Eaton Eaton Power Defense PXR Modbus RTU template

Eaton Power Defense PXR

Breaker trip unit that reports status, currents, voltages, power and energy of a Power Defense breaker.

The Eaton Power Defense PXR is the electronic trip unit of Power Defense molded case circuit breakers that protects the circuit and measures current, voltage, power and energy in the switchboard. This Modbus RTU template reads breaker status, loads, energy, counters and the event log, and lets you change relay, demand, clock and Modbus settings from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 19200 baud
Registers
393, read and write
Brand
Eaton
Key readings
Breaker status · Phase currents · Line voltages · Active power · Energy · Power factor · Trip counters · Breaker health
Available commands
Remote control commands · Relay functions · Power demand interval · Clock · Modbus settings
Compatible models
PXR 20 · PXR 20D · PXR 25 · PXR 25 Motor Protection · Power Defense frames 2 to 6 (PDG2 to PDG6) with integrated Modbus RTU
Last updated

Registers (393)

392 read, 40 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Breaker StatusRead
Cause Of StatusRead
Current Phase AARead
Current Phase BARead
Current Phase CARead
Ground CurrentARead
Neutral CurrentARead
Voltage A-BVRead
Voltage B-CVRead
Voltage C-AVRead
Voltage A-NVRead
Voltage B-NVRead
Voltage C-NVRead
Peak Demand Current Phase AARead
Peak Demand Current Phase BARead
Peak Demand Current Phase CARead
Peak Demand Neutral CurrentARead
Active Power TotalWRead
Reactive Power TotalvarRead
Apparent Power TotalVARead
Power FactorRead
FrequencyHzRead
Minimum Demand Current Phase AARead
Minimum Demand Current Phase BARead
Minimum Demand Current Phase CARead
Minimum Demand Neutral CurrentARead
Active Power Peak DemandWRead
Product IDRead
Frequency FineHzRead
Trip Unit Temperature°CRead
Reactive Power Peak DemandvarRead
Apparent Power Peak DemandVARead
Demand Current Phase AARead
Demand Current Phase BARead
Demand Current Phase CARead
Demand Neutral CurrentARead
Active Power DemandWRead
Reactive Power DemandvarRead
Apparent Power DemandVARead
Minimum Current Phase AARead
Maximum Current Phase AARead
Minimum Current Phase BARead
Maximum Current Phase BARead
Minimum Current Phase CARead
Maximum Current Phase CARead
Minimum Ground CurrentARead
Maximum Ground CurrentARead
Minimum Neutral CurrentARead
Maximum Neutral CurrentARead
Minimum Voltage A-BVRead
Maximum Voltage A-BVRead
Minimum Voltage B-CVRead
Maximum Voltage B-CVRead
Minimum Voltage C-AVRead
Maximum Voltage C-AVRead
Minimum Voltage A-NVRead
Maximum Voltage A-NVRead
Minimum Voltage B-NVRead
Maximum Voltage B-NVRead
Minimum Voltage C-NVRead
Maximum Voltage C-NVRead
Current Unbalance%Read
Voltage Unbalance%Read
Current Phase A THD%Read
Current Phase B THD%Read
Current Phase C THD%Read
Neutral Current THD%Read
Voltage A-B THD%Read
Voltage B-C THD%Read
Voltage C-A THD%Read
Voltage A-N THD%Read
Voltage B-N THD%Read
Voltage C-N THD%Read
Inst, Short Delay And High Inst CountRead
Long Delay And Ground Fault Trip CountRead
Operations CountRead
Short Delay Trip CountRead
Instantaneous Trip CountRead
High Current Trip CountRead
Long Delay Trip CountRead
Ground Fault Trip CountRead
Total Trip CountRead
Test Trip CountRead
Open By Communication CountRead
Manual Open CountRead
Last Operation YearRead
Last Operation MonthRead
Last Operation DayRead
Last Operation HourRead
Last Operation MinuteRead
Last Operation SecondRead
Maximum Trip Unit Temperature°CRead
Maximum Temperature YearRead
Maximum Temperature MonthRead
Maximum Temperature DayRead
Maximum Temperature HourRead
Maximum Temperature MinuteRead
Maximum Temperature SecondRead
Running Time MinutesRead
Running Time HoursRead
Running Time DaysRead
Breaker HealthRead
Harmonics SourceRead
Harmonic 0%Read
Harmonic 1%Read
Harmonic 2%Read
Harmonic 3%Read
Harmonic 4%Read
Harmonic 5%Read
Harmonic 6%Read
Harmonic 7%Read
Harmonic 8%Read
Harmonic 9%Read
Harmonic 10%Read
Harmonic 11%Read
Harmonic 12%Read
Harmonic 13%Read
Harmonic 14%Read
Harmonic 15%Read
Harmonic 16%Read
Harmonic 17%Read
Harmonic 18%Read
Harmonic 19%Read
Harmonic 20%Read
Harmonic 21%Read
Harmonic 22%Read
Harmonic 23%Read
Harmonic 24%Read
Harmonic 25%Read
Harmonic 26%Read
Harmonic 27%Read
Harmonic 28%Read
Harmonic 29%Read
