Eaton PowerXL DE1

Variable speed starter with speed control, motor current and drive settings.

The Eaton PowerXL DE1 is a variable speed starter that sets the speed of three phase motors in pumps, fans and conveyors with little configuration. This Modbus RTU template reads status, faults, frequency, motor current, DC link voltage and heatsink temperature, and lets you start, stop and set the speed and drive settings from ModbusCloud.

Protocol
Modbus RTU
Connection
RS485, 115200 baud
Registers
72, read and write
Brand
Eaton
Key readings
Output frequency · Motor current · DC link voltage · Heatsink temperature · Fault number · Run time
Available commands
Command word · Speed reference · Ramp times · Drive settings
Compatible models
PowerXL DE1 (DE1-12..., DE1-34...) · PowerXL DE11 (DE11-12..., DE11-34...)
Last updated

Registers (72)

72 read, 56 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
Status and Fault WordRead
Actual SpeedHzRead
Motor CurrentARead
DC Link VoltageVRead
Heatsink Temperature°CRead
Analog Input 1%Read
Digital InputsRead
Run Time HourshRead
Run Time Min SecRead
Last FaultRead
Fieldbus CommandRead and write
Speed ReferenceHzRead and write
Starter Type CodeRead
Starter PowerRead
Voltage RangeVRead
Control Software VersionRead
Power Software VersionRead
Starter RecognitionRead
Maximum FrequencyHzRead and write
Minimum FrequencyHzRead and write
Acceleration TimesRead and write
Deceleration TimesRead and write
Stop ModeRead and write
Energy OptimizerRead and write
Motor Nominal VoltageVRead and write
Motor Nominal CurrentARead and write
Motor Nominal FrequencyHzRead and write
Motor Nominal SpeedrpmRead and write
Voltage Boost%Read and write
Control SourceRead and write
PasswordRead and write
Digital Input ConfigurationRead and write
AI1 Signal RangeRead and write
AI1 GainRead and write
AI1 InvertRead and write
DI3 LogicRead and write
Fixed Frequency 1HzRead and write
Fixed Frequency 2HzRead and write
Fixed Frequency 3HzRead and write
Fixed Frequency 4HzRead and write
Digital Reference Reset ModeRead and write
DC BrakeRead and write
DC Brake Time at StopsRead and write
DC Brake Voltage%Read and write
DC Brake Frequency at StopHzRead and write
Switching FrequencyRead and write
Start ModeRead and write
Overvoltage ControlRead and write
Auto Thermal ManagementRead and write
Thermal Memory EnableRead and write
PDP AddressRead and write
RS485 Baud RateRead and write
Modbus TimeoutRead and write
Parameter SetRead and write
Password Level 2Read and write
Parameter LockRead and write
Action on Communication LossRead and write
Parameter AccessRead and write
Skip Band 1Read and write
Skip Frequency 1Read and write
AI1 OffsetRead and write
Fire Mode FunctionRead and write
Motor IdentificationRead and write
Modbus AddressRead and write
Modbus Data FormatRead and write
CAN Baud RateRead and write
Relay Output 1 FunctionRead and write
Relay Output 1 Upper LimitRead and write
Relay Output 1 HysteresisRead and write
Relay Output 1 On DelayRead and write
TCP Enable ServiceRead and write
TCP Security TimeoutRead and write

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Show frequency, motor current and fault state of every starter on one dashboard for a pump or ventilation installation.
  • Get an alert when the fault bit comes on and see the fault number, such as overcurrent or overtemperature.
  • Follow the heatsink temperature over a year of history to spot a blocked cabinet fan or a dirty filter.
  • Change the speed of a fan or pump remotely, without going to the cabinet.
  • Check ramp times, frequency limits and motor data of every starter from ModbusCloud.

Installation

  1. Connect pins 7 (A) and 8 (B) of the RJ45 port to the RS485 port of the ModbusCloud Gateway, with a 120 ohm termination at both ends of the bus.

  2. Set the Modbus address in P-47, the baud rate in P-35 and parity and stop bits in P-48.

  3. Set P-12 to 3 for control over Modbus and wire an enable to DI1 or DI2.

  4. Add a Modbus device in ModbusCloud with the same settings and import this template.

  5. Check that the status word, DC link voltage and heatsink temperature come in before you write a speed.

Things to watch for

The starter does not answer on the bus. What should I check?

Compare the address in P-47, the baud rate in P-35 and the parity and stop bits in P-48 with the settings in ModbusCloud. The factory baud rate is 115.2 kbit/s. Check the A and B wires on pins 7 and 8 of the RJ45 plug and the termination at both ends of the bus.

Writing the command word or speed reference has no effect. Why?

The starter only accepts commands over Modbus when P-12 is 3, and it still needs an enable signal on DI1 or DI2. Bit 0 of the command word must be 1 to run; bit 2 resets a fault. The speed reference is in 0.1 Hz and must lie between P-02 and P-01.

Why does writing a setting fail?

Settings such as frequency limits, motor data and the input configuration can only be changed while the starter is stopped. A parameter lock in P-39 or P-41 also blocks writing. Stop the motor, check P-39 and P-41 and write again.

The starter stops or trips when the connection drops. Is that intended?

P-36 sets the time after a communication loss and P-40 the reaction: continue, warn, ramp to stop, coast or trip. With P-36 at 0 nothing happens. Choose what is safe for the installation before you control the starter remotely.

Want to see how it works?