariff 3 Peak Time DD-hhRead
Last Month Imported Active Demand Tariff 3 Peak Time mm-ssRead
Last Month Imported Active Demand Tariff 4 PeakWRead
Last Month Imported Active Demand Tariff 4 Peak Time YY-MMRead
Last Month Imported Active Demand Tariff 4 Peak Time DD-hhRead
Last Month Imported Active Demand Tariff 4 Peak Time mm-ssRead
Last Month Total Exported Active Demand PeakWRead
Last Month Total Exported Active Demand Peak Time YY-MMRead
Last Month Total Exported Active Demand Peak Time DD-hhRead
Last Month Total Exported Active Demand Peak Time mm-ssRead
Last Month Exported Active Demand Tariff 1 PeakWRead
Last Month Exported Active Demand Tariff 1 Peak Time YY-MMRead
Last Month Exported Active Demand Tariff 1 Peak Time DD-hhRead
Last Month Exported Active Demand Tariff 1 Peak Time mm-ssRead
Last Month Exported Active Demand Tariff 2 PeakWRead
Last Month Exported Active Demand Tariff 2 Peak Time YY-MMRead
Last Month Exported Active Demand Tariff 2 Peak Time DD-hhRead
Last Month Exported Active Demand Tariff 2 Peak Time mm-ssRead
Last Month Exported Active Demand Tariff 3 PeakWRead
Last Month Exported Active Demand Tariff 3 Peak Time YY-MMRead
Last Month Exported Active Demand Tariff 3 Peak Time DD-hhRead
Last Month Exported Active Demand Tariff 3 Peak Time mm-ssRead
Last Month Exported Active Demand Tariff 4 PeakWRead
Last Month Exported Active Demand Tariff 4 Peak Time YY-MMRead
Last Month Exported Active Demand Tariff 4 Peak Time DD-hhRead
Last Month Exported Active Demand Tariff 4 Peak Time mm-ssRead
Last Month Total Imported Reactive Demand PeakvarRead
Last Month Total Imported Reactive Demand Peak Time YY-MMRead
Last Month Total Imported Reactive Demand Peak Time DD-hhRead
Last Month Total Imported Reactive Demand Peak Time mm-ssRead
Last Month Imported Reactive Demand Tariff 1 PeakvarRead
Last Month Imported Reactive Demand Tariff 1 Peak Time YY-MMRead
Last Month Imported Reactive Demand Tariff 1 Peak Time DD-hhRead
Last Month Imported Reactive Demand Tariff 1 Peak Time mm-ssRead
Last Month Imported Reactive Demand Tariff 2 PeakvarRead
Last Month Imported Reactive Demand Tariff 2 Peak Time YY-MMRead
Last Month Imported Reactive Demand Tariff 2 Peak Time DD-hhRead
Last Month Imported Reactive Demand Tariff 2 Peak Time mm-ssRead
Last Month Imported Reactive Demand Tariff 3 PeakvarRead
Last Month Imported Reactive Demand Tariff 3 Peak Time YY-MMRead
Last Month Imported Reactive Demand Tariff 3 Peak Time DD-hhRead
Last Month Imported Reactive Demand Tariff 3 Peak Time mm-ssRead
Last Month Imported Reactive Demand Tariff 4 PeakvarRead
Last Month Imported Reactive Demand Tariff 4 Peak Time YY-MMRead
Last Month Imported Reactive Demand Tariff 4 Peak Time DD-hhRead
Last Month Imported Reactive Demand Tariff 4 Peak Time mm-ssRead
Last Month Total Exported Reactive Demand PeakvarRead
Last Month Total Exported Reactive Demand Peak Time YY-MMRead
Last Month Total Exported Reactive Demand Peak Time DD-hhRead
Last Month Total Exported Reactive Demand Peak Time mm-ssRead
Last Month Exported Reactive Demand Tariff 1 PeakvarRead
Last Month Exported Reactive Demand Tariff 1 Peak Time YY-MMRead
Last Month Exported Reactive Demand Tariff 1 Peak Time DD-hhRead
Last Month Exported Reactive Demand Tariff 1 Peak Time mm-ssRead
Last Month Exported Reactive Demand Tariff 2 PeakvarRead
Last Month Exported Reactive Demand Tariff 2 Peak Time YY-MMRead
Last Month Exported Reactive Demand Tariff 2 Peak Time DD-hhRead
Last Month Exported Reactive Demand Tariff 2 Peak Time mm-ssRead
Last Month Exported Reactive Demand Tariff 3 PeakvarRead
Last Month Exported Reactive Demand Tariff 3 Peak Time YY-MMRead
Last Month Exported Reactive Demand Tariff 3 Peak Time DD-hhRead
Last Month Exported Reactive Demand Tariff 3 Peak Time mm-ssRead