Harmonic 30%Read
Harmonic 31%Read
Harmonic 32%Read
Harmonic 33%Read
Harmonic 34%Read
Breaker ClosedRead
Unacknowledged TripRead
Active Or Unacknowledged AlarmRead
Maintenance Mode ActiveRead
Test Mode ActiveRead
Long Delay Pickup ActiveRead
Zone Interlock ActiveRead
Ground Is Source GroundRead
Setpoint PasswordWrite
Setpoint Group SelectRead and write
Breaker RatingARead
Breaker FrameRead
Style 1Read
Style 2Read
Maintenance ModeRead and write
ARMS LevelRead and write
System FrequencyHzRead
Reverse FeedRead and write
Sign ConventionRead and write
Power Demand WindowRead and write
Power Demand IntervalminRead and write
Display LanguageRead and write
Display RotationRead and write
Relay 1 FunctionRead and write
Relay 2 FunctionRead and write
Relay 3 FunctionRead and write
Pole Location Phase ARead and write
Modbus Slave IDRead and write
Modbus Baud RateRead and write
Modbus ParityRead and write
Modbus Stop BitsRead and write
Invalid Object Access ModeRead and write
Float Word OrderRead and write
Fixed Point Word OrderRead and write
Invalid Object Access Mode (High Address)Read and write
Float Word Order (High Address)Read and write
Fixed Point Word Order (High Address)Read and write
Remote Control Word 1Read and write
Remote Control Word 2Read and write
Remote Control Word 3Read and write
Remote Control Word 1 (High Address)Read and write
Remote Control Word 2 (High Address)Read and write
Remote Control Word 3 (High Address)Read and write
Clock MonthRead and write
Clock DayRead and write
Clock YearRead and write
Clock Day Of WeekRead and write
Clock HourRead and write
Clock MinuteRead and write
Clock SecondRead and write
Clock Hundredths Of SecondRead and write
Device NameRead
Model NameRead
Catalog NumberRead
Style NumberRead
Serial NumberRead
Date CodeRead
Firmware Version 1Read
Firmware Version 2Read
USB VersionRead
Product ID Fixed DataRead
Breaker Status (Fixed Point)Read
Cause Of Status (Fixed Point)Read
Current Phase A (Fixed Point)ARead
Current Phase B (Fixed Point)ARead
Current Phase C (Fixed Point)ARead
Ground Current (Fixed Point)ARead
Neutral Current (Fixed Point)ARead
Voltage A-B (Fixed Point)VRead
Voltage B-C (Fixed Point)VRead
Voltage C-A (Fixed Point)VRead
Voltage A-N (Fixed Point)VRead
Voltage B-N (Fixed Point)VRead
Voltage C-N (Fixed Point)VRead
Peak Demand Current Phase A (Fixed Point)ARead
Peak Demand Current Phase B (Fixed Point)ARead
Peak Demand Current Phase C (Fixed Point)ARead
Peak Demand Neutral Current (Fixed Point)ARead
Active Power Total (Fixed Point)WRead
Reactive Power Total (Fixed Point)varRead
Apparent Power Total (Fixed Point)VARead
Power Factor (Fixed Point)Read
Frequency (Fixed Point)HzRead
Minimum Demand Current Phase A (Fixed Point)ARead
Minimum Demand Current Phase B (Fixed Point)ARead
Minimum Demand Current Phase C (Fixed Point)ARead
Minimum Demand Neutral Current (Fixed Point)ARead
Active Power Peak Demand (Fixed Point)WRead
Frequency Fine (Fixed Point)HzRead
Forward EnergykWhRead
Reverse EnergykWhRead
Total EnergykWhRead
Apparent EnergykVAhRead
Trip Unit Temperature (Fixed Point)°CRead
Reactive Power Peak Demand (Fixed Point)varRead
Apparent Power Peak Demand (Fixed Point)VARead
Demand Current Phase A (Fixed Point)ARead
Demand Current Phase B (Fixed Point)ARead
Demand Current Phase C (Fixed Point)ARead
Demand Neutral Current (Fixed Point)ARead
Active Power Demand (Fixed Point)WRead
Reactive Power Demand (Fixed Point)varRead
Apparent Power Demand (Fixed Point)VARead
Minimum Current Phase A (Fixed Point)ARead
Maximum Current Phase A (Fixed Point)ARead
Minimum Current Phase B (Fixed Point)ARead
Maximum Current Phase B (Fixed Point)ARead
Minimum Current Phase C (Fixed Point)ARead
Maximum Current Phase C (Fixed Point)ARead
Minimum Ground Current (Fixed Point)ARead
Maximum Ground Current (Fixed Point)ARead
Minimum Neutral Current (Fixed Point)ARead
Maximum Neutral Current (Fixed Point)ARead
Minimum Voltage A-B (Fixed Point)VRead
Maximum Voltage A-B (Fixed Point)VRead
Minimum Voltage B-C (Fixed Point)VRead
Maximum Voltage B-C (Fixed Point)VRead
Minimum Voltage C-A (Fixed Point)VRead
Maximum Voltage C-A (Fixed Point)VRead
Minimum Voltage A-N (Fixed Point)VRead
Maximum Voltage A-N (Fixed Point)VRead
Minimum Voltage B-N (Fixed Point)VRead
Maximum Voltage B-N (Fixed Point)VRead
