Eaton PowerXL DE1
Variable speed starter with speed control, motor current and drive settings.
The Eaton PowerXL DE1 is a variable speed starter that sets the speed of three phase motors in pumps, fans and conveyors with little configuration. This Modbus RTU template reads status, faults, frequency, motor current, DC link voltage and heatsink temperature, and lets you start, stop and set the speed and drive settings from ModbusCloud.
- Protocol
- Modbus RTU
- Connection
- RS485, 115200 baud
- Registers
- 72, read and write
- Brand
- Eaton
- Key readings
- Output frequency · Motor current · DC link voltage · Heatsink temperature · Fault number · Run time
- Available commands
- Command word · Speed reference · Ramp times · Drive settings
- Compatible models
- PowerXL DE1 (DE1-12..., DE1-34...) · PowerXL DE11 (DE11-12..., DE11-34...)
- Last updated
Registers (72)
72 read, 56 write
| Name | Unit | Access | Address (Hidden until you enter your email) | Function (hidden) | Type (hidden) |
|---|---|---|---|---|---|
| Status and Fault Word | Read | ||||
| Actual Speed | Hz | Read | |||
| Motor Current | A | Read | |||
| DC Link Voltage | V | Read | |||
| Heatsink Temperature | °C | Read | |||
| Analog Input 1 | % | Read | |||
| Digital Inputs | Read | ||||
| Run Time Hours | h | Read | |||
| Run Time Min Sec | Read | ||||
| Last Fault | Read | ||||
| Fieldbus Command | Read and write | ||||
| Speed Reference | Hz | Read and write | |||
| Starter Type Code | Read | ||||
| Starter Power | Read | ||||
| Voltage Range | V | Read | |||
| Control Software Version | Read | ||||
| Power Software Version | Read | ||||
| Starter Recognition | Read | ||||
| Maximum Frequency | Hz | Read and write | |||
| Minimum Frequency | Hz | Read and write | |||
| Acceleration Time | s | Read and write | |||
| Deceleration Time | s | Read and write | |||
| Stop Mode | Read and write | ||||
| Energy Optimizer | Read and write | ||||
| Motor Nominal Voltage | V | Read and write | |||
| Motor Nominal Current | A | Read and write | |||
| Motor Nominal Frequency | Hz | Read and write | |||
| Motor Nominal Speed | rpm | Read and write | |||
| Voltage Boost | % | Read and write | |||
| Control Source | Read and write | ||||
| Password | Read and write | ||||
| Digital Input Configuration | Read and write | ||||
| AI1 Signal Range | Read and write | ||||
| AI1 Gain | Read and write | ||||
| AI1 Invert | Read and write | ||||
| DI3 Logic | Read and write | ||||
| Fixed Frequency 1 | Hz | Read and write | |||
| Fixed Frequency 2 | Hz | Read and write | |||
| Fixed Frequency 3 | Hz | Read and write | |||
| Fixed Frequency 4 | Hz | Read and write | |||
| Digital Reference Reset Mode | Read and write | ||||
| DC Brake | Read and write | ||||
| DC Brake Time at Stop | s | Read and write | |||
| DC Brake Voltage | % | Read and write | |||
| DC Brake Frequency at Stop | Hz | Read and write | |||
| Switching Frequency | Read and write | ||||
| Start Mode | Read and write | ||||
| Overvoltage Control | Read and write | ||||
| Auto Thermal Management | Read and write | ||||
| Thermal Memory Enable | Read and write | ||||
| PDP Address | Read and write | ||||
| RS485 Baud Rate | Read and write | ||||
| Modbus Timeout | Read and write | ||||
| Parameter Set | Read and write | ||||
| Password Level 2 | Read and write | ||||
| Parameter Lock | Read and write | ||||
| Action on Communication Loss | Read and write | ||||
| Parameter Access | Read and write | ||||
| Skip Band 1 | Read and write | ||||
| Skip Frequency 1 | Read and write | ||||
| AI1 Offset | Read and write | ||||
| Fire Mode Function | Read and write | ||||
| Motor Identification | Read and write | ||||
| Modbus Address | Read and write | ||||
| Modbus Data Format | Read and write | ||||
| CAN Baud Rate | Read and write | ||||
| Relay Output 1 Function | Read and write | ||||
| Relay Output 1 Upper Limit | Read and write | ||||
| Relay Output 1 Hysteresis | Read and write | ||||
| Relay Output 1 On Delay | Read and write | ||||
| TCP Enable Service | Read and write | ||||
| TCP Security Timeout | Read and write |
Loading registers…
Send your device list
If a device is not in the library yet, we build the template for free as soon as we have the register data.
Use cases
- Show frequency, motor current and fault state of every starter on one dashboard for a pump or ventilation installation.
- Get an alert when the fault bit comes on and see the fault number, such as overcurrent or overtemperature.
- Follow the heatsink temperature over a year of history to spot a blocked cabinet fan or a dirty filter.
- Change the speed of a fan or pump remotely, without going to the cabinet.
- Check ramp times, frequency limits and motor data of every starter from ModbusCloud.
Installation
Connect pins 7 (A) and 8 (B) of the RJ45 port to the RS485 port of the ModbusCloud Gateway, with a 120 ohm termination at both ends of the bus.
Set the Modbus address in P-47, the baud rate in P-35 and parity and stop bits in P-48.
Set P-12 to 3 for control over Modbus and wire an enable to DI1 or DI2.
Add a Modbus device in ModbusCloud with the same settings and import this template.
Check that the status word, DC link voltage and heatsink temperature come in before you write a speed.
Things to watch for
The starter does not answer on the bus. What should I check?
Compare the address in P-47, the baud rate in P-35 and the parity and stop bits in P-48 with the settings in ModbusCloud. The factory baud rate is 115.2 kbit/s. Check the A and B wires on pins 7 and 8 of the RJ45 plug and the termination at both ends of the bus.
Writing the command word or speed reference has no effect. Why?
The starter only accepts commands over Modbus when P-12 is 3, and it still needs an enable signal on DI1 or DI2. Bit 0 of the command word must be 1 to run; bit 2 resets a fault. The speed reference is in 0.1 Hz and must lie between P-02 and P-01.
Why does writing a setting fail?
Settings such as frequency limits, motor data and the input configuration can only be changed while the starter is stopped. A parameter lock in P-39 or P-41 also blocks writing. Stop the motor, check P-39 and P-41 and write again.
The starter stops or trips when the connection drops. Is that intended?
P-36 sets the time after a communication loss and P-40 the reaction: continue, warn, ramp to stop, coast or trip. With P-36 at 0 nothing happens. Choose what is safe for the installation before you control the starter remotely.
More Eaton templates