Last Month Exported Reactive Demand Tariff 4 PeakvarRead
Last Month Exported Reactive Demand Tariff 4 Peak Time YY-MMRead
Last Month Exported Reactive Demand Tariff 4 Peak Time DD-hhRead
Last Month Exported Reactive Demand Tariff 4 Peak Time mm-ssRead
Last Month Total Apparent Demand PeakVARead
Last Month Total Apparent Demand Peak Time YY-MMRead
Last Month Total Apparent Demand Peak Time DD-hhRead
Last Month Total Apparent Demand Peak Time mm-ssRead
Last Month Phase A Current Demand PeakARead
Last Month Phase A Current Demand Peak Time YY-MMRead
Last Month Phase A Current Demand Peak Time DD-hhRead
Last Month Phase A Current Demand Peak Time mm-ssRead
Last Month Phase B Current Demand PeakARead
Last Month Phase B Current Demand Peak Time YY-MMRead
Last Month Phase B Current Demand Peak Time DD-hhRead
Last Month Phase B Current Demand Peak Time mm-ssRead
Last Month Phase C Current Demand PeakARead
Last Month Phase C Current Demand Peak Time YY-MMRead
Last Month Phase C Current Demand Peak Time DD-hhRead
Last Month Phase C Current Demand Peak Time mm-ssRead
Max Total CurrentARead
Max Total Current Time YY-MMRead
Max Total Current Time DD-hhRead
Max Total Current Time mm-ssRead
Max Phase A CurrentARead
Max Phase A Current Time YY-MMRead
Max Phase A Current Time DD-hhRead
Max Phase A Current Time mm-ssRead
Max Phase B CurrentARead
Max Phase B Current Time YY-MMRead
Max Phase B Current Time DD-hhRead
Max Phase B Current Time mm-ssRead
Max Phase C CurrentARead
Max Phase C Current Time YY-MMRead
Max Phase C Current Time DD-hhRead
Max Phase C Current Time mm-ssRead
Max Average Phase VoltageVRead
Max Average Phase Voltage Time YY-MMRead
Max Average Phase Voltage Time DD-hhRead
Max Average Phase Voltage Time mm-ssRead
Max Phase A VoltageVRead
Max Phase A Voltage Time YY-MMRead
Max Phase A Voltage Time DD-hhRead
Max Phase A Voltage Time mm-ssRead
Max Phase B VoltageVRead
Max Phase B Voltage Time YY-MMRead
Max Phase B Voltage Time DD-hhRead
Max Phase B Voltage Time mm-ssRead
Max Phase C VoltageVRead
Max Phase C Voltage Time YY-MMRead
Max Phase C Voltage Time DD-hhRead
Max Phase C Voltage Time mm-ssRead
Max Average Line VoltageVRead
Max Average Line Voltage Time YY-MMRead
Max Average Line Voltage Time DD-hhRead
Max Average Line Voltage Time mm-ssRead
Max Line AB VoltageVRead
Max Line AB Voltage Time YY-MMRead
Max Line AB Voltage Time DD-hhRead
Max Line AB Voltage Time mm-ssRead
Max Line BC VoltageVRead
Max Line BC Voltage Time YY-MMRead
Max Line BC Voltage Time DD-hhRead
Max Line BC Voltage Time mm-ssRead
Max Line CA VoltageVRead
Max Line CA Voltage Time YY-MMRead
Max Line CA Voltage Time DD-hhRead
Max Line CA Voltage Time mm-ssRead
Max FrequencyHzRead
Max Frequency Time YY-MMRead
Max Frequency Time DD-hhRead
Max Frequency Time mm-ssRead
Max Total Active PowerWRead
Max Total Active Power Time YY-MMRead
Max Total Active Power Time DD-hhRead
Max Total Active Power Time mm-ssRead
Max Phase A Active PowerWRead
Max Phase A Active Power Time YY-MMRead
Max Phase A Active Power Time DD-hhRead
Max Phase A Active Power Time mm-ssRead
Max Phase B Active PowerWRead
Max Phase B Active Power Time YY-MMRead
Max Phase B Active Power Time DD-hhRead
Max Phase B Active Power Time mm-ssRead
Max Phase C Active PowerWRead
Max Phase C Active Power Time YY-MMRead
Max Phase C Active Power Time DD-hhRead
Max Phase C Active Power Time mm-ssRead
Max Total Apparent PowerVARead
Max Total Apparent Power Time YY-MMRead
Max Total Apparent Power Time DD-hhRead
Max Total Apparent Power Time mm-ssRead
Max Phase A Apparent PowerVARead
Max Phase A Apparent Power Time YY-MMRead
Max Phase A Apparent Power Time DD-hhRead
Max Phase A Apparent Power Time mm-ssRead
Max Phase B Apparent PowerVARead
Max Phase B Apparent Power Time YY-MMRead