Minimum Voltage C-N (Fixed Point)VRead
Maximum Voltage C-N (Fixed Point)VRead
Current Unbalance (Fixed Point)%Read
Voltage Unbalance (Fixed Point)%Read
Current Phase A THD (Fixed Point)%Read
Current Phase B THD (Fixed Point)%Read
Current Phase C THD (Fixed Point)%Read
Neutral Current THD (Fixed Point)%Read
Voltage A-B THD (Fixed Point)%Read
Voltage B-C THD (Fixed Point)%Read
Voltage C-A THD (Fixed Point)%Read
Voltage A-N THD (Fixed Point)%Read
Voltage B-N THD (Fixed Point)%Read
Voltage C-N THD (Fixed Point)%Read
Inst, Short Delay And High Inst Count (Fixed Point)Read
Long Delay And Ground Fault Trip Count (Fixed Point)Read
Operations Count (Fixed Point)Read
Short Delay Trip Count (Fixed Point)Read
Instantaneous Trip Count (Fixed Point)Read
High Current Trip Count (Fixed Point)Read
Long Delay Trip Count (Fixed Point)Read
Ground Fault Trip Count (Fixed Point)Read
Total Trip Count (Fixed Point)Read
Test Trip Count (Fixed Point)Read
Open By Communication Count (Fixed Point)Read
Manual Open Count (Fixed Point)Read
Last Operation Year (Fixed Point)Read
Last Operation Month (Fixed Point)Read
Last Operation Day (Fixed Point)Read
Last Operation Hour (Fixed Point)Read
Last Operation Minute (Fixed Point)Read
Last Operation Second (Fixed Point)Read
Maximum Trip Unit Temperature (Fixed Point)°CRead
Maximum Temperature Year (Fixed Point)Read
Maximum Temperature Month (Fixed Point)Read
Maximum Temperature Day (Fixed Point)Read
Maximum Temperature Hour (Fixed Point)Read
Maximum Temperature Minute (Fixed Point)Read
Maximum Temperature Second (Fixed Point)Read
Running Time Minutes (Fixed Point)Read
Running Time Hours (Fixed Point)Read
Running Time Days (Fixed Point)Read
Breaker Health (Fixed Point)Read
Harmonics Source (Fixed Point)Read
Harmonic 0 (Fixed Point)%Read
Harmonic 1 (Fixed Point)%Read
Harmonic 2 (Fixed Point)%Read
Harmonic 3 (Fixed Point)%Read
Harmonic 4 (Fixed Point)%Read
Harmonic 5 (Fixed Point)%Read
Harmonic 6 (Fixed Point)%Read
Harmonic 7 (Fixed Point)%Read
Harmonic 8 (Fixed Point)%Read
Harmonic 9 (Fixed Point)%Read
Harmonic 10 (Fixed Point)%Read
Harmonic 11 (Fixed Point)%Read
Harmonic 12 (Fixed Point)%Read
Harmonic 13 (Fixed Point)%Read
Harmonic 14 (Fixed Point)%Read
Harmonic 15 (Fixed Point)%Read
Harmonic 16 (Fixed Point)%Read
Harmonic 17 (Fixed Point)%Read
Harmonic 18 (Fixed Point)%Read
Harmonic 19 (Fixed Point)%Read
Harmonic 20 (Fixed Point)%Read
Harmonic 21 (Fixed Point)%Read
Harmonic 22 (Fixed Point)%Read
Harmonic 23 (Fixed Point)%Read
Harmonic 24 (Fixed Point)%Read
Harmonic 25 (Fixed Point)%Read
Harmonic 26 (Fixed Point)%Read
Harmonic 27 (Fixed Point)%Read
Harmonic 28 (Fixed Point)%Read
Harmonic 29 (Fixed Point)%Read
Harmonic 30 (Fixed Point)%Read
Harmonic 31 (Fixed Point)%Read
Harmonic 32 (Fixed Point)%Read
Harmonic 33 (Fixed Point)%Read
Harmonic 34 (Fixed Point)%Read
Forward Energy WhWhRead
Reverse Energy WhWhRead
Total Energy WhWhRead
Apparent Energy VAhVAhRead
Event Type SelectRead and write
Earliest Event IDRead
Latest Event IDRead
Requested Event IDRead and write
Previous Event IDRead
Next Event IDRead
Event MonthRead
Event DayRead
Event YearRead
Event Day Of WeekRead
Event HourRead
Event MinuteRead
Event SecondRead
Event Hundredths Of SecondRead
Event Data FormatRead
Event Validity Bits LowRead
Event Validity Bits High Or CauseRead
Event Status CauseRead
Event Current Phase AARead
Event Current Phase BARead
Event Current Phase CARead
Event Neutral CurrentARead
Event Ground Current SourceARead
Event Ground Current ResidualARead
Event Voltage A-BVRead
Event Voltage B-CVRead
Event Voltage C-AVRead
Event Voltage A-NVRead
Event Voltage B-NVRead
Event Voltage C-NVRead
Event Active PowerWRead
Event Reactive PowervarRead
Event Apparent PowerVARead
Event Active Power DemandWRead
Event Reactive Power DemandvarRead
Event Apparent Power DemandVARead
Event Trip Unit Temperature°CRead
Event FrequencyHzRead
Event Power FactorRead
Event Operations CountRead
Event Binary StatusRead
Breaker Closed ValidRead
Unacknowledged Trip ValidRead
Active Or Unacknowledged Alarm ValidRead
Maintenance Mode Active ValidRead
Test Mode Active ValidRead
Long Delay Pickup Active ValidRead
Zone Interlock Active ValidRead
Ground Is Source Ground ValidRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Use cases

