Brink Flair

Controls Brink Flair ventilation units via CO2-based airflow regulation over Modbus.

Template for Brink Flair 225-600 heat recovery ventilation units over Modbus RTU. Reads sensor data such as temperatures, humidity, CO2 levels, fan speeds, and pressures. Writes airflow presets, CO2 thresholds, bypass settings, and postheater setpoints for CO2-based airflow regulation.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
150, read and write
Brand
Brink
Key readings
Supply and exhaust airflow (m3/h) · Supply and exhaust fan speed (RPM) · Temperature sensors (NTC1, NTC2, exhaust) · CO2 sensor values (1-4) · Relative humidity (inlet, exhaust, RHT) · Supply and exhaust pressure (Pa)
Available commands
Flow presets 0-3 · CO2 sensor low/high levels · Bypass mode and temperature settings · Postheater setpoint
Compatible models
BRINK Flair 225 · BRINK Flair 325 · BRINK Flair 400 · BRINK Flair 450 · BRINK Flair 600
Last updated

Registers (150)

150 read, 67 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Software version number 0Read
Appliance TypeRead
Dipswitch valueRead
Serial number 0Read
Serial number 1Read
Serial number 2Read
HRA (Heat Recovery Appliance) Active FunctionRead
Fan control typeRead
Ventilation modeRead
Hardware versionRead
Software version number 2Read
Temperature sensor exhaust fan°CRead
Software version number 1Read
Current supply pressurePaRead
Current exhaust pressurePaRead
Fan Inlet StatusRead
Setpoint supply airm³/hRead
Current value of supplyairm³/hRead
Speed supply fanrpmRead
Temperature sensorsupply fan°CRead
Fan inlet sensor rel.humidity%Read
Fan exhaust StatusRead
Setpoint flow exhaust airm³/hRead
current value flowexhaust airm³/hRead
MassFlow exhaust,actual valuekg/hRead
Speed exhaust fanrpmRead
Fan exhaust sensor rel.humidity%Read
Bypass statusRead
Status preheaterRead
Capacity of preheater%Read
Frost statusRead
Frost heaterpower%Read
Flow switch positionRead
NTC1 temperature°CRead
NTC2 temperature°CRead
RHT Sensor Humidity%Read
Signal output StatusRead
Status filterRead
eBus power statusRead
Current timeRead
Current dateRead
Operating timeRead
Filters used in daysRead
Filters used in m3/hm³Read
Total flow in m3/hm³Read
Geo heat exchangerStatusRead
CO2 sensor 1 statusRead
Value CO2 sensor 1ppmRead
CO2 sensor 2 statusRead
Value CO2 sensor 2ppmRead
CO2 sensor 3 statusRead
Value CO2 sensor 3ppmRead
CO2 sensor 4 statusRead
Value CO2 sensor 4ppmRead
Software version numberUIF Module(e.g. "S1.01.03.0001")Read
Software version numberUIF Module(e.g. "S1.01.03.0001")Read
Software version numberUIF Module(e.g. "S1.01.03.0001")Read
Hardware versionnumber UIF Module (e.g."H1.1")Read
Device TypeRead
Dipswitch valueRead
Language Data versionUIF Module (e.g."S1.01.03.0001")Read
Language Data versionUIF Module (e.g."S1.01.03.0001")Read
Language Data versionUIF Module (e.g."S1.01.03.0001")Read
Software version nr UIFModule (e.g."S1.01.03.0001")Read
Software version nr UIFModule (e.g."S1.01.03.0001")Read
Software version nr UIFModule (e.g."S1.01.03.0001")Read
Local UIF SwitchRead
Local Button valueRead
Software version nExtension ModuleUWA2-E (e.g."S1.01.03.0001")Read
Software version nExtension ModuleUWA2-E (e.g."S1.01.03.0001")Read
Software version nExtension ModuleUWA2-E (e.g."S1.01.03.0001")Read
Hardware version nrExtension ModuleUWA2-E (e.g. "H1.1")Read
Device TypeRead
Temperature NTC Extension°CRead
Extension contact 1Read
Extension contact 2Read
Extension AnalogueInput 1VRead
Extension AnalogueInput 2VRead
Extension Relay output 1Read
Dipswitch valueRead
Extension Relay output 2Read
Extension Analogue Output 1VRead
Extension Analogue Output 2VRead
Flow preset 0Read and write
Flow preset 1Read and write
Flow preset 2Read and write
Flow preset 3Read and write
Switch default positionRead and write
Use display as switchRead and write
Imbalans allowedRead and write
Imbalance valueRead and write
Offset imbalance supply%Read and write
Offset imbalance exhaust%Read and write
Bypass modeRead and write
Bypass temperature fromdwelling°CRead and write
Bypass temperature from outside°CRead and write
Bypass temperature hysteresis°CRead and write
Bypass boostRead and write
Bypass boost switch positionRead and write
Frost control minimum inlet temperature°CRead and write
Days before filter warningRead and write
External heater modeRead and write
Postheater setpoint°CRead and write
RHT (humidity) sensor modeRead and write
RHT (humidity) sensor sensitivityRead and write
CO2 sensor modeRead and write
CO2 sensor 1 low levelppmRead and write
CO2 sensor 1 high levelppmRead and write
CO2 sensor 2 low levelppmRead and write
CO2 sensor 4 high levelppmRead and write
CO2 sensor 2 high levelppmRead and write
CO2 sensor 3 low levelppmRead and write
CO2 sensor 3 high levelppmRead and write
CO2 sensor 4 low levelppmRead and write
Signal output SettingRead and write
Switch type Input 1Read and write
Digital Input 1 functionRead and write
Digital input 1 supply fan functionRead and write
Digital Input 1 exhaust fan functionRead and write
Switch type Input 2Read and write
Digital input 2 functionRead and write
Digital input 2 supply fan functionRead and write
Digital input 2 exhaust fan functionRead and write
Analogue input 2 ModeRead and write
Analogue Input 1 ModeRead and write
Analogue input 1 VminVRead and write
Analogue input 1 VmaxVRead and write
Analogue input 2 VminVRead and write
Analogue input 2 VmaxVRead and write
Geo-heat exchangerRead and write
Minimum temperature geo-heat exchanger°CRead and write
Maximum temperaturegeo-heat exchanger°CRead and write
Default geo heatexchanger Valve PositionRead and write
Geo heat exchangervalve outputRead and write
LanguageRead and write
Date formatRead and write
Time notationRead and write
Date Month DayRead and write
Date YearRead and write
TimeRead and write
DateTime RestRead and write
Modbus interface typeRead and write
Modbus slave addressRead and write
Modbus speedRead and write
Modbus control switched onRead and write
Request change in switch positionRead and write
Desired flow rate settingRead and write
Request StandbyRead and write
Reset filter warningRead and write
Appliance resetRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor CO2 levels and airflow rates on a live dashboard to verify adequate ventilation in each zone.
  • Create an alert when CO2 concentration exceeds the Max PPM threshold for more than 15 minutes.
  • Remotely adjust Q Min and Q Max airflow setpoints to match seasonal occupancy patterns.
  • Log supply and exhaust temperatures to verify heat recovery efficiency over time.
  • Set up notifications when exhaust humidity rises above a defined limit, indicating potential moisture problems.
  • Compare fan speed and pressure data across multiple Brink Flair units in a multi-dwelling project.