Max Phase B Apparent Power Time DD-hhRead
Max Phase B Apparent Power Time mm-ssRead
Max Phase C Apparent PowerVARead
Max Phase C Apparent Power Time YY-MMRead
Max Phase C Apparent Power Time DD-hhRead
Max Phase C Apparent Power Time mm-ssRead
Max Total Reactive PowervarRead
Max Total Reactive Power Time YY-MMRead
Max Total Reactive Power Time DD-hhRead
Max Total Reactive Power Time mm-ssRead
Max Phase A Reactive PowervarRead
Max Phase A Reactive Power Time YY-MMRead
Max Phase A Reactive Power Time DD-hhRead
Max Phase A Reactive Power Time mm-ssRead
Max Phase B Reactive PowervarRead
Max Phase B Reactive Power Time YY-MMRead
Max Phase B Reactive Power Time DD-hhRead
Max Phase B Reactive Power Time mm-ssRead
Max Phase C Reactive PowervarRead
Max Phase C Reactive Power Time YY-MMRead
Max Phase C Reactive Power Time DD-hhRead
Max Phase C Reactive Power Time mm-ssRead
Min Total CurrentARead
Min Total Current Time YY-MMRead
Min Total Current Time DD-hhRead
Min Total Current Time mm-ssRead
Min Phase A CurrentARead
Min Phase A Current Time YY-MMRead
Min Phase A Current Time DD-hhRead
Min Phase A Current Time mm-ssRead
Min Phase B CurrentARead
Min Phase B Current Time YY-MMRead
Min Phase B Current Time DD-hhRead
Min Phase B Current Time mm-ssRead
Min Phase C CurrentARead
Min Phase C Current Time YY-MMRead
Min Phase C Current Time DD-hhRead
Min Phase C Current Time mm-ssRead
Min Average Phase VoltageVRead
Min Average Phase Voltage Time YY-MMRead
Min Average Phase Voltage Time DD-hhRead
Min Average Phase Voltage Time mm-ssRead
Min Phase A VoltageVRead
Min Phase A Voltage Time YY-MMRead
Min Phase A Voltage Time DD-hhRead
Min Phase A Voltage Time mm-ssRead
Min Phase B VoltageVRead
Min Phase B Voltage Time YY-MMRead
Min Phase B Voltage Time DD-hhRead
Min Phase B Voltage Time mm-ssRead
Min Phase C VoltageVRead
Min Phase C Voltage Time YY-MMRead
Min Phase C Voltage Time DD-hhRead
Min Phase C Voltage Time mm-ssRead
Min Average Line VoltageVRead
Min Average Line Voltage Time YY-MMRead
Min Average Line Voltage Time DD-hhRead
Min Average Line Voltage Time mm-ssRead
Min Line AB VoltageVRead
Min Line AB Voltage Time YY-MMRead
Min Line AB Voltage Time DD-hhRead
Min Line AB Voltage Time mm-ssRead
Min Line BC VoltageVRead
Min Line BC Voltage Time YY-MMRead
Min Line BC Voltage Time DD-hhRead
Min Line BC Voltage Time mm-ssRead
Min Line CA VoltageVRead
Min Line CA Voltage Time YY-MMRead
Min Line CA Voltage Time DD-hhRead
Min Line CA Voltage Time mm-ssRead
Min FrequencyHzRead
Min Frequency Time YY-MMRead
Min Frequency Time DD-hhRead
Min Frequency Time mm-ssRead
Min Total Active PowerWRead
Min Total Active Power Time YY-MMRead
Min Total Active Power Time DD-hhRead
Min Total Active Power Time mm-ssRead
Min Phase A Active PowerWRead
Min Phase A Active Power Time YY-MMRead
Min Phase A Active Power Time DD-hhRead
Min Phase A Active Power Time mm-ssRead
Min Phase B Active PowerWRead
Min Phase B Active Power Time YY-MMRead
Min Phase B Active Power Time DD-hhRead
Min Phase B Active Power Time mm-ssRead
Min Phase C Active PowerWRead
Min Phase C Active Power Time YY-MMRead
Min Phase C Active Power Time DD-hhRead
Min Phase C Active Power Time mm-ssRead
Min Total Apparent PowerVARead
Min Total Apparent Power Time YY-MMRead
Min Total Apparent Power Time DD-hhRead
Min Total Apparent Power Time mm-ssRead
Min Phase A Apparent PowerVARead
Min Phase A Apparent Power Time YY-MMRead
Min Phase A Apparent Power Time DD-hhRead
Min Phase A Apparent Power Time mm-ssRead
Min Phase B Apparent PowerVARead
Min Phase B Apparent Power Time YY-MMRead
Min Phase B Apparent Power Time DD-hhRead
Min Phase B Apparent Power Time mm-ssRead
Min Phase C Apparent PowerVARead
Min Phase C Apparent Power Time YY-MMRead
Min Phase C Apparent Power Time DD-hhRead
