Eaton Eaton PowerXL DC1 Modbus RTU template

Eaton PowerXL DC1

Compact frequency inverter with speed control, motor values and drive parameters.

The Eaton PowerXL DC1 is a compact frequency inverter that controls the speed of three phase motors in pumps, fans and conveyors. This Modbus RTU template reads status, faults, frequency, current, torque, power, DC link voltage and temperatures, and lets you write the command word, speed reference, ramp time and drive parameters from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 9600 baud
Registers
100, read and write
Brand
Eaton
Key readings
Output frequency · Motor current · Motor torque · Output power · DC link voltage · Heatsink temperature · Fault number
Available commands
Command word · Speed reference · Ramp time · Drive parameters
Compatible models
PowerXL DC1 (DC1-1D, DC1-12, DC1-32, DC1-34)
Last updated

Registers (100)

100 read, 72 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Status and Fault WordRead
Actual SpeedHzRead
Motor CurrentARead
Motor Torque%Read
Output PowerkWRead
DC Link VoltageVRead
Heatsink Temperature°CRead
Control Board Temperature°CRead
Motor VoltageRead
Analog Input 1%Read
Analog Input 2%Read
Digital InputsRead
Run Time HourshRead
Run Time Min SecRead
Hours Run Enable HourshRead
Hours Run Enable Min SecRead
Scope Channel 1Read
Scope Channel 2Read
Fieldbus CommandRead and write
Speed ReferenceHzRead and write
Modbus Ramp TimesRead and write
Drive Type CodeRead
Drive PowerRead
Voltage RangeVRead
Control Software VersionRead
Power Software VersionRead
Drive RecognitionRead
Serial Number 4Read
Serial Number 3Read
Serial Number 2Read
Serial Number 1Read
Maximum FrequencyHzRead and write
Minimum FrequencyHzRead and write
Acceleration TimesRead and write
Deceleration TimesRead and write
Stop ModeRead and write
Energy OptimizerRead and write
Motor Nominal VoltageVRead and write
Motor Nominal CurrentARead and write
Motor Nominal FrequencyHzRead and write
Motor Nominal SpeedrpmRead and write
Voltage Boost%Read and write
Control SourceRead and write
Application Mode MacroRead and write
PasswordRead and write
Digital Input ConfigurationRead and write
AI1 Signal RangeRead and write
Switching FrequencyRead and write
Relay Output 1 FunctionRead and write
Relay Output 1 Upper Limit%Read and write
Fixed Frequency 1HzRead and write
Fixed Frequency 2HzRead and write
Fixed Frequency 3HzRead and write
Fixed Frequency 4HzRead and write
Quick Deceleration TimesRead and write
Analog Output 1 FunctionRead and write
Skip Band 1HzRead and write
Skip Frequency 1HzRead and write
V/f Mid VoltageVRead and write
V/f Mid FrequencyHzRead and write
Start ModeRead and write
Digital Reference Reset ModeRead and write
DC BrakeRead and write
Spin Start EnableRead and write
Brake ChopperRead and write
AI1 Gain%Read and write
RS485 SettingsRead and write
Password Level 2Read and write
Parameter LockRead and write
AI1 Offset%Read and write
Display ScaleRead and write
PID1 KpRead and write
PID1 TisRead and write
PID1 ModeRead and write
PID1 Setpoint SourceRead and write
PID1 Digital SetpointRead and write
PID1 Feedback SourceRead and write
AI2 Signal RangeRead and write
Standby TimesRead and write
PID1 Wake Up LevelRead and write
CAN Baud RateRead and write
Thermal Memory EnableRead and write
Parameter AccessRead and write
Action on Communication LossRead and write
Relay Output 1 HysteresisRead and write
Relay Output 1 On DelaysRead and write
Modbus ParityRead and write
TCP Enable ServiceRead and write
TCP Security TimeoutRead and write
Motor Control ModeRead and write
Motor IdentificationRead and write
Speed Controller Gain%Read and write
Current Limit%Read and write
Stator ResistanceΩRead and write
Stator Inductance d-AxisRead and write
Stator Inductance q-AxisRead and write
DC Brake Frequency at StopHzRead and write
DC Brake Current%Read and write
Local Control Logic 1Read and write
Local Control Logic 2Read and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show frequency, current and power of each drive on one dashboard for a pump or fan installation.
  • Get an alert when the fault bit is set and see the fault number, such as overcurrent or overtemperature.
  • Watch heatsink temperature over a year of history to spot clogged filters or a failing fan.
  • Change the speed reference of a pump or fan remotely without going to the panel.
  • Check ramp times, frequency limits and motor data of every drive from ModbusCloud.

Installation

  1. Connect the RJ45 interface of the drive to the RS485 port of the ModbusCloud Gateway, with termination at both ends of the bus.

  2. Set the drive address and baud rate in P-36 and the parity in P-56.

  3. Set P-12 to 3 for control over Modbus, or 4 to also send the ramp time.

  4. In ModbusCloud, add a Modbus device with the same settings and import this template.

  5. Check that status word, DC link voltage and heatsink temperature come in before you write a speed reference.

Things to watch for

The drive does not answer on the bus. What should I check?

Check the address and baud rate in P-36 and the parity in P-56 against ModbusCloud. Check the RJ45 wiring and the termination at both ends of the bus. Addresses run from 1 to 63.

Writing the command word or speed reference has no effect. Why?

The drive only takes commands over Modbus when P-12 is 3 or 4. Bit 0 of the command word must be 1 to run; bit 2 resets a fault. The speed reference is in 0.1 Hz and must lie between P-02 and P-01. Depending on P-15 a digital input can also block or override the bus.

Why does writing a parameter fail?

Some parameters, such as motor voltage, motor frequency, control source and input configuration, can only be changed when the drive is stopped. A parameter lock in P-38 or a password can also block writing. Stop the drive, check P-38 and write again.

The drive trips when the connection drops. Is that intended?

The timeout part of P-36 sets this. With 0 the drive keeps running on the last data; t settings trip after 30 ms to 3 s, r settings ramp the motor to a stop. Choose the behavior that is safe for the installation before you control the drive remotely.

Want to see how it works?