  • Show the status and phase currents of every outgoing breaker in a switchboard on one ModbusCloud dashboard.
  • Send an email alert when a breaker trips or when the cause of status changes away from normal.
  • Track energy and peak demand per feeder over the 365 days of history to see which group uses the most.
  • Watch phase current unbalance and THD to find overloaded or polluted circuits before they cause trouble.
  • Follow trip and operation counters and the breaker health value to plan maintenance of the breaker.

Installation

  1. Check that the PXR style has integrated Modbus RTU and that the trip unit gets 24 V DC auxiliary power.

  2. Wire RTU_D(+) and RTU_D(-) as a shielded twisted pair to RS485 A and B of the ModbusCloud Gateway, connect RTU_GND and put 120 ohm termination at both ends of the bus.

  3. Set the Modbus address, baud rate and parity on the trip unit display or with Power Xpert Protection Manager; the default is address 2, 19200 baud, even parity.

  4. In ModbusCloud, add a Modbus device on the Gateway with the same address and settings and import this template.

  5. Check that breaker status, phase currents and frequency come in and match the trip unit display.

Things to watch for

The breaker does not answer on Modbus at all. What should I check?

Integrated Modbus only works with 24 V DC auxiliary power on the trip unit and only on styles with Modbus. Then check address, baud rate and parity on the display (default 2, 19200, even), swap RTU_D(+) and RTU_D(-) if needed and make sure the bus is terminated at both ends.

Why do currents and power show huge or random numbers?

The trip unit sends 32-bit values low word first by default, which this template expects. If someone changed the float or fixed point word order registers to high word first, set them back or the values will be scrambled.

Why do some registers stay empty or return an error?

Not every PXR model measures everything: voltage, power, demand and harmonics need a PXR 25 or a style with voltage sensing, and ground current only exists on units with ground fault protection. Unused registers return an error or an invalid value on those models.

Can I change settings or reset the breaker from ModbusCloud?

Display, relay, demand, clock and Modbus settings can be written; the settings registers show group 0 by default. Writing setpoints needs the password first. Remote control commands such as reset trip use three words that the trip unit only accepts together in one write, so test each command carefully before you rely on it.

Want to see how it works?