Min Phase C Apparent Power Time mm-ssRead
Min Total Reactive PowervarRead
Min Total Reactive Power Time YY-MMRead
Min Total Reactive Power Time DD-hhRead
Min Total Reactive Power Time mm-ssRead
Min Phase A Reactive PowervarRead
Min Phase A Reactive Power Time YY-MMRead
Min Phase A Reactive Power Time DD-hhRead
Min Phase A Reactive Power Time mm-ssRead
Min Phase B Reactive PowervarRead
Min Phase B Reactive Power Time YY-MMRead
Min Phase B Reactive Power Time DD-hhRead
Min Phase B Reactive Power Time mm-ssRead
Min Phase C Reactive PowervarRead
Min Phase C Reactive Power Time YY-MMRead
Min Phase C Reactive Power Time DD-hhRead
Min Phase C Reactive Power Time mm-ssRead
Dual Source EnableRead and write
Dual Source Energy SourceRead and write
Clear Dual Source EnergyWrite
Clear Dual Source Change LogWrite
Dual Source Grid Active EnergyWhRead and write
Dual Source Alternate Active EnergyWhRead and write
Dual Source Grid Reactive EnergyvarhRead and write
Dual Source Alternate Reactive EnergyvarhRead and write
Dual Source Grid Apparent EnergyVAhRead and write
Dual Source Alternate Apparent EnergyVAhRead and write
Source Change 1 Time YY-MMRead
Source Change 1 Time DD-hhRead
Source Change 1 Time mm-ssRead
Source Change 1 DirectionRead
Source Change 1 Grid Active EnergyWhRead
Source Change 1 Alternate Active EnergyWhRead
Source Change 1 Grid Reactive EnergyvarhRead
Source Change 1 Alternate Reactive EnergyvarhRead
Source Change 1 Grid Apparent EnergyVAhRead
Source Change 1 Alternate Apparent EnergyVAhRead
Source Change 2 Time YY-MMRead
Source Change 2 Time DD-hhRead
Source Change 2 Time mm-ssRead
Source Change 2 DirectionRead
Source Change 2 Grid Active EnergyWhRead
Source Change 2 Alternate Active EnergyWhRead
Source Change 2 Grid Reactive EnergyvarhRead
Source Change 2 Alternate Reactive EnergyvarhRead
Source Change 2 Grid Apparent EnergyVAhRead
Source Change 2 Alternate Apparent EnergyVAhRead
Source Change 3 Time YY-MMRead
Source Change 3 Time DD-hhRead
Source Change 3 Time mm-ssRead
Source Change 3 DirectionRead
Source Change 3 Grid Active EnergyWhRead
Source Change 3 Alternate Active EnergyWhRead
Source Change 3 Grid Reactive EnergyvarhRead
Source Change 3 Alternate Reactive EnergyvarhRead
Source Change 3 Grid Apparent EnergyVAhRead
Source Change 3 Alternate Apparent EnergyVAhRead
Meter AddressRead and write
Baud RateRead and write
Parity SettingRead and write
Energy Pulse Output TypeRead and write
Demand Calculation MethodRead and write
Demand Calculation PeriodminRead and write
Demand Slipping TimeminRead and write
Reactive Power Calculation MethodRead and write
VAR/PF ConventionRead and write
Sealed Parameters SelectionRead and write
Communication Revise AuthorityRead and write
PasswordWrite
New PasswordWrite
Meter Data ResetWrite
Optional Display Symbol 1Read
Optional Display Symbol 2Read
Parameter Measurement SideRead and write
Wiring ModeRead and write
CT2 ValueRead and write
CT1 ValueARead and write
CTN ValueARead and write
PT2 ValueVRead and write
PT1 ValueVRead and write
Energy Pulse ConstantRead and write
Energy Pulse WidthmsRead and write
Energy Display DecimalsRead and write
Relay Operating ModeRead and write
Connection Detection EnableRead and write
Clock YearRead and write
Clock MonthRead and write
Clock DayRead and write
Clock HourRead and write
Clock MinuteRead and write
Clock SecondRead and write
Run TimehRead
Load TimehRead
Alarm SwitchRead and write
Alarm Channel EnableRead and write
Alarm Channel OutputRead and write
Alarm Output ModeRead and write
Alarm Pulse Output TimemsRead and write
Alarm 1 ParameterRead and write
Alarm 1 Compare MethodRead and write
Alarm 1 SetpointRead and write
Alarm 1 DelaymsRead and write
Alarm 2 ParameterRead and write
Alarm 2 Compare MethodRead and write
