FoxESS FoxESS H3 Series Hybrid Inverter (grid) Modbus RTU template

FoxESS H3 Series Hybrid Inverter (grid)

The FoxESS H3 Series Hybrid Inverter is a three-phase hybrid solar inverter designed for residential and light-commercial PV-plus-battery installations. It converts PV power to AC, charges a connected battery, and can feed surplus energy into the grid. This ModbusCloud template reads the H3 Series grid-side registers over Modbus RTU via RS485: per-phase active power on phases R, S, and T (registers 31026 to 31028, signed watts, positive export, negative import) and a cumulative energy counter at register 32012. Connecting these four registers to the ModbusCloud portal gives installers continuous visibility of grid exchange on every phase without relying on the FoxESS cloud.

Protocol
Modbus RTU
Connection
RS485
Registers
4, read only
Brand
FoxESS
Last updated

Registers (4)

4 read, 0 write

NameUnitAccessAddress (Hidden until you enter your email)Function (hidden)Type (hidden)
power_aWRead
power_bWRead
power_cWRead
energyRead

Loading registers…

Send your device list

If a device is not in the library yet, we build the template for free as soon as we have the register data.

Number of installations (optional)

Use cases

  • Monitor per-phase grid power in real time to verify balanced three-phase loading across R, S, and T.
  • Alert on sustained negative values on any phase to detect unexpected grid import during peak PV hours.
  • Track the cumulative energy counter over time to report monthly grid-export totals for feed-in tariff billing.
  • Compare phase R, S, and T power readings to identify phase imbalance caused by single-phase loads.
  • Verify that export-limiting is working correctly by checking that phase power stays below the contractual threshold.

Installation

  1. On the FoxESS H3 Series front panel, navigate to Settings > Communication > RS485 > Device ID and set the Modbus slave ID to 247 (the inverter ships with a default of 000).

  2. Connect the ModbusCloud Gateway to the inverter RS485 port: wire RS485-A to pin 4 and RS485-B to pin 3 of the inverter's CT/COM connector using a twisted-pair cable such as a section of CAT5.

  3. In the ModbusCloud portal, add a new device, select the FoxESS H3 Series Hybrid Inverter (grid) template, and assign the unit ID 247 that you set on the inverter front panel.

  4. Spot-check the connection by reading register 31026 live in the portal: at midday with active PV production you should see a positive watt value on phase R confirming successful communication.

Things to watch for

All three phase power registers return zero. What is wrong?

The most common cause is that the RS485 slave ID on the inverter is still at its factory default of 000. Navigate to Settings > Communication > RS485 > Device ID on the inverter panel and set it to 247. Also check that the A and B wires are not swapped: a constantly flashing RX LED on the RS485 adapter with no TX response is a reliable sign of reversed polarity.

The Gateway connects but phase readings seem inverted or wrong sign.

Registers 31026 to 31028 are signed int16 values where positive indicates export to the grid and negative indicates import from the grid. If your readings are consistently opposite to what you expect, confirm that the smart meter or CT clamp connected to the inverter is wired in the correct direction according to the FoxESS installation manual.

Can I connect the ModbusCloud Gateway via the inverter's Ethernet port?

No. The FoxESS H3 Series does not expose Modbus on its Ethernet port. TCP port 502 is not open on the H3's LAN interface. Modbus RTU over RS485 is the only supported path. Use an RS485 to USB or RS485 to serial adapter connected to the inverter's CT/COM connector.

The energy register at 32012 shows an unexpectedly large value. Is this correct?

Register 32012 is a uint32 cumulative counter and holds the total lifetime grid energy, not a daily or session value. The raw register value may require a scaling factor applied by your integration layer to convert it to the correct engineering unit. Cross-check against the FoxESS app or display to confirm the absolute reading matches.

Want to see how it works?