Installation

  1. Connect the ModbusCloud Gateway to the Brink Flair unit via the RS-485 terminals on the UWA2-B or UWA2-E Modbus interface module.

  2. Configure the Modbus RTU settings on the gateway to 19200 baud, even parity, and set the correct slave address matching the unit.

  3. On the Brink Flair unit, ensure register 8000 is set to 2 to enable CO2-based flow control, and verify register 8002 is configured for flow control mode.

  4. Set the position switch on the ventilation unit to position 1 so that CO2 regulation is active.

  5. Import the Brink Flair template in the ModbusCloud portal and assign it to the connected gateway.

  6. Verify live data appears on the dashboard by checking that airflow, temperature, and CO2 readings update correctly.

Things to watch for

CO2-based airflow control is not responding. What should I check?

Verify that register 8000 is set to 2 and the physical position switch on the unit is set to position 1. CO2 control does not operate when the switch is at position 0 or the fan symbol (absent mode).

What baud rate and parity settings does the Brink Flair require?

The Brink Flair uses 19200 baud with even parity (parity setting 1). Ensure these match exactly on your ModbusCloud gateway, as mismatched settings will prevent communication.

Can I read and write Q Min, Q Max, and PPM thresholds?

Yes. Registers 6001 (Q Min), 6003 (Q Max), 6151 (Min PPM), and 6152 (Max PPM) are all readable and writable. Changes take effect immediately on the unit.

Which Modbus interface module do I need on the Brink Flair?

You need the Brink UWA2-B or UWA2-E Modbus interface module installed on the ventilation unit. Refer to the corresponding Brink Modbus manual for wiring and addressing details.

Want to see how it works?