Alarm 2 SetpointRead and write
Alarm 2 DelaymsRead and write
Alarm 3 ParameterRead and write
Alarm 3 Compare MethodRead and write
Alarm 3 SetpointRead and write
Alarm 3 DelaymsRead and write
Alarm 4 ParameterRead and write
Alarm 4 Compare MethodRead and write
Alarm 4 SetpointRead and write
Alarm 4 DelaymsRead and write
Alarm 5 ParameterRead and write
Alarm 5 Compare MethodRead and write
Alarm 5 SetpointRead and write
Alarm 5 DelaymsRead and write
Alarm 6 ParameterRead and write
Alarm 6 Compare MethodRead and write
Alarm 6 SetpointRead and write
Alarm 6 DelaymsRead and write
Alarm 7 ParameterRead and write
Alarm 7 Compare MethodRead and write
Alarm 7 SetpointRead and write
Alarm 7 DelaymsRead and write
Alarm 8 ParameterRead and write
Alarm 8 Compare MethodRead and write
Alarm 8 SetpointRead and write
Alarm 8 DelaymsRead and write
Alarm 9 ParameterRead and write
Alarm 9 Compare MethodRead and write
Alarm 9 SetpointRead and write
Alarm 9 DelaymsRead and write
Alarm 10 ParameterRead and write
Alarm 10 Compare MethodRead and write
Alarm 10 SetpointRead and write
Alarm 10 DelaymsRead and write
Alarm 11 ParameterRead and write
Alarm 11 Compare MethodRead and write
Alarm 11 SetpointRead and write
Alarm 11 DelaymsRead and write
Alarm 12 ParameterRead and write
Alarm 12 Compare MethodRead and write
Alarm 12 SetpointRead and write
Alarm 12 DelaymsRead and write
Programming CountRead
Latest Programming Time YY-MMRead
Latest Programming Time DD-hhRead
Latest Programming Time mm-ssRead
Latest Programming CodeRead
Previous Programming Time YY-MMRead
Previous Programming Time DD-hhRead
Previous Programming Time mm-ssRead
Previous Programming CodeRead
Third Programming Time YY-MMRead
Third Programming Time DD-hhRead
Third Programming Time mm-ssRead
Third Programming CodeRead
Demand Reset CountRead
Latest Demand Reset Time YY-MMRead
Latest Demand Reset Time DD-hhRead
Latest Demand Reset Time mm-ssRead
Previous Demand Reset Time YY-MMRead
Previous Demand Reset Time DD-hhRead
Previous Demand Reset Time mm-ssRead
Third Demand Reset Time YY-MMRead
Third Demand Reset Time DD-hhRead
Third Demand Reset Time mm-ssRead
Meter Unseal CountRead
Latest Meter Unseal Time YY-MMRead
Latest Meter Unseal Time DD-hhRead
Latest Meter Unseal Time mm-ssRead
Latest Meter Reseal Time YY-MMRead
Latest Meter Reseal Time DD-hhRead
Latest Meter Reseal Time mm-ssRead
Previous Unseal Time YY-MMRead
Previous Unseal Time DD-hhRead
Previous Unseal Time mm-ssRead
Previous Reseal Time YY-MMRead
Previous Reseal Time DD-hhRead
Previous Reseal Time mm-ssRead
Third Unseal Time YY-MMRead
Third Unseal Time DD-hhRead
Third Unseal Time mm-ssRead
Third Reseal Time YY-MMRead
Third Reseal Time DD-hhRead
Third Reseal Time mm-ssRead
Event Reset CountRead
Latest Event Reset Time YY-MMRead
Latest Event Reset Time DD-hhRead
Latest Event Reset Time mm-ssRead
Latest Event Reset CodeRead
Previous Event Reset Time YY-MMRead
Previous Event Reset Time DD-hhRead
Previous Event Reset Time mm-ssRead
Previous Event Reset CodeRead
Third Event Reset Time YY-MMRead
Third Event Reset Time DD-hhRead
Third Event Reset Time mm-ssRead
Third Event Reset CodeRead
Meter Reset CountRead
Latest Meter Reset Time YY-MMRead
Latest Meter Reset Time DD-hhRead
Latest Meter Reset Time mm-ssRead
Previous Meter Reset Time YY-MMRead
Previous Meter Reset Time DD-hhRead
Previous Meter Reset Time mm-ssRead
Third Meter Reset Time YY-MMRead
Third Meter Reset Time DD-hhRead
Third Meter Reset Time mm-ssRead
Relay OutputRead and write
SunSpec SunSpec IdentifierRead
SunSpec Common Model IDRead
SunSpec Common Model LengthRead
SunSpec ManufacturerRead
SunSpec ModelRead
SunSpec OptionsRead
SunSpec VersionRead
SunSpec Serial NumberRead
SunSpec Modbus Device AddressRead and write
SunSpec Meter Model IDRead
SunSpec Meter Model LengthRead
SunSpec Total CurrentARead
SunSpec Phase A CurrentARead
SunSpec Phase B CurrentARead
SunSpec Phase C CurrentARead
SunSpec Current Scale FactorRead
SunSpec Average Phase Voltage (L-N)VRead
SunSpec Phase A Voltage (A-N)VRead
SunSpec Phase B Voltage (B-N)VRead
SunSpec Phase C Voltage (C-N)VRead
SunSpec Average Line Voltage (L-L)VRead
SunSpec Line Voltage ABVRead
SunSpec Line Voltage BCVRead
SunSpec Line Voltage CAVRead
SunSpec Voltage Scale FactorRead
SunSpec FrequencyHzRead
SunSpec Frequency Scale FactorRead
SunSpec Total Active PowerWRead
SunSpec Phase A Active PowerWRead
SunSpec Phase B Active PowerWRead
SunSpec Phase C Active PowerWRead
SunSpec Active Power Scale FactorRead
SunSpec Total Apparent PowerVARead
SunSpec Phase A Apparent PowerVARead
SunSpec Phase B Apparent PowerVARead
SunSpec Phase C Apparent PowerVARead
SunSpec Apparent Power Scale FactorRead
SunSpec Total Reactive PowervarRead
SunSpec Phase A Reactive PowervarRead
SunSpec Phase B Reactive PowervarRead
SunSpec Phase C Reactive PowervarRead
SunSpec Reactive Power Scale FactorRead
SunSpec Total Power FactorRead
SunSpec Phase A Power FactorRead
SunSpec Phase B Power FactorRead
SunSpec Phase C Power FactorRead
SunSpec Power Factor Scale FactorRead
SunSpec Total Active Energy ExportedkWhRead and write
SunSpec Phase A Active Energy ExportedkWhRead and write
SunSpec Phase B Active Energy ExportedkWhRead and write
SunSpec Phase C Active Energy ExportedkWhRead and write
SunSpec Total Active Energy ImportedkWhRead and write
SunSpec Phase A Active Energy ImportedkWhRead and write
SunSpec Phase B Active Energy ImportedkWhRead and write
SunSpec Phase C Active Energy ImportedkWhRead and write
SunSpec Active Energy Scale FactorRead
SunSpec Total Apparent Energy ExportedkVAhRead and write
SunSpec Phase A Apparent Energy ExportedkVAhRead and write
SunSpec Phase B Apparent Energy ExportedkVAhRead and write
SunSpec Phase C Apparent Energy ExportedkVAhRead and write
SunSpec Total Apparent Energy ImportedkVAhRead and write
SunSpec Phase A Apparent Energy ImportedkVAhRead and write
SunSpec Phase B Apparent Energy ImportedkVAhRead and write
SunSpec Phase C Apparent Energy ImportedkVAhRead and write
SunSpec Apparent Energy Scale FactorRead
SunSpec Total Reactive Energy Imported Q1kvarhRead and write
SunSpec Phase A Reactive Energy Imported Q1kvarhRead and write
SunSpec Phase B Reactive Energy Imported Q1kvarhRead and write
SunSpec Phase C Reactive Energy Imported Q1kvarhRead and write
SunSpec Total Reactive Energy Imported Q2kvarhRead and write
SunSpec Phase A Reactive Energy Imported Q2kvarhRead and write
SunSpec Phase B Reactive Energy Imported Q2kvarhRead and write
SunSpec Phase C Reactive Energy Imported Q2kvarhRead and write
SunSpec Total Reactive Energy Exported Q3kvarhRead and write
SunSpec Phase A Reactive Energy Exported Q3kvarhRead and write
SunSpec Phase B Reactive Energy Exported Q3kvarhRead and write
SunSpec Phase C Reactive Energy Exported Q3kvarhRead and write
SunSpec Total Reactive Energy Exported Q4kvarhRead and write
SunSpec Phase A Reactive Energy Exported Q4kvarhRead and write
SunSpec Phase B Reactive Energy Exported Q4kvarhRead and write
SunSpec Phase C Reactive Energy Exported Q4kvarhRead and write
SunSpec Reactive Energy Scale FactorRead
SunSpec Meter Event FlagsRead
SunSpec End Model IDRead
SunSpec End Model LengthRead
SunSpec 50000 SunSpec IdentifierRead
SunSpec 50000 Common Model IDRead
SunSpec 50000 Common Model LengthRead
SunSpec 50000 ManufacturerRead
SunSpec 50000 ModelRead
SunSpec 50000 OptionsRead
SunSpec 50000 VersionRead
SunSpec 50000 Serial NumberRead
SunSpec 50000 Modbus Device AddressRead and write
SunSpec 50000 Meter Model IDRead
SunSpec 50000 Meter Model LengthRead
SunSpec 50000 Total CurrentARead
SunSpec 50000 Phase A CurrentARead
SunSpec 50000 Phase B CurrentARead
SunSpec 50000 Phase C CurrentARead
SunSpec 50000 Current Scale FactorRead
SunSpec 50000 Average Phase Voltage (L-N)VRead
SunSpec 50000 Phase A Voltage (A-N)VRead
SunSpec 50000 Phase B Voltage (B-N)VRead
SunSpec 50000 Phase C Voltage (C-N)VRead
SunSpec 50000 Average Line Voltage (L-L)VRead
SunSpec 50000 Line Voltage ABVRead
SunSpec 50000 Line Voltage BCVRead
SunSpec 50000 Line Voltage CAVRead
SunSpec 50000 Voltage Scale FactorRead
SunSpec 50000 FrequencyHzRead
SunSpec 50000 Frequency Scale FactorRead
SunSpec 50000 Total Active PowerWRead
SunSpec 50000 Phase A Active PowerWRead
SunSpec 50000 Phase B Active PowerWRead
SunSpec 50000 Phase C Active PowerWRead
SunSpec 50000 Active Power Scale FactorRead
SunSpec 50000 Total Apparent PowerVARead
SunSpec 50000 Phase A Apparent PowerVARead
SunSpec 50000 Phase B Apparent PowerVARead
SunSpec 50000 Phase C Apparent PowerVARead
SunSpec 50000 Apparent Power Scale FactorRead
SunSpec 50000 Total Reactive PowervarRead
SunSpec 50000 Phase A Reactive PowervarRead
SunSpec 50000 Phase B Reactive PowervarRead
SunSpec 50000 Phase C Reactive PowervarRead
SunSpec 50000 Reactive Power Scale FactorRead
SunSpec 50000 Total Power FactorRead
SunSpec 50000 Phase A Power FactorRead
SunSpec 50000 Phase B Power FactorRead
SunSpec 50000 Phase C Power FactorRead
SunSpec 50000 Power Factor Scale FactorRead
SunSpec 50000 Total Active Energy ExportedWhRead and write
SunSpec 50000 Phase A Active Energy ExportedWhRead and write
SunSpec 50000 Phase B Active Energy ExportedWhRead and write
SunSpec 50000 Phase C Active Energy ExportedWhRead and write
SunSpec 50000 Total Active Energy ImportedWhRead and write
SunSpec 50000 Phase A Active Energy ImportedWhRead and write
SunSpec 50000 Phase B Active Energy ImportedWhRead and write
SunSpec 50000 Phase C Active Energy ImportedWhRead and write
SunSpec 50000 Active Energy Scale FactorRead
SunSpec 50000 Total Apparent Energy ExportedVAhRead and write
SunSpec 50000 Phase A Apparent Energy ExportedVAhRead and write
SunSpec 50000 Phase B Apparent Energy ExportedVAhRead and write
SunSpec 50000 Phase C Apparent Energy ExportedVAhRead and write
SunSpec 50000 Total Apparent Energy ImportedVAhRead and write
SunSpec 50000 Phase A Apparent Energy ImportedVAhRead and write
SunSpec 50000 Phase B Apparent Energy ImportedVAhRead and write
SunSpec 50000 Phase C Apparent Energy ImportedVAhRead and write
SunSpec 50000 Apparent Energy Scale FactorRead
SunSpec 50000 Total Reactive Energy Imported Q1varhRead and write
SunSpec 50000 Phase A Reactive Energy Imported Q1varhRead and write
SunSpec 50000 Phase B Reactive Energy Imported Q1varhRead and write
SunSpec 50000 Phase C Reactive Energy Imported Q1varhRead and write
SunSpec 50000 Total Reactive Energy Imported Q2varhRead and write
SunSpec 50000 Phase A Reactive Energy Imported Q2varhRead and write
SunSpec 50000 Phase B Reactive Energy Imported Q2varhRead and write
SunSpec 50000 Phase C Reactive Energy Imported Q2varhRead and write
SunSpec 50000 Total Reactive Energy Exported Q3varhRead and write
SunSpec 50000 Phase A Reactive Energy Exported Q3varhRead and write
SunSpec 50000 Phase B Reactive Energy Exported Q3varhRead and write
SunSpec 50000 Phase C Reactive Energy Exported Q3varhRead and write
SunSpec 50000 Total Reactive Energy Exported Q4varhRead and write
SunSpec 50000 Phase A Reactive Energy Exported Q4varhRead and write
SunSpec 50000 Phase B Reactive Energy Exported Q4varhRead and write
SunSpec 50000 Phase C Reactive Energy Exported Q4varhRead and write
SunSpec 50000 Reactive Energy Scale FactorRead
SunSpec 50000 Meter Event FlagsRead
SunSpec 50000 End Model IDRead
SunSpec 50000 End Model LengthRead

Loading registers…

The ModbusCloud Gateway, front at an angle, with the RS485 terminal and the antenna connectors

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show per-tenant energy use on a dashboard with imported energy per phase and per tariff.
  • Get an alert when a phase current or the total active power passes a threshold you set.
  • Compare this month's peak demand with last month to spot new loads before the utility bill does.
  • Keep a year of voltage, current and power factor history to back up a complaint about supply quality.
  • Switch the relay output from ModbusCloud to shed a load or reset an external alarm.

Installation

  1. Wire RS485 A, B and S of the meter to the RS485 port of the ModbusCloud Gateway. Daisy chain only and put a 120 to 300 ohm resistor at the last device.

  2. On the meter or with the Accuenergy utility software, set address, baud rate and parity. The default is address 1, 19200 baud, no parity, 1 stop bit.

  3. Set the wiring mode and the CT and PT ratio to match the installation.

  4. In ModbusCloud, add a Modbus device (RTU) with the same address and serial settings and import this template.

  5. Check that Frequency reads about 50 Hz and that Phase A Voltage matches the voltage you measure.

Things to watch for

The meter does not answer on the RS485 bus. What should I check?

Check address and serial settings first: the default is 19200 baud, no parity and 1 stop bit, and many tools default to even parity. Then swap A and B, check the shield on one side only, and make sure the meter is set to Modbus RTU and not BACnet MS/TP, as both share the same RS485 port.

Why do my energy values look ten or a hundred times too small or too large?

Compare one energy register with the meter display. The energy decimal setting in 21AH changes how energy is shown. If the values differ by a fixed factor, adjust the scale of the energy registers in the portal to match the display.

Why does the meter ignore what I write to a setting or a counter?

Settings and counters only accept writes after you write the password to 20BH and set the communication revise authority in 20AH. A sealed meter (Seal Status 0x0A) also refuses changes to locked settings. The meter only accepts multi-register writes, so writes must use function code 16.

The peak demand time shows strange numbers. How do I read it?

Each time stamp is three registers with two bytes each: year and month, day and hour, minute and second. A value of 6667 in the first register is 0x1A0B, so year 26 (2026) and month 11.

Can I connect several AcuRev meters to one Gateway?

Yes. Give each meter its own address between 1 and 247, use the same baud rate and parity on all of them, and add each meter in ModbusCloud as a separate Modbus device with this template.

Want to